Manual Sun Microsystems 1800

90 pages 3.07 mb
Download

Go to site of 90

Summary
  • Sun Microsystems 1800 - page 1

    901 San Antonio Road Palo Alto, CA 94303-4900 USA 650 960-1300 Fax 650 969-9131 Netra ™ ft 1800 Installation Guide Part No.: 805-4533-10 Revision A, February 1999 Sun Microsystems, Inc. Send comments about this document to: docfeedback@sun.com ...

  • Sun Microsystems 1800 - page 2

    Please Recycle Copyright 1999 Sun Microsystems, Inc., 901 San Antonio Road • Palo Alto, CA 94303 USA. All rights reserved. This product or document is protected by copyright and distributed under licenses restricting its use, copying, distribution, and decompilation. No part of this product or document may be reproduced in any form by any means w ...

  • Sun Microsystems 1800 - page 3

    iii Contents 1. Before Installation 1 Electrical Supply Considerations 1 Environmental Considerations 1 Dimensions 2 Airflow Consideration when Mounting in the Equipment Frame 2 Mechanical Considerations when Mounting in the Equipment Frame 6 Mounting Requirements 6 2. Hardware Installation 9 Unshipping and Mounting the System 9 Mounting Flanges 13 ...

  • Sun Microsystems 1800 - page 4

    iv Netra ft 1800 Installation Guide • February 1999 Installing the Filter T rays 36 CAF External I/O Connections 38 System Console T erminal Connections 39 Modem Port Connections 40 Alarms Port Connections 41 3. Electrical Supply Installation 43 System Switch 43 DC Source Site Requir ements 44 Overcurr ent Pr otection Requirements 44 Required Con ...

  • Sun Microsystems 1800 - page 5

    Contents v 6. Installing and Conf iguring Sun StorEdge V olume Manager 65 Before Y ou Install Sun StorEdge V olume Manager 65 Installing the V olume Manager Software 67 Mounting the CD-ROM Manually 67 Running the Installation 67 Setting up the V olume Manager Environment 68 Initializing the V olume Manager 69 Setting up Boot Disks 70 Setting up Oth ...

  • Sun Microsystems 1800 - page 6

    vi Netra ft 1800 Installation Guide • February 1999 ...

  • Sun Microsystems 1800 - page 7

    vii Figur es FIGURE 1-1 Netra ft 1800 Airflow Requirements (External) 4 FIGURE 1-2 Netra ft 1800 Airflow Requirements (Internal) 5 FIGURE 2-1 Shipping Brackets and Sacrificial Plinth 11 FIGURE 2-2 Location Matrix For Mounting Flange Screws (19-inch rack) 14 FIGURE 2-3 Support Rail and Fixings (19-inch Rack) 15 FIGURE 2-4 Orientation of Support Rail ...

  • Sun Microsystems 1800 - page 8

    viii Netra ft 1800 Installation Guide • February 1999 FIGURE 2-18 Removing a DSK Module 34 FIGURE 2-19 Cable Management Shelf 35 FIGURE 2-20 Large Filter Tray 36 FIGURE 2-21 Small Filter Tray 37 FIGURE 2-22 External I/O Connections on CAF Module 38 FIGURE 3-1 Circuit Breakers for Single Power Rails 46 FIGURE 3-2 Circuit Breakers for Dual Power Ra ...

  • Sun Microsystems 1800 - page 9

    ix T ables T ABLE 1-1 Mounting Hole Pattern Dimensions 7 T ABLE 2-1 19-inch Mounting Flange Kit 13 T ABLE 2-2 Support Rail Screw Hole Locations 15 T ABLE 2-3 23-inch, 24-inch and 600mm Mounting Flange Kits 18 T ABLE 2-4 Console Connector Pinout 39 T ABLE 2-5 Console and Modem Port Parameters 39 T ABLE 2-6 Modem Port Pinout 40 T ABLE 2-7 Alarms Port ...

  • Sun Microsystems 1800 - page 10

    x Netra ft 1800 Installation Guide • February 1999 ...

  • Sun Microsystems 1800 - page 11

    xi Pr eface This document describes the installation procedures for the core har dwar e and software used in the Netra ™ ft 1800. Upon completion of the procedur es in this manual, the Netra ft 1800 is fully functional as a fault-tolerant Solaris ™ server . Who Should Use This Book This guide is intended to be read by installation engineers, so ...

