    ZONEKIT4ZCAR Comfort Zone Installation and Start-Up Instructions NOTE: Read the entire instruction manual before starting the installation. TABLE OF CONTENTS PAGE Safety Consideration ......................................................................1 Installation Considerations..........................................................1-2 Intro ...

  • Carrier ZONEKIT4ZCAR - page 2

    2. Use vibration isolators (flex connectors) on zone dampers and duct work to minimize noise. 3. Place dampers away from areas that may be noise sensitive. 4. TXV is required in air conditioning and heat pump applica- tions. 5. Use separate isolated transformer to supply power to Comfort Zone System (50 va minimum, class 2, field supplied). 6. Load ...

  • Carrier ZONEKIT4ZCAR - page 3

    Table 1—Wiring Requirements FROM COMFORT ZONE CENTER TO NO. OF WIRES GAGE MAX. LENGTH (FT) Four Zone Controller 3‡ 18/22 200/100 5‡ 18/22 200/100 Remote Room Sen- sors 2‡ 18/22 200/100 Remote Duct Sensors 2‡ 18/22 200/100 Dx Coil Sensor 2‡ 18/22 200/100 Home Access Module 3‡ 18/22 1000/100 ISOSAT* 3‡ 18/22 1000/100 Transformer† 21 ...

  • Carrier ZONEKIT4ZCAR - page 4

    Before insulating the duct work, check for proper damper opera- tion. Apply the 24vac between COM and OPN to open the damper and COM and CLS to close the damper. (See Fig. 7.) The damper will modulate counter-clockwise to open and clockwise to close. If in an emergency it becomes necessary to force a damper open, manually press in the red quick bla ...

  • Carrier ZONEKIT4ZCAR - page 5

    2. Secure flexible duct to zone damper using SMACNA or other approved method. 3. Properly seal joint using duct tape, mastic, or other approved method. Do not allow mastic to come in contact with actuator. 4. Insulate damper using 1-1/2-in. to 2-in. insulation. (Check your local codes.) NOTE: All zone dampers and duct work must be properly supporte ...

  • Carrier ZONEKIT4ZCAR - page 6

    5. Insert 2-conductor wiring through 1 of pre-drilled holes in side of back plate. 6. Connect sensor to 2-wire conductor using provided wire nuts. (See Fig. 16 for connection to Comfort Zone Center.) Step 7—Install Dx Coil Sensor The Dx coil temperature sensor is recommended for use in heat pump with fan coil applications only. The sensor should ...

  • Carrier ZONEKIT4ZCAR - page 7

    Fig. 16—Comfort Zone System Wiring Diagram A94311  Zone Dampers Dx Coil Sensor (optional) Outside Air Sensor (optional) Duct Sensor Zone 2* Zone 3* Zone 4* Zone 1 4-Zone Controller Remote Room Sensors 72 68 2:45 24 VAC Transformer (Field Supplied) 50 VAC req. for basic 4 damper system. Please see Page 1, Electrica ...

  • Carrier ZONEKIT4ZCAR - page 8

    Changing the base temperatures will change the Comfort Temperature Setpoints used in the system schedules. Always set the Base Temperatures prior to programming the system schedules. Comfort Zone also uses a minimum temperature and a maximum temperature for comfort setpoints. The minimum and maximum temperatures are the same for all 4 zones. The Ma ...

  • Carrier ZONEKIT4ZCAR - page 9

    If Fan Switch on 4 zone controller is set to ON instead of Auto, then system fan will run continuously. Any time Comfort Zone is operating fan, it will be in active control of system. NOTE: If Auto Fan Off For Heating option (rotary switch position T-9) is ON, and Fan Switch on the 4 zone controller is ON, Comfort Zone will operate fan full time. O ...

  • Carrier ZONEKIT4ZCAR - page 10

    heater. The electric strip heat is much more expensive to operate when comparing cost per unit of heat. Because auxiliary stages of heating tend to be more expensive to operate, Comfort Zone attempts to keep number of stages at a minimum. CONFIGURATION OPTIONS FOR EQUIPMENT OPERATION Comfort Zone has several configurable options which allow it to c ...

