RTS KGATX0101400 - page 1
TECHNICAL MANU AL This manual should remain with the unit. R TS A utomatic T ransfer Switch 400A, 120/240V , Single-phase Model No.: KGA TX0101400 A ne w standar d of reliability ...
-
RTS KGATX0101400 - page 2
The manufacturer cannot anticipate every possible circumstance that might involve a hazard. The warn- ings in this manual, and on tags and decals affixed to the unit are, therefore, not all-inclusive. If using a procedure, work method or operating technique the manufacturer does not specifically recommend, ensure that it is safe for others. Also ma ...
-
RTS KGATX0101400 - page 3
T able of Cont ents 1 Safety Rules ......................................... Inside F ront Cover Section 1 — General Information ................................... 2 1.1 Introduction............................................................. 2 1.2 Equipment Description ........................................... 2 1.3 Transfer Switch Data Labe ...
-
RTS KGATX0101400 - page 4
2 Section 1 — General Information RTS “W” T ype T ransfer Switch 1.1 I NTRODUCTION This manual has been prepared especially for the purpose of familiarizing personnel with the design, application, installation, operation and servicing of the applicable equipment. Read the manual carefully and comply with all instructions. This will help to pr ...
-
RTS KGATX0101400 - page 5
3 2.1 I NTRODUCTION T O I NST ALL A TION This equipment has been wired and tested at the factory . Installing the switch includes the following procedures: • Mounting the enclosure. • Connecting utility and generator power source leads. • Connecting the load leads. • Connecting any auxiliary contact (if needed) • Installing/connecting any ...
-
RTS KGATX0101400 - page 6
4 Use a torque wr ench to tighten the conductors, being sure not to overtighten, or damage to the switch base could occur . If undertightened, a loose connection would result, causing excess heat which could damage the switch base. Connect power source load conductors to clearly marked transfer mechanism terminal lugs as fol- lows 1. Connect UT ...
-
RTS KGATX0101400 - page 7
5 3.2 MAN U AL OP ER A TION D ANGER Do NOT manually transfer under load. Disconnect transfer switch from all power sour c- es by approved means, such as a main cir cuit breaker(s). A manual HANDLE is shipped with the transfer switch. Manual operation must be checked BEFORE the transfer switch is operated electrically . T o check manual operatio ...
-
RTS KGATX0101400 - page 8
6 3.2.2 CL OSE T O EM ERGENCY SOURCE SI DE Before proceeding, verify the position of the switch by observing window “B” in F igure 3.1. If window “B” reads “ON”, the contacts are closed in the EMERGENCY (ST ANDBY) position. No further action is required. If it reads “OFF”, proceed with Step 1. Step 1: With the handle attached to the ...
-
RTS KGATX0101400 - page 9
7 3.4 GEN ER A T OR T ESTS U N DER L O AD 1. Set the generator's main circuit breaker to its OFF or OPEN position. 2. Manually actuate the transfer switch main con- tacts to their EMERGENCY (ST ANDBY) position. Refer to “Manual Operation ” section. 3. T o start the generator , set the AUTO/OFF/MANU AL switch to MANU AL. When engine starts, ...
-
RTS KGATX0101400 - page 10
8 Section 4 — Installation Diagram RTS “W” T ype T ransfer Switch Installation Diagram – Drawing No. 0F640 1 6 09.6mm [ 24.0" ] 9 17mm [ 36.1" ] T RIPLE EK O SU ITABLE FOR 1" , 1.25" & 1.50" CONDUIT 3 PLA C E S 2 54mm [ 10.0" ] 7 94mm [ 31.3" ] 6 0.8mm [ 2.4" ] 6 1.3mm [ 2.4" ] 4 87mm [ 19.2& ...
-
RTS KGATX0101400 - page 11
9 Section 5 — Electrical Data RTS “W” T ype T ransfer Switch Interconnection Diagram - Drawing No. 0G1 944 ...
-
RTS KGATX0101400 - page 12
B2 A2 B1 A1 C 6 9 TR 1 7 TR E1 E1 N2A N2A N1A E2 2 05 12 6 TR 2 3 1 94 2 3 1 94 N2A LE G EN D G T S N O TE S : A LL CO NTA C T S S H O WN WIT H TRAN S FER S WIT C H IN U TILIT Y P O S ITI O N . B A WHITE RED L S 2 L S3 L S 1 T 1 T2 2 3 5 6 1 4 C - CO NTA C T O R A C T U ATIN G CO I L G T S - TRAN S FER S WIT C H CO NTA C T OR L S 1 , L S 2 , L S3 - ...
-
RTS KGATX0101400 - page 13
11 TR G T S T1 E1 N1 T2 E2 N2 B1 B2 A2 A1 N1A N1A 12 6 E2 E1 N2A 2 05 N1A 2 05 E1 E1 A 7 1 B 9 3 T1 T2 N1A N2A 12 6 2 05 N1A N1A N1A N1A F2 F1 2 3 19 4 T S U TILITY 2 U TILITY 1 1 94 2 3 2 3 1 94 2 3 1 94 N1 N2 N2A N2A N2A N2A N2A N2A N1A 2 3 1 94 Section 5 — Electrical Data RTS “W” T ype T ransfer Switch Wiring Diagram/Schematic – Drawing ...
-
RTS KGATX0101400 - page 14
12 Section 6 — Exploded Views and P arts List RTS “W” T ype T ransfer Switch 400 A Switch Assembly – Drawing No. 0G1 51 0$ ...
-
RTS KGATX0101400 - page 15
13 Section 6 — Exploded Views and P arts List RTS “W” T ype T ransfer Switch 400 A Switch Assembly – Drawing No. 0G1 51 0$ ITEM P ART NO . QTY . DESCRIPTION 1 0D72 9 4 1 XFER S W -W 400A600V2P 2 0A7 8 22 6 LUG, S LDL SS 600/250-1/0X1/4-2 8 3 026 9 02 5 S CREW T APTITE # 8 - 3 2X1/4 BP 4 0C7 9 07J 2 CO VER LUG 2P 400AMP 5 024526 1 S CREW HHT ...
-
RTS KGATX0101400 - page 16
Section 8 — W arranty RTS “W” T ype T ransfer Switch CAR R I ER W AR R ANT Y/SERVICE Carrier will warrant that from the date of purchase, our transfer switch will be free from defects in material and workmanship for the items and periods set forth in the warranty statement found in the owners manual of the Carrier generator that this transfer ...