  • Sun Microsystems 1800 - page 12

    xii Netra ft 1800 Installation Guide • February 1999 Chapter 6 “Installing and Conf iguring Sun StorEdge V olume Manager” summarizes what you need to know in order to use the V olume Manager on the Netra ft 1800. Related Books ■ Netra ft 1800 Software Release Notes (Part No. 805-4527-10) ■ Netra ft 1800 Hardware Release Notes (Part No. 80 ...

  • Sun Microsystems 1800 - page 13

    Preface xiii Shell Pr ompts in Command Examples The following table shows the default Open Boot PROM (OBP) prompt and the system prompt and superuser pr ompt for the C shell, Bourne shell, and Korn shell. Symbols The following symbols mean: Note – A note provides information which should be consider ed by the reader . Caution – Cautions accompa ...

  • Sun Microsystems 1800 - page 14

    xiv Netra ft 1800 Installation Guide • February 1999 Sun Documentation on the W eb The docs.sun.com sm web site enables you to access Sun technical documentation on the W eb. Y ou can browse the docs.sun.com archive or sear ch for a specif ic book title or subject at: http://docs.sun.com Sun W elcomes Y our Comments W e are interested in improvin ...

  • Sun Microsystems 1800 - page 15

    1 CHAPTER 1 Befor e Installation This section provides information on what should be consider ed when choosing a location for a Netra ft 1800 system. Note – This equipment is only intended for installation in a Restricted Access Location as defined by UL1950, 3r d Edition, and EN60950: 1992 / A1 1: 1997. Electrical Supply Considerations Before yo ...

  • Sun Microsystems 1800 - page 16

    2 Netra ft 1800 Installation Guide • February 1999 ■ Relative humidity ■ Operating: 5 to 85% noncondensing 1 ■ Storage: 10 to 90% noncondensing 1 ■ Elevation ■ Operating: 0 to 3000 meters ■ Storage: 0 to 12000 meters Dimensions ■ Height: 1466.85 mm (57.75 inches) 33U NOM ■ W idth: 437.60 mm (17.22 inches) ■ Depth: 392.8 mm (15.4 ...

  • Sun Microsystems 1800 - page 17

    Chapter 1 Bef ore Installation 3 3. A minimum of 2U (88.9 mm/3.5 inches) clearance must be allowed at both top and bottom of the Netra ft 1800 cabinet when mounted to allow adequate inlet and exhaust ventilation. 4. The Netra ft 1800 system must not be mounted above any heat-generating sources within the same frame unless a heat deflector is used t ...

  • Sun Microsystems 1800 - page 18

    4 Netra ft 1800 Installation Guide • February 1999 FIGURE 1-1 Netra ft 1800 Airflow Requirements (External) Minimum 2U (90 mm) gap Minimum 2U (90 mm) gap ...

  • Sun Microsystems 1800 - page 19

    Chapter 1 Bef ore Installation 5 FIGURE 1-2 Netra ft 1800 Airflow Requirements (Internal) F ront Rear F ront Rear F ront F an unit CPU PSU PSU PSU PSU PSU PSU CPU CPU CAF CAF CAF CAF Min. 75 mm between front of system and rac k door (if fitted) Min. 2U (90 mm) gap at top of system Min. 2U (90 mm) gap at base of system ...

  • Sun Microsystems 1800 - page 20

    6 Netra ft 1800 Installation Guide • February 1999 Mechanical Considerations when Mounting in the Equipment Frame Caution – Mechanical assistance is requir ed if installing a loaded chassis. If you intend not to use a lifting device for installation, all modules other than the motherboards must be r emoved from the system prior to lifting. The ...

  • Sun Microsystems 1800 - page 21

    Chapter 1 Bef ore Installation 7 Adjustable rear f langes can be fitted. They pr ovide a mounting face anywhere between 400 mm and 500 mm (15.75 inches and 19.7 inches) from the front of the system (see “Mounting Flanges” on page 13). The vertical mounting hole pattern should conform to the standar d dimensions given in T ABLE 1- 1 . Loading Th ...

  • Sun Microsystems 1800 - page 22

    8 Netra ft 1800 Installation Guide • February 1999 Depth The front door (if f itted) must provide a minimum of 75 mm (3 inches) of clearance across the entir e front surface of the Netra ft 1800 to allow for routing of I/O cables. As all I/O cables must be routed fr om the front of the Netra ft 1800 system, due consideration should be made of the ...

  • Sun Microsystems 1800 - page 23

    9 CHAPTER 2 Har dwar e Installation This chapter provides information on the initial har dware installation pr ocedure, including installing modules and external I/O connections. Unshipping and Mounting the System Once you have removed the packaging from the system, you must then unship the system from the delivery pallet and brackets before attemp ...