  • Carrier ZONEKIT4ZCAR - page 11

    NOTE: Comfort Zone uses a 3-minute timer to delay start of second-stage (heating or cooling). This timer is started whenever first-stage heating or cooling is energized. This delay cannot be overridden or disabled. STAGE CONTROL DURING EQUIPMENT OPERATION As shown earlier, Comfort Zone has 6 configurable options which help govern equipment operatio ...

  • Carrier ZONEKIT4ZCAR - page 12

    then temperature at which first stage will be shut down will be offset 5°F above limit value (110°F to 114°F). If limit temperature is between 110°F and 155°F, then temperature at which first stage will shut down will be offset 20°F above limit value (130°F to 175°F). For Cooling modes the temperature is fixed at 50°F (10°C) for starting ...

  • Carrier ZONEKIT4ZCAR - page 13

    If a value of 105 to 110 is selected (second-stage heating is turned off at this value) then the first-stage high temperature trip limit is the programmed value plus 5°F (first-stage is turned off). If a value of 111 to 155 is selected (second-stage heating is turned off) then the first-stage high temperature trip limit is the programmed value plu ...

  • Carrier ZONEKIT4ZCAR - page 14

    7. Write down on a piece of paper AND GIVE TO THE OWNER a list showing what rooms are controlled by what dampers, and their corresponding zone numbers. Keep list for your future use. 8. Instruct owner to turn cool switch OFF in the fall, and turn it ON in the spring. 9. Make sure emergency heat switch is in the OFF position. If a gas furnace is use ...

  • Carrier ZONEKIT4ZCAR - page 15

    Cool Switch OFF —Cooling will not come on. AUTO —Cooling will come on when any zone is more than 1.5°F above desired cool setpoint. Fan Switch ON —Fan will stay on continuously (recommended). AUTO —Fan will come on only when heating or cooling is required. Emergency Heat Switch (Heat Pump Systems only) OFF —Electric strip heat will not c ...

  • Carrier ZONEKIT4ZCAR - page 16

    Press ADVANCE TIME/DAY button until desired start time is displayed. 6. Adjust setpoints. Adjust setpoints using up and down buttons until desired temperatures for the selected time period appear in display. These setpoints will be used during the time period currently displayed in clock window. 7. Complete time period programming. Repeat 4 through ...

  • Carrier ZONEKIT4ZCAR - page 17

    OUTSIDE AIR TEMPERATURE SENSOR The Outside Air Temperature Sensor must be used whenever an Outside Air Damper is installed. An Outside Air Temperature Sensor must also be used for dual fuel applications. Step 16—Troubleshooting This section contains information to assist you in troubleshooting problems and errors associated with the Comfort Zone ...

  • Carrier ZONEKIT4ZCAR - page 18

    Table 11—Toggle Summary TOGGLE SETTING ON OFF DEFAULT (T1)-Timeguard Override Timeguard delay is 30 sec, overrides 5-minute delay be- tween de-energizing and re-energizing HVAC stages. This option automatically returns to OFF after 30 sec timeout. If equipment has been shut down due to a leaving air tem- perature trip, the timeguard override has ...

  • Carrier ZONEKIT4ZCAR - page 19

    Table 12—Operating Problems SYMPTOM POSSIBLE CAUSE No Display Thermostat is not receiving power. 1. Verify that comfort zone center is receiving 24 vac. (50 va minimum required with 4 motorized dampers, 5 va for each additional motorized damper.) 2. Check that the thermostat is receiving a steady 10 VDC across the red and white wires at the syste ...

  • Carrier ZONEKIT4ZCAR - page 20

    Table 13—Storage Failure Errors Error Display (Dial Position T4) must be turned on. SF ERROR CODE DESCRIPTION SOLUTION 01 Temperature Programming Error Reprogram the scheduled temperatures. 02 Time Period Programming Error Reprogram the scheduled time periods. 03 Zone 1 Temperature Calibration Out of Range 1. Turn selection dial to position 2. 2. ...

  • Carrier ZONEKIT4ZCAR - page 21

    Table 14—Hardware Failure Errors Error Display (Dial Position T4) must be turned on. HF ERROR CODE DESCRIPTION SOLUTION 40 Zone 1 Temperature Sensor Bad sensor, shorted or open. 1. Check wiring and sensor. 2. Replace failed sensor, if necessary. Valid temperature range = 30°—180°F. 41 Zone 2 Temperature Sensor Bad sensor, shorted or open. 1. ...

  • Carrier ZONEKIT4ZCAR - page 22

    UNIT 24 VAC (R) C Y STANDARD SINGLE SPEED AIR CONDITIONER Yellow Red Blue White Brown Green Orange Black COOL 1 (Y1) COOL 2 (Y2) HEAT 1 (W1) HEAT 2 (W2) FAN (G) RV-COOL (O) RV-HEAT (O) OR FAN COIL COMFORT ZONE SYSTEM Y W2 W3 R C G O L E A A93227 UNIT 24 VAC (R) STANDARD SINGLE SPEED AIR CONDITIONER Yellow Red Blue White Brown Green Oran ...

  • Carrier ZONEKIT4ZCAR - page 23

    Fig. 19—Typical Wiring Diagrams (Fan Coil with Air Conditioner) Continued A94034 E UNIT 24 VAC (R) 2-SPEED AIR CONDITIONER (38TD) Yellow Red Blue White Brown Green Orange Black COOL 1 (Y1) COOL 2 (Y2) HEAT 1 (W1) HEAT 2 (W2) FAN (G) RV-COOL (O) RV-HEAT (O) OR FAN COIL COMFORT ZONE CENTER C R Y2 L Y1 Y1 R C G L E W3 Y/ Y2 W2 23 ...

  • Carrier ZONEKIT4ZCAR - page 24

    UNIT 24 VAC (R) C Y STANDARD SINGLE SPEED AIR CONDITIONER Yellow Red Blue White Brown Green Orange Black COOL 1 (Y1) COOL 2 (Y2) HEAT 1 (W1) HEAT 2 (W2) FAN (G) RV-COOL (O) RV-HEAT (O) OR VARIABLE SPEED FURNACE COMFORT ZONE CENTER Y W G R C RELAY COIL Green (P5) CONNECTION AT CONTROL BOARD Black 13 NOTE: Put set-up Switch No. 2 ...

  • Carrier ZONEKIT4ZCAR - page 25

    UNIT 24 VAC (R) Y2 R C 2-SPEED AIR CONDITIONER (38TD) Yellow Red Blue White Brown Green Orange Black COOL 1 (Y1) COOL 2 (Y2) HEAT 1 (W1) HEAT 2 (W2) FAN (G) RV-COOL (O) RV-HEAT (O) OR VARIABLE SPEED FURNACE COMFORT ZONE CENTER W G C R Y Y1 L RELAY COIL Green (P5) CONNECTION AT CONTROL BOARD Black 13 E (KGATT0101VSP) NOTE: Put set- ...

  • Carrier ZONEKIT4ZCAR - page 26

    Fig. 20—Typical Wiring Diagrams (Furnace with Air Conditioner) Continued Locking furnace into "low fire" may help prevent over conditioning in the heating mode. This will allow the furnace to stage between low and high fire. Before using this feature read furnace Installation Instructions for two- stage operation. Connect "W2" ...

  • Carrier ZONEKIT4ZCAR - page 27

    Fig. 21—Typical Wiring Diagrams (Fan Coil with Heat Pump) UNIT 24 VAC (R) STANDARD SINGLE SPEED HEAT PUMP Yellow Red Blue White Brown Green Orange Black COOL 1 (Y1) COOL 2 (Y2) HEAT 1 (W1) HEAT 2 (W2) FAN (G) RV-COOL (O) RV-HEAT (O) OR FAN COIL COMFORT ZONE CENTER G C R Y W2 O R C L A E Y W2 O W3 A93242 UNIT 24 VAC (R) STANDARD SINGLE SP ...

  • Carrier ZONEKIT4ZCAR - page 28

    Fig. 21—Typical Wiring Diagrams (Fan Coil with Heat Pump) Continued UNIT 24 VAC (R) 2-SPEED HEAT PUMP (38YD) Yellow Red Blue White Brown Green Orange Black COOL 1 (Y1) COOL 2 (Y2) HEAT 1 (W1) HEAT 2 (W2) FAN (G) RV-COOL (O) RV-HEAT (O) OR FAN COIL COMFORT ZONE SYSTEM G C R Y1 W2 O W2 R C E E O Y2 L W3 Y/ Y2 L W3 Y1 A94044 28 ...

  • Carrier ZONEKIT4ZCAR - page 29

    Fig. 22—Typical Wiring Diagram (Furnace with Heat Pump) UNIT 24 VAC (R) Y W2 STANDARD SINGLE SPEED HEAT PUMP Yellow Red Blue White Brown Green Orange Black COOL 1 (Y1) COOL 2 (Y2) HEAT 1 (W1) HEAT 2 (W2) FAN (G) RV-COOL (O) RV-HEAT (O) OR VARIABLE SPEED FURNACE COMFORT ZONE CENTER G A R C O R R1 R1 = Relay DPST, Pilot Duty, 24-v coil ...

  • Carrier ZONEKIT4ZCAR - page 30

    Fig. 22—Typical Wiring Diagrams (Furnace with Heat Pump) Continued UNIT 24 VAC (R) C R Y2 L 2-SPEED HEAT PUMP (38YD) Yellow Red Blue White Brown Green Orange Black COOL 1 (Y1) COOL 2 (Y2) HEAT 1 (W1) HEAT 2 (W2) FAN (G) RV-COOL (O) RV-HEAT (O) OR VARIABLE SPEED FURNACE COMFORT ZONE CENTER G Y1 R1 R R1 = Relay DPST, Pilot Duty, 24-v co ...

  • Carrier ZONEKIT4ZCAR - page 31

    Fig. 22—Typical Wiring Diagrams (Furnace with Heat Pump) Continued UNIT 24 VAC (R) C R Y1 O 2-SPEED HEAT PUMP (38YD) Yellow Red Blue White Brown Green Orange Black COOL 1 (Y1) COOL 2 (Y2) HEAT 1 (W1) HEAT 2 (W2) FAN (G) RV-COOL (O) RV-HEAT (O) OR FURNACE COMFORT ZONE CENTER G Y2 H R1 R R1 = Relay DPST, Pilot Duty, 24-v coil (HN61KK324) o ...

  • Carrier ZONEKIT4ZCAR - page 32

    Comfort Zone Configuration Table TOGGLE DESCRIPTION FACTORY DEFAULT RECORD JOB SETTING T1 Timeguard Override OFF T2 Celsius Temperature Display OFF T3 2400 Baud Rate ON T4 Error Code Display ON T5 Enable Broadcast ON T6 Heat Pump Operation OFF T7 Outside Air Temp Sensor Attached OFF T8 Comfort Trend Setting ON T9 Auto Fan Off For Heat OFF T10 High/ ...

Manufacturer Carrier Category Air Conditioner

Documents that we receive from a manufacturer of a Carrier ZONEKIT4ZCAR can be divided into several groups. They are, among others:
- Carrier technical drawings
- ZONEKIT4ZCAR manuals
- Carrier product data sheets
- information booklets
- or energy labels Carrier ZONEKIT4ZCAR
All of them are important, but the most important information from the point of view of use of the device are in the user manual Carrier ZONEKIT4ZCAR.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals Carrier ZONEKIT4ZCAR, service manual, brief instructions and user manuals Carrier ZONEKIT4ZCAR. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product Carrier ZONEKIT4ZCAR.

A complete manual for the device Carrier ZONEKIT4ZCAR, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use Carrier ZONEKIT4ZCAR by users. Manuals are usually written by a technical writer, but in a language understandable to all users of Carrier ZONEKIT4ZCAR.

A complete Carrier manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual Carrier ZONEKIT4ZCAR - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the Carrier ZONEKIT4ZCAR, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the Carrier ZONEKIT4ZCAR, that we can find in the current document
3. Tips how to use the basic functions of the device Carrier ZONEKIT4ZCAR - which should help us in our first steps of using Carrier ZONEKIT4ZCAR
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with Carrier ZONEKIT4ZCAR
5. FAQ - Frequently Asked Questions
6. Contact detailsInformation about where to look for contact to the manufacturer/service of Carrier ZONEKIT4ZCAR in a specific country, if it was not possible to solve the problem on our own.

Do you have a question concerning Carrier ZONEKIT4ZCAR?

Use the form below

If you did not solve your problem by using a manual Carrier ZONEKIT4ZCAR, ask a question using the form below. If a user had a similar problem with Carrier ZONEKIT4ZCAR it is likely that he will want to share the way to solve it.

Copy the text from the picture

Comments (0)