    D500-08-00 1 I56-5 12-0 7R DH500 Intelligent Air Duct Smoke Detector Housing INST ALLA TION AND MAINTENANCE INSTRUCTIONS 3825 Ohio A venue , St. Charles, Illinois 60 174 1-800-SENSOR2, F AX: 63 0-377-6495 www .systemsensor .com Before Installing Please thoroughly r ead S ystem Sensor’ s Guide for Proper Use of Smoke Detectors in Duct Applications ...

  • System Sensor DH500 - page 2

    D500-08-00 2 I56-5 12-0 7R NO TE: The inlet sampling tube must be or dered sepa- rately . It must be the corr ect length for the width of the duct where it will be installed. See T able 1 to determine the inlet tube r equired for differ ent duct widths. Smoke detector heads (155 1, ionization; 255 1, photoelectr onic) must be or der ed separ ately ...

  • System Sensor DH500 - page 3

    D500-08-00 3 I56-5 12-0 7R T able 1. Sampling (Inlet) Tubes T ube Outside Duct Width ST -1.5 1 to 2 ft. (0.3 to 0.6 m) ST -3 2 to 4 ft. (0.6 to 1.2 m) ST -5 4 to 8 ft. (1.2 to 2.4 m) ST -1 0 8 to 12 ft. (2.4 to 3.7 m) Step 4. Install the Inlet Tube The inlet tube (shown in Figure 3) is identified by a series HOLE B HOLE A DUCT WALL SPEED NUT SCREW ...

  • System Sensor DH500 - page 4

    D500-08-00 4 I56-5 12-0 7R W A RN ING In no case should mor e than 2 air inlet holes be cut off the tube . There must be a minimum of 1 0 holes in the tube exposed to the air stream. B. Installation for Ducts Mor e Than 8 Feet W ide NO TE: T o install inlet tubes in ducts more than 8 feet wide , work must be performed inside the air duct. Sampling ...

  • System Sensor DH500 - page 5

    D500-08-00 5 I56-5 12-0 7R NO TE: This pr ocedure should only be used in an emergen- cy , and it is not intended as a permanent substitute for or dering the correct length tubes. Step 5. Field Wiring Wiring Installation Guidelines All wiring must be installed in compliance with the Canadian Electrical Code and the local codes having juris- diction. ...

  • System Sensor DH500 - page 6

    D500-08-00 6 I56-5 12-0 7R (+) (-) RA400 REMOTE ALARM LED OPTION 1 PER UNIT 8mA CURRENT DRAW RA400Z (+) RA400Z or (-) RTS451/ RTS451KEY EXTERNAL (-) POWER (+) SUPPLY * RTS451/RTS451KEY REMOTE TEST STATION LED OPTION 1 PER UNIT 8mA CURRENT DRAW TEST COIL OPTION 1 PER UNIT 95mA CURRENT DRAW 4 5 3 2 1 Unused Remote Test (+) (-) (+) (+) (-) (-) (+) RA4 ...

  • System Sensor DH500 - page 7

    TWIST COUNTERCLOCKWISE TO REMOVE DUCT HOUSING TWIST CLOCKWISE TO INST ALL DETECTOR HEAD MOLDED RIB TEST MAGNET P AINTED SIDE TO WARD HOUSING DUCT DETECTOR HOUSING DETECTOR HEAD 2. T o determine that smok e is capable of entering the sens- ing chamber , a visual ex amination should be conducted to note any obscurations ar ound the sensing chamber . ...

  • System Sensor DH500 - page 8

    D500-08-00 8 I56-5 12-0 7R Step 8. Install the Cover Install the cov er using the four scr ew s . Be certain filter s are installed as specified in Step 6. Make sur e that the co ver fits into the base gr oov e and that all gask ets ar e in their pr oper positions. Tighten the four cov er scr e ws to 1 0 in/lbs. Step 9. Per form the Final System Ch ...

  • System Sensor DH500 - page 9

    D500-08-00 9 I56-5 12-0 7R Both T ypes Of Units 16. R einstall the detector housing. 17. R estore pow er to the sy stem. 18. Put detector into alarm using appropriate method described in STEP 7. PERFORM DETECT OR CHECK (page 7 of this manual). 19. Notify the proper authorities that testing has been completed and the smoke detector system is again o ...

  • System Sensor DH500 - page 10

    D500-08-00 1 0 I56-5 12-0 7R ...

  • System Sensor DH500 - page 11

    D500-08-00 1 1 I56-5 12-0 7R Three-Y ear Limited W arranty Sy stem Sensor warr ants its enclosed smok e detector to be free from defects in materials and w orkmanship under normal use and service for a period of three year s fr om date of manufacture . System Sensor makes no other expr ess w arranty for this smoke detector . No agent, repr esentati ...

  • System Sensor DH500 - page 12

    D500-08-00 12 I56-5 12-0 7R © 200 3 System Sensor DETECTOR TEST LOG Detector Identification Infor mation Manufacturer and Serial Date Detector Model:______________________ Number: ______________________ Installed: ___________________ Description of Detector Location: _________________________________________________________________________________ ...

Manufacturer System Sensor Category Smoke Alarm

Documents that we receive from a manufacturer of a System Sensor DH500 can be divided into several groups. They are, among others:
- System Sensor technical drawings
- DH500 manuals
- System Sensor product data sheets
- information booklets
- or energy labels System Sensor DH500
All of them are important, but the most important information from the point of view of use of the device are in the user manual System Sensor DH500.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals System Sensor DH500, service manual, brief instructions and user manuals System Sensor DH500. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product System Sensor DH500.

A complete manual for the device System Sensor DH500, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use System Sensor DH500 by users. Manuals are usually written by a technical writer, but in a language understandable to all users of System Sensor DH500.

A complete System Sensor manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual System Sensor DH500 - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the System Sensor DH500, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the System Sensor DH500, that we can find in the current document
3. Tips how to use the basic functions of the device System Sensor DH500 - which should help us in our first steps of using System Sensor DH500
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with System Sensor DH500
5. FAQ - Frequently Asked Questions
6. Contact detailsInformation about where to look for contact to the manufacturer/service of System Sensor DH500 in a specific country, if it was not possible to solve the problem on our own.

Do you have a question concerning System Sensor DH500?

Use the form below

If you did not solve your problem by using a manual System Sensor DH500, ask a question using the form below. If a user had a similar problem with System Sensor DH500 it is likely that he will want to share the way to solve it.

Copy the text from the picture

Comments (0)