  • Sun Microsystems 1800 - page 24

    10 Netra ft 1800 Installation Guide • February 1999 Note – Do not discard the tools after unshipping and mounting the system. They can be stored in the cloth bag supplied and attached to the rack adjacent to the system for easy access when requir ed. ...

  • Sun Microsystems 1800 - page 25

    Chapter 2 Hardware Installation 11 ▼ T o Unship and Mount the System FIGURE 2-1 Shipping Brackets and Sacrificial Plinth 2 x Allen bolts securing brack et to pallet 4 x Phillips screws at front of plinth 3 x Phillips screws at rear of plinth 2 x Phillips screws on each brac ket Inser t lifting de vice here ...

  • Sun Microsystems 1800 - page 26

    12 Netra ft 1800 Installation Guide • February 1999 1. Remove all modules except the motherboards from the chassis and put them in a safe place. Refer to “Removing and Installing Modules” on page 23. 2. Using the Phillips No.2 screwdriver (supplied), remove the two Phillips screws securing the four red brackets (two on each side) to the chass ...

  • Sun Microsystems 1800 - page 27

    Chapter 2 Hardware Installation 13 Mounting Flanges The system is supplied with the appropriate mounting f langes; other mounting flanges kits ar e available, as follows, to enable the system to mounted in differ ent industry-standard racks: ■ 19-inch racks X-Option No. X6938A ■ 23-inch racks X-Option No. X6939A ■ 24-inch racks X-Option No. X ...

  • Sun Microsystems 1800 - page 28

    14 Netra ft 1800 Installation Guide • February 1999 The sides of the system chassis are pr ovided with tapped screwholes as shown in FIGURE 2-2 . FIGURE 2-2 Location Matrix For Mounting Flange Screws (19-inch rack) The front f langes (see FIGURE 2-6 on page 17) ar e screwed to holes in column C or column D. Use column B only if the rear f langes ...

  • Sun Microsystems 1800 - page 29

    Chapter 2 Hardware Installation 15 FIGURE 2-3 Support Rail and Fixings (19-inch Rack) The mounting screws should be placed in position pairs E1 and F1, E2 and F2, E3 and F3, E4 and F4 or E5 and F5. The pair of holes to be used depends on the front- to-back depth of the rack (mounting flange to mounting f lange). The holes marked with the appropriat ...

  • Sun Microsystems 1800 - page 30

    16 Netra ft 1800 Installation Guide • February 1999 FIGURE 2-4 Orientation of Support Rail Spacers The rear f langes are used to mount the chassis in the r ear of the rack as shown in FIGURE 2-5 . FIGURE 2-5 Rear Rack Mounting (19-inch Rack) Chassis Suppor t r ail (340-5484) Spacer (340-5483) Screw Chassis Rack Rear flange (340-5479/5480) Spacer ...

  • Sun Microsystems 1800 - page 31

    Chapter 2 Hardware Installation 17 FIGURE 2-6 19-inch Rack Mounting Flange Kit Rear top mounting flange (left 340-5479 right 340-5480) Use M4 10mm screws Rear bottom mounting flange (left 340-5481 right 340-5482) Use M4 10mm screws F ront mounting flange (left 340-4699 right 340-4698) Use M5 8mm screws Spacer (340-5483) Suppor t r ail (340-5484) ...

  • Sun Microsystems 1800 - page 32

    18 Netra ft 1800 Installation Guide • February 1999 23-inch, 24-inch and 600mm Mountings The 23-inch, 24-inch and 600mm mounting kits consist of the following items: Refer to FIGURE 2-7 on page 19 for 23-inch kits, FIGURE 2-8 on page 20 for 24-inch kits and FIGURE 2-9 on page 21 for 600mm kits. The sides of the system chassis are pr ovided with t ...

  • Sun Microsystems 1800 - page 33

    Chapter 2 Hardware Installation 19 FIGURE 2-7 23-inch Rack Mounting Flange Kit F ront mounting flange (left 340-4592 right 340-4591) Use M5 6mm screws Slide suppor t (340-5330) Use M5 8mm screws Rear top mounting flange (340-5449) Use M5 6mm screws Rear bottom mounting flange (340-5450) Use M5 6mm screws ...

  • Sun Microsystems 1800 - page 34

    20 Netra ft 1800 Installation Guide • February 1999 FIGURE 2-8 24-inch Rack Mounting Flange Kit F ront mounting flange (left 340-5445 right 340-5446) Use M5 6mm screws Slide suppor t (340-5330) Use M5 8mm screws Rear top mounting flange (340-5447) Use M5 6mm screws Rear bottom mounting flange (340-5448) Use M5 6mm screws ...

  • Sun Microsystems 1800 - page 35

    Chapter 2 Hardware Installation 21 FIGURE 2-9 600-mm Rack Mounting Flange Kit F ront mounting flange (left 340-5328 right 340-5329) Use M5 6mm screws Slide suppor t (340-5330) Use M5 8mm screws Rear top mounting flange (340-5331) Use M5 6mm screws Rear bottom mounting flange (340-5427) Use M5 6mm screws ...

  • Sun Microsystems 1800 - page 36

    22 Netra ft 1800 Installation Guide • February 1999 Cable Bracket Assemblies Six cable bracket mounting assemblies are pr ovided with each mounting flange kit. These can be fitted to the mounting f langes to facilitate cable management. FIGURE 2-10 Cable Bracket Assembly The brackets can be fixed to the mounting f langes in the requir ed position ...

  • Sun Microsystems 1800 - page 37

    Chapter 2 Hardware Installation 23 Removing and Installing Modules This chapter describes how to remove and insert: ■ CPUset, PCI, CAF and PSU modules (“T o Remove a Module” on page 24) ■ CPUset modules: “CPUset Modules” on page 25 ■ PCI modules: “PCI Modules” on page 28 ■ CAF modules: “CAF Modules” on page 27 ■ PSU module ...

  • Sun Microsystems 1800 - page 38

    24 Netra ft 1800 Installation Guide • February 1999 FIGURE 2-11 Module Injector/ejector Lever The module is disengaged from its electrical connection when the slide is moved towards the r ounded end of the lever , exposing the red warning dot. The general procedur e refers to CPUset, CAF , PCI and PSU modules. For more specific instructions for t ...

  • Sun Microsystems 1800 - page 39

    Chapter 2 Hardware Installation 25 CPUset Modules CPUset modules have two injector levers which must be operated simultaneously . As you pull out the CPUset module, the handle in the top panel pops up and must be depressed again manually in or der to withdraw the module fully from the chassis (see FIGURE 2-12 ). Once the handle is clear of the cros ...

  • Sun Microsystems 1800 - page 40

    26 Netra ft 1800 Installation Guide • February 1999 FIGURE 2-12 Removing a CPUset Module ...

  • Sun Microsystems 1800 - page 41

    Chapter 2 Hardware Installation 27 CAF Modules FIGURE 2-13 Removing a CAF ...

  • Sun Microsystems 1800 - page 42

    28 Netra ft 1800 Installation Guide • February 1999 PCI Modules FIGURE 2-14 Removing a PCI Card Carrier ...

  • Sun Microsystems 1800 - page 43

    Chapter 2 Hardware Installation 29 PSU Modules FIGURE 2-15 Removing a Power Supply ...

  • Sun Microsystems 1800 - page 44

    30 Netra ft 1800 Installation Guide • February 1999 ▼ T o Replace a Module 1. Slide the module into its slot but not fully home. A module will not fit into a slot designed for a differ ent class of module. 2. When the lever engages with the chassis, raise it to push the module fully home. 3. Move the slide in the lever into the engaged position ...

  • Sun Microsystems 1800 - page 45

    Chapter 2 Hardware Installation 31 FIGURE 2-16 Removing an RMM Module ...

  • Sun Microsystems 1800 - page 46

    32 Netra ft 1800 Installation Guide • February 1999 ▼ T o Replace the RMM 1. Slide the RMM into its slot until it is almost completely home. A module will not fit into a slot designed for a differ ent class of module. 2. Lower the handle to engage the RMM fully in its slot. 3. Slide the latch in the handle to the right (towards the ‘locked’ ...

  • Sun Microsystems 1800 - page 47

    Chapter 2 Hardware Installation 33 FIGURE 2-17 Removing a Disk Drive NO TE: The injector/ejector le v er of a disk drive module does not s witch the power on and off . If the chassis is powered on, the disk driv e will power off when it is remov ed and pow er on as soon as it is inser ted, regardless of the position of the le ver . ...

  • Sun Microsystems 1800 - page 48

    34 Netra ft 1800 Installation Guide • February 1999 FIGURE 2-18 Removing a DSK Module ▼ T o Replace the Disk Chassis 1. Slide the disk chassis into its slot until it is almost completely in. 2. Lower the handle to engage the disk chassis fully in its slot. 3. Slide the latch in the handle to the right (towards the ‘locked’ symbol). 4. Repla ...

  • Sun Microsystems 1800 - page 49

    Chapter 2 Hardware Installation 35 Flexible Module Cabling The cable management shelf is illustrated in FIGURE 2-19 . FIGURE 2-19 Cable Management Shelf The cable management shelf adjacent to the PCI card locations is flexible and can be used in a number of differ ent configurations. The holes are equidistant, and the hooks can be inserted in whate ...

  • Sun Microsystems 1800 - page 50

    36 Netra ft 1800 Installation Guide • February 1999 Installing the Filter T rays The Netra ft 1800 has three filter trays, two lar ge and one small. ▼ T o Install the Filter T rays FIGURE 2-20 Large Filter T ray ...

  • Sun Microsystems 1800 - page 51

    Chapter 2 Hardware Installation 37 FIGURE 2-21 Small Filter T ray 1. Insert the trays into the appropriate apertures at the base of the chassis; the two large trays are f itted on the left and the small tray on the right. It is unimportant which way up the trays are fitted. 2. Push the trays securely home and hand-tighten the two thumbscrews on eac ...

  • Sun Microsystems 1800 - page 52

    38 Netra ft 1800 Installation Guide • February 1999 CAF External I/O Connections The Netra ft 1800 system has the following connectors on each CAF module: ■ Female 25-pole D-type connectors for the system console and modem ports (RS232). ■ A male 9-pole D-type connector for the Remote Control Pr ocessor (RCP) ports. ■ A male 15-pole D-type ...

  • Sun Microsystems 1800 - page 53

    Chapter 2 Hardware Installation 39 System Console T erminal Connections The system console and modem connections are provided on separate 25-pole female D-type connectors. T ABLE 2-4 shows the pin allocation on these connectors. Except for pin 1, all pins of the console and modem connectors are isolated from the frame ground of the Netra ft 1800 sy ...

  • Sun Microsystems 1800 - page 54

    40 Netra ft 1800 Installation Guide • February 1999 System consoles can be connected only to the CAF module. Modem Port Connections The modem port pinout is described in T ABLE 2-6 . Stop bits 1 Parity enable/sense off/of f XON/XOFF protocol on T ABLE 2-6 Modem Port Pinout Pin Function Description 1 GND Chassis ground 2 TxD Output data 3 RxD Inpu ...

  • Sun Microsystems 1800 - page 55

    Chapter 2 Hardware Installation 41 Alarms Port Connections The alarms port pinout is described in T ABLE 2-7 . T ABLE 2-7 Alarms Port Pinout Pin Description Pin Description 1 RESET0+ 9 ALARM0-NC 2 RESET0- 10 ALARM0-COM 3 RESET1+ 11 ALARM1-NO 4 RESET1- 12 ALARM1-NC 5 SYSTEM-NO 13 ALARM1-COM 6 SYSTEM-NC 14 ALARM2-NO 7 SYSTEM-COM 15 ALARM2-COM 8 ALARM ...

  • Sun Microsystems 1800 - page 56

    42 Netra ft 1800 Installation Guide • February 1999 ...

  • Sun Microsystems 1800 - page 57

    43 CHAPTER 3 Electrical Supply Installation This chapter provides information about the Netra ft 1800 system switches and the installation of the electrical supply . See the Netra ft 1800 Hardware Reference Manual for full details of the electrical supply hardware. The Netra ft 1800 has six power input feed pairs, three for each side, which plug in ...

  • Sun Microsystems 1800 - page 58

    44 Netra ft 1800 Installation Guide • February 1999 Note – The system On and Stby switches handle low voltage signals only; the high- power circuits do not pass thr ough these switches. DC Sour ce Site Requir ements The DC source site r equirements ar e as follows: ■ Suitable for use in –48 Vdc ((classified SEL V) nominal or –60 Vdc (clas ...

  • Sun Microsystems 1800 - page 59

    Chapter 3 Electrical Supply Installation 45 Caution – Double pole circuit br eakers are r equired on each rail for DC installations. This is necessary because the return path of the current is not isolated in the PSU. FIGURE 3-1 on page 3-46 shows the required arrangement for single power rails. FIGURE 3-2 on page 3-47 shows the required arrangem ...

  • Sun Microsystems 1800 - page 60

    46 Netra ft 1800 Installation Guide • February 1999 FIGURE 3-1 Circuit Br eakers for Single Power Rails CB R TN B R TN A –48V A –48V B R TN B R TN BA –48V A –48V B R TN B R TN A –48V A –48V B R TN B R TN A –48V A –48V B R TN B R TN A –48V A –48V B R TN B R TN A –48V A –48V B CB CB CB CB CB CB CB CB CB CB CB –48V supply A ...

  • Sun Microsystems 1800 - page 61

    Chapter 3 Electrical Supply Installation 47 FIGURE 3-2 Circuit Br eakers for Dual Power Rails CB R TN B R TN A –48V A –48V B R TN B R TN A –48V A –48V B R TN B R TN A –48V A –48V B R TN B R TN A –48V A –48V B R TN B R TN A –48V A –48V B R TN B R TN A –48V A –48V B CB CB CB CB CB CB CB CB CB CB CB –48V supply A –48V suppl ...

  • Sun Microsystems 1800 - page 62

    48 Netra ft 1800 Installation Guide • February 1999 Requir ed Connection Materials DC branch circuits: ■ The requir ed number of field wiring kits ar e supplied in the shipkit with each system, according to conf iguration. Grounding: ■ One Thomas & Betts two-hole lug (part number: 54204-UB) suitable for 8 A WG conductor or UL/CSA approved ...

  • Sun Microsystems 1800 - page 63

    Chapter 3 Electrical Supply Installation 49 Dual Gr ounding Envir onment Caution – T o be compatible with grounding environments requiring isolation between logic 0V and chassis ground, the f itted gr ounding bridge plate must be removed and individual connections made to logic 0V and chassis gr ound studs. The grounding bridge plate is located o ...

  • Sun Microsystems 1800 - page 64

    50 Netra ft 1800 Installation Guide • February 1999 FIGURE 3-3 Location of Chassis-to-Logic-0V Link and Grounding Points, and W rist Strap Connection Point Chassis to logic 0V link Grounding studs Wrist strap connection point ...

  • Sun Microsystems 1800 - page 65

    Chapter 3 Electrical Supply Installation 51 Connecting the Power Leads The inlet power filter must be plugged into the power sockets on the motherboards at the back of the Netra ft 1800, then the six power leads must be attached to the input power filter . Note – Disengage all the PSUs before you insert the power connectors. Inserting the connect ...

  • Sun Microsystems 1800 - page 66

    52 Netra ft 1800 Installation Guide • February 1999 ▼ T o Assemble the Power Inlet and Leads 1. Insert the socket in the appropriate slot on the motherboard. The socket can only be inserted one way round. The label on the front of the f ilter indicates the correct orientation. 2. T ighten the captive spring-loaded screws, preferably f inger-tig ...

  • Sun Microsystems 1800 - page 67

    Chapter 3 Electrical Supply Installation 53 4. Insert the leads into the appropriate receptacles in the terminal block. Refer to FIGURE 3-6 . FIGURE 3-6 Power Lead Receptacles 5. T ighten the terminal block power lead M4 securing screws to 1.5-1.8 Nm. Refer to FIGURE 3-7 . FIGURE 3-7 Power Lead Securing Screws Inser t po wer leads here P ower lead ...

  • Sun Microsystems 1800 - page 68

    54 Netra ft 1800 Installation Guide • February 1999 6. Use cable ties to secure the wires to the swivel loops in the mounting bracket (see FIGURE 3-8 ). The loops can be rotated to a convenient position. This strain relief method must be implemented. Caution – Observe correct working practices regar ding the termination of cable ties. FIGURE 3- ...

  • Sun Microsystems 1800 - page 69

    55 CHAPTER 4 Powering on the System This chapter describes the procedure for powering on the Netra ft 1800. ▼ T o Power On the System 1. Prior to powering on, inspect the supply conductors for mechanical security . 2. Activate the external circuit breakers. Note – The power supply units (PSUs) remember their last r equested state. They are ship ...

  • Sun Microsystems 1800 - page 70

    56 Netra ft 1800 Installation Guide • February 1999 4. Push the other On system switch (on the other CAF front panel). FIGURE 4-1 System Switches (Front Panel) The PSU, CPUset and CAF Power LEDs will successively light, and the terminal will display the output from the Power On Self T est (POST). The POST sequence may take some time. The CPUset L ...

  • Sun Microsystems 1800 - page 71

    57 CHAPTER 5 Softwar e and Operating Envir onment Installation This chapter describes all the steps necessary to install a software and operating environment r elease for the Netra ft 1800. T o perform the steps described here, you should be familiar with the Solaris operating environment. Netra ft 1800 Install Media The release softwar e consists ...

  • Sun Microsystems 1800 - page 72

    58 Netra ft 1800 Installation Guide • February 1999 Installation Methods The Netra ft 1800 supports two types of installation: local , from a local CD-ROM drive; or network , from a machine set up as a Solaris installation server . The requir ements for these two types of installation are described in the following subsections. Y ou must install ...

  • Sun Microsystems 1800 - page 73

    Chapter 5 Software and Oper ating Environment Installation 59 Network Installation T o perform a network installation of the Netra ft 1800 software, you must ensure the following: ■ Access to a SP ARC server on which the Netra ft 1800 software can be installed. (A CD-ROM drive is needed for the initial server installation but need not be present ...

  • Sun Microsystems 1800 - page 74

    60 Netra ft 1800 Installation Guide • February 1999 Befor e Y ou Start Caution – Before inserting a CD-ROM disk into your system r ead “Handling and T aking Care of your CD-ROM Disks” in the Netra ft 1800 Compliance and Safety Manual . In some circumstances if your CD-ROM disk does not have a clean data surface your system may fail to boot. ...

  • Sun Microsystems 1800 - page 75

    Chapter 5 Software and Oper ating Environment Installation 61 b. Insert the Netra ft 1800 CD-ROM in the drive on side A, at the top of the system, or the drive on side B at the bottom of the system. Check that the Power LED is lit on the RMM that contains the CD-ROM drive. 4. Boot the system. a. For local installation, type: if you inserted the CD ...

  • Sun Microsystems 1800 - page 76

    62 Netra ft 1800 Installation Guide • February 1999 Y ou must leave two free slices for Sun StorEdge V olume Manager. The disk layout should have a maximum of five slices, plus the overlap slice, similar to the following: There will be some r ounding differ ences. Y ou must also leave 1024 sectors, or 512K, fr ee for Sun StorEdge V olume Manager ...

  • Sun Microsystems 1800 - page 77

    Chapter 5 Software and Oper ating Environment Installation 63 10. Install the appropriate patches. Refer to the Release Notes accompanying the CD. 1 1. Install the required PCI drivers and, if desired, SunVTS. Refer to the Release Notes accompanying the CD. 5.1 Finishing Installation Finishing installation includes: ■ Appending the path to the Ne ...

  • Sun Microsystems 1800 - page 78

    64 Netra ft 1800 Installation Guide • February 1999 For a C-shell, in your $HOME/.cshrc file type: For a Bourne or Korn shell, in your $HOME/.profile file type: setenv MANPATH ${MANPATH}:/opt/SUNWftm MANPATH=${MANPATH}:/opt/SUNWftm export MANPATH ...

  • Sun Microsystems 1800 - page 79

    65 CHAPTER 6 Installing and Conf iguring Sun StorEdge V olume Manager This section contains guidelines for installing Sun StorEdge V olume Manager to provide fault tolerant mass storage on the Netra ft 1800 system. The main steps involved are: 1. Using pkgadd to load the V olume Manager packages, and install any required patches. 2. Conf iguring th ...

  • Sun Microsystems 1800 - page 80

    66 Netra ft 1800 Installation Guide • February 1999 In the following procedur e, you use cmsconfig to obtain the Disk attribute of the HDD module and the Funct_0 attribute of the CD-ROM drive (plus Funct_1 if you have an additional drive). T o identify the device name of the root disk: 1. Start cmsconfig: 2. Locate the HDD modules in the list. Y ...

  • Sun Microsystems 1800 - page 81

    Chapter 6 Installing and Configuring Sun StorEdge V olume Manager 67 Caution – Failures during the Sun StorEdge V olume Manager boot disk encapsulation process could r esult in loss of data on the root f ile system. Caution – Encapsulation of the boot disk will requir e that the installed system is shutdown and rebooted several times. Installin ...

  • Sun Microsystems 1800 - page 82

    68 Netra ft 1800 Installation Guide • February 1999 Setting up the V olume Manager Environment When you have loaded the V olume Manager software, and before you r un vxinstall to initialize it, you must configure the softwar e to run as r equired on the Netra ft 1800. This involves the following: ■ Setting default volume creation to mirr or dis ...

