    Manufacturer reserves the right to disco ntinue, or change at any time, specifications or de signs without notice and without inc urring obligations. Catalog No . 04-53 500073-01 Printed in U .S .A. Form 50PSW -C1SI Pg 1 10-10 Replaces: Ne w Installation, Star t-Up , and Ser vice Instructions CONