    036-21031 -004 Rev. A (0603) FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE ® TECHNIC AL GUIDE STELLAR PLUS TM 12 SEER SPLIT -SYSTEM HEA T P UMPS MOD ELS: E*FH018 Thru E*FH06 0 (1.5 THRU 5 NOMINAL TONS) Due to cont inuous produc t improvem ent, specifi cations are subje ct to change w ithout notice. Vis it us on the web at www ...

  • York E*FH018 - page 2

    036-2103 1-004 Re v. A (0603 ) 2 Unitary Produ cts Grou p All dim ensions are in inches. They are subje ct to ch ange withou t notice. Certif ied dimens ions will be provide d upon request. PHYSICAL AND ELECTRICAL DA T A MODEL E4FH018 E4FH024 E4FH030 E4F H036 E4FH045 E5FH048 E4FH060 Unit Supply V olt age 208/230-1-60 Normal V olt age Range 1 1. Rat ...

  • York E*FH018 - page 3

    036-21031 -004 Rev. A (0603) Unitary Pro ducts Group 3 PROCEDURES: 1. Unit factory charge list ed on the unit nameplate includes refigerant for the condenser , the smallest evaporator and for 15 f eet of intercon- necting line tubing. 2. V erify the orifice size and the additional charge required for the specific evaporator coil in the system using ...

  • York E*FH018 - page 4

    036-2103 1-004 Re v. A (0603 ) 4 Unitary Produ cts Grou p - = No t appl icab le COOLING CAP ACITY - With Air Handler Coils UNIT MODEL AIR HANDLER COIL MODEL 1 1. G2 FD co ils av ailab le wi th a f acto ry in sta lle d hori zont al drain pan. See p rice pag es for spec ific m ode l number . COO LING MODEL ELEC TRIC HEA T K W 2 2. Sing le phas e unit ...

  • York E*FH018 - page 5

    036-21031 -004 Rev. A (0603) Unitary Pro ducts Group 5 * Require s a 2F D Blower T ime De lay unl ess a standa rd furn ace is e quipped with one . ** Refer to Qu ick Selection Chart for specific fu rnace m atch-u p. COOLING CAP ACITY - With Up flow , Downflow and Horizont al Furnace and Coils UNIT MODE L FURNACE** COIL MODEL COO LING NOMINAL AIRFLO ...

  • York E*FH018 - page 6

    036-2103 1-004 Re v. A (0603 ) 6 Unitary Produ cts Grou p HEA TING PERFORMANCE - Air Handler and Mu lti-position Coils UNIT MODE L COIL 1 MODE L ARI HEA TING 2 OUTD O O R TE M P 3 47 ° F 17 ° FH S P F- 3 ° F 7 ° F1 7 ° F 27 ° F 37 ° F 47 ° F5 7 ° F MBH COP MBH COP STD. V . S. MBH KW MBH KW MBH KW MBH KW MBH KW MBH KW MBH KW E4FH018 F2RP/F2 ...

  • York E*FH018 - page 7

    036-21031 -004 Rev. A (0603) Unitary Pro ducts Group 7 COP equa ls MBH output divided b y (total KW inp ut x 3.4 12). HSPF ( Heating Seasonal Perfo rmanc e Factor) is the to tal heati ng outpu t duri ng a nor mal ann ual usa ge per iod for heating divided by t he total ele ctric power input du ring th e same period . — = Not Applicable. HEA TING ...

  • York E*FH018 - page 8

    036-2103 1-004 Re v. A (0603 ) 8 Unitary Produ cts Grou p ACCESSORIES Refer to Price Ma nual for sp ecific mod el numbe rs. St art Ass ist Kit (2SA067*) Blow er Ti me Del ay - Avail able to in crease ef fic iency whe n inst alled. Ins tal ls on indoor sec tion an d maint ains blowe r for approxi mately on e minute af ter c ooling therm osta t has b ...

  • York E*FH018 - page 9

    036-21031 -004 Rev. A (0603) Unitary Pro ducts Group 9 TYPICAL INST ALLA TION TYPICAL FIELD WIRING - (AIR HANDLER / ELECTRICAL HEA T ) THERMOST A T TO INDOOR BLOWER TO COIL NEC CLASS 2 WIRING NEC CLASS 1 WIRING TO POWER SUPPL Y WEA THERPROOF DISCONNECT SWITCH Seal open ing(s) with per magum or equivalent 24” SERVICE ACCESS CLEARANCE 48” OVERHEA ...

  • York E*FH018 - page 10

    036-2103 1-004 Re v. A (0603 ) 10 Unitary Produ cts Grou p Multipliers for determining the performance with oth er indoor sections. NOTE: For dry bu lb te mpera ture s dif fer ent th an t hose liste d (bet ween 73-87 F), s e nsib le ca pac ity in crea ses b y 1060 BTUH pe r 10 00 CFM per deg ree ab ove t he listed tem pera ture an d decreas es by 1 ...

  • York E*FH018 - page 11

    036-21031 -004 Rev. A (0603) Unitary Pro ducts Group 11 Multipliers for determining the performance with oth er indoor sections. NOTE: For dry b ulb tem peratu res differe nt than tho se list ed (be tween 7 3-87 F), sensibl e capacity increase s by 10 60 BTUH p er 100 0 CFM per de gree a bove th e lis t ed t e mper atur e and de cre a ses by 106 0 ...

  • York E*FH018 - page 12

    036-2103 1-004 Re v. A (0603 ) 12 Unitary Produ cts Grou p Multipliers for determining the performance with oth er indoor sections. NOTE: For dry bu lb te mpera ture s dif fer ent th an t hose liste d (bet ween 73-87 F), s e nsib le ca pac ity in crea ses b y 1060 BTUH pe r 10 00 CFM per deg ree ab ove t he listed tem pera ture an d decreas es by 1 ...

  • York E*FH018 - page 13

    036-21031 -004 Rev. A (0603) Unitary Pro ducts Group 13 Multipliers for determining the performance with oth er indoor sections. NOTE: For dry b ulb tem peratu res differe nt than tho se list ed (be tween 7 3-87 F), sensibl e capacity increase s by 10 60 BTUH p er 100 0 CFM per de gree a bove th e lis t ed t e mper atur e and de cre a ses by 106 0 ...

  • York E*FH018 - page 14

    036-2103 1-004 Re v. A (0603 ) 14 Unitary Produ cts Grou p Multipliers for determining the performance with oth er indoor sections. NOTE: For dry bu lb te mpera ture s dif fer ent th an t hose liste d (bet ween 73-87 F), s e nsib le ca pac ity in crea ses b y 1060 BTUH pe r 10 00 CFM per deg ree ab ove t he listed tem pera ture an d decreas es by 1 ...

  • York E*FH018 - page 15

    036-21031 -004 Rev. A (0603) Unitary Pro ducts Group 15 Multipliers for determining the performance with oth er indoor sections. NOTE: For dry b ulb tem peratu res differe nt than tho se list ed (be tween 7 3-87 F), sensibl e capacity increase s by 10 60 BTUH p er 100 0 CFM per de gree a bove th e lis t ed t e mper atur e and de cre a ses by 106 0 ...

  • York E*FH018 - page 16

    036-2103 1-004 Re v. A (0603 ) 16 Unitary Produ cts Grou p Multipliers for determining the performance with oth er indoor sections. NOTE: For dry bu lb te mpera ture s dif fer ent th an t hose liste d (bet ween 73-87 F), s e nsib le ca pac ity in crea ses b y 1060 BTUH pe r 10 00 CFM per deg ree ab ove t he listed tem pera ture an d decreas es by 1 ...

  • York E*FH018 - page 17

    036-21031 -004 Rev. A (0603) Unitary Pro ducts Group 17 Multipliers for determining the performance with oth er indoor sections. HEA TING PERFORMANCE DA T A CONDENSING UNIT MODEL NO. E4FH018S06 EV APORA TOR COIL MODEL NO. F 2RP/F2FP024 AIR TEMP . ENTERING OUTDOOR UNIT AIR TEMP . ENTERING INDOOR COIL ID CF M 600 650 700 MBTUH K.W . C. O.P . MBTUH K. ...

  • York E*FH018 - page 18

    036-2103 1-004 Re v. A (0603 ) 18 Unitary Produ cts Grou p Multipliers for determining the performance with oth er indoor sections. HEA TING PERFORMANCE DA T A CONDENSING UNIT MODEL NO. E4FH024S06 EV APORA TOR COIL MODEL NO. F 2RP/F2FP030 AIR TEMP . ENTERING OUTDOOR UNIT AIR TEMP . ENTERING INDOOR COIL ID CF M 750 800 850 MBTUH K.W . C.O.P . MBTUH ...

  • York E*FH018 - page 19

    036-21031 -004 Rev. A (0603) Unitary Pro ducts Group 19 Multipliers for determining the performance with oth er indoor sections. HEA TING PERFORMANCE DA T A CONDENSING UNIT MODEL NO E4FH30S06 EV APORA TOR COIL MODEL NO G2FD030(S,H)17 AIR TEMP . ENTERING OUTDOOR UNIT AIR TEMP . ENTERING INDOOR COIL ID CF M 950 1050 1 150 MBTUH K.W . C. O.P . MBTUH K ...

  • York E*FH018 - page 20

    036-2103 1-004 Re v. A (0603 ) 20 Unitary Produ cts Grou p Multipliers for determining the performance with oth er indoor sections. HEA TING PERFORMANCE DA T A CONDENSING UNIT MODEL NO. E4FH036S06 EV APORA TOR COIL MODEL NO. F 2RP/F2FP036 AIR TEMP . ENTERING OUTDOOR UNIT AIR TEMP . ENTERING INDOOR COIL ID CF M 1 150 1250 1350 MBTUH K.W . C.O.P . MB ...

  • York E*FH018 - page 21

    036-21031 -004 Rev. A (0603) Unitary Pro ducts Group 21 Multipliers for determining the performance with oth er indoor sections. HEA TING PERFORMANCE DA T A CONDENSING UNIT MODEL NO E4FH042S06 EV APORA TOR COIL MODEL NO F2RP/F2FP042 AIR TEMP . ENTERING OUTDOOR UNIT AIR TEMP . ENTERING INDOOR COIL ID CF M 1200 1400 1000 MBTUH K.W . C. O.P . MBTUH K. ...

  • York E*FH018 - page 22

    036-2103 1-004 Re v. A (0603 ) 22 Unitary Produ cts Grou p Multipliers for determining the performance with oth er indoor sections. HEA TING PERFORMANCE DA T A CONDENSING UNIT MODEL NO E5FH048S06 EV APORA TOR COIL MODEL NO F2FP048 AIR TEMP . ENTERING OUTDOOR UNIT AIR TEMP . ENTERING INDOOR COIL ID CF M 1450 1600 1750 MBTUH K.W . C.O.P . MBTUH K.W . ...

  • York E*FH018 - page 23

    036-21031 -004 Rev. A (0603) Unitary Pro ducts Group 23 Multipliers for determining the performance with oth er indoor sections. HEA TING PERFORMANCE DA T A CONDENSING UNIT MODEL NO E4FH060S06 EV APORA TOR COIL MODEL NO G2FD060(S,H)24 AIR TEMP . ENTERING OUTDOOR UNIT AIR TEMP . ENTERING INDOOR COIL ID CF M 1700 1850 2000 MBTUH K.W . C. O.P . MBTUH ...

  • York E*FH018 - page 24

    Subject to change without notice. Printed in U.S.A. 036-21031-004 Rev. A (0603) Copyright © by Y ork International Corp. 2003. All rights reserved. Supersedes: 036-21031-003 Rev . A (0403) Unit ary 5005 Norma n Product Y ork OK Group Drive 7306 9 MA TCHING INDOOR COMP ONENTS G1UA 1/2 CASED UPFLOW G1HD HORIZONT AL DUCT G2FD* MUL TI-POSITION (UPFLOW ...

Manufacturer York Category Air Conditioner

Documents that we receive from a manufacturer of a York E*FH018 can be divided into several groups. They are, among others:
- York technical drawings
- E*FH018 manuals
- York product data sheets
- information booklets
- or energy labels York E*FH018
All of them are important, but the most important information from the point of view of use of the device are in the user manual York E*FH018.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals York E*FH018, service manual, brief instructions and user manuals York E*FH018. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product York E*FH018.

Similar manuals

A complete manual for the device York E*FH018, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use York E*FH018 by users. Manuals are usually written by a technical writer, but in a language understandable to all users of York E*FH018.

A complete York manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual York E*FH018 - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the York E*FH018, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the York E*FH018, that we can find in the current document
3. Tips how to use the basic functions of the device York E*FH018 - which should help us in our first steps of using York E*FH018
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with York E*FH018