  • Sun Microsystems 1800 - page 83

    Chapter 6 Installing and Configuring Sun StorEdge V olume Manager 69 These commands create a startup script that enables the V olume Manager to exit back to the OBP upon encountering a stale boot plex, allowing the V olume Manager to try alternative boot disks. Enabling Recovery Behavior and Boot Disk Detection T o enable correct recovery behavior ...

  • Sun Microsystems 1800 - page 84

    70 Netra ft 1800 Installation Guide • February 1999 Setting up Boot Disks Y ou must encapsulate the boot disk for Sun StorEdge V olume Manager to be able to mirror it. Y ou are str ongly recommended to do the following to ensure that the boot disk is configur ed for the Netra ft 1800: ■ Assuming that A-DSK0 is the Solaris install disk, you shou ...

  • Sun Microsystems 1800 - page 85

    Chapter 6 Installing and Configuring Sun StorEdge V olume Manager 71 Setting up Other Disks Use vxdiskadm to add disks other than the boot disks to the system as new V olume Manager disks after the vxinstall process is complete. Select option 1, Add or initialize disks. See the Sun StorEdge V olume Manager System Administrator ’ s Guide for full ...

  • Sun Microsystems 1800 - page 86

    72 Netra ft 1800 Installation Guide • February 1999 Boot Disk Aliases Sun StorEdge V olume Manager boot disk aliases are not automatically updated when a disk is physically relocated. Y ou must update boot aliases manually using the eeprom command when you relocate an HDD module. Y ou might prefer to use the aliases defined by the PROM, for examp ...

  • Sun Microsystems 1800 - page 87

    73 Index A airflow clearance, 3 direction of, 2 inlet plenum, 6 natural convection, 2 requir ements, 2 alarms connector, 38 alarms port pinout, 41 B boot device, setting default, 62 boot disk detection, configuring, 69 brackets, removing, 12 C cable bracket assemblies, 13, 22 cable management, 35 cable routing, 8 CAF module connectors, 38 removing, ...

  • Sun Microsystems 1800 - page 88

    74 Netra ft 1800 Installation Guide • F ebruar y 1999 environmental considerations, 1 environmental f ilters, installing, 37 Ethernet address, 60 F filter r eplacement kit, 3 filters, installing, 37 flanges, See mounting f langes frame ground, 49 G GR 63 Core heat r elease calculation result, 2 grounding connections, 51 dual, 48 isolation, 49 mat ...

  • Sun Microsystems 1800 - page 89

    Index 75 O On system switch, 56 ON/STBY switch, 43, 44 operating environment installation, 57 overcurr ent protection, 44 P packaging, 12 partitions, requir ed by V olume Manager, 62 patches, requir ed, 58 P A TH, setting up, 63 PCI card carrier removing, 28 platform, shipping, 12 plinth, mounting, 12 power DC source r equirements, 44 DC supply and ...

  • Sun Microsystems 1800 - page 90

    76 Netra ft 1800 Installation Guide • F ebruar y 1999 W weight empty chassis, 6 maximum, 2 removable modules, 6 ...

Manufacturer Sun Microsystems Category Computer Accessories

Documents that we receive from a manufacturer of a Sun Microsystems 1800 can be divided into several groups. They are, among others:
- Sun Microsystems technical drawings
- 1800 manuals
- Sun Microsystems product data sheets
- information booklets
- or energy labels Sun Microsystems 1800
All of them are important, but the most important information from the point of view of use of the device are in the user manual Sun Microsystems 1800.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals Sun Microsystems 1800, service manual, brief instructions and user manuals Sun Microsystems 1800. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product Sun Microsystems 1800.

A complete manual for the device Sun Microsystems 1800, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use Sun Microsystems 1800 by users. Manuals are usually written by a technical writer, but in a language understandable to all users of Sun Microsystems 1800.

A complete Sun Microsystems manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual Sun Microsystems 1800 - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the Sun Microsystems 1800, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the Sun Microsystems 1800, that we can find in the current document
3. Tips how to use the basic functions of the device Sun Microsystems 1800 - which should help us in our first steps of using Sun Microsystems 1800
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with Sun Microsystems 1800
5. FAQ - Frequently Asked Questions
6. Contact detailsInformation about where to look for contact to the manufacturer/service of Sun Microsystems 1800 in a specific country, if it was not possible to solve the problem on our own.

Do you have a question concerning Sun Microsystems 1800?

Use the form below

If you did not solve your problem by using a manual Sun Microsystems 1800, ask a question using the form below. If a user had a similar problem with Sun Microsystems 1800 it is likely that he will want to share the way to solve it.

Copy the text from the picture

Comments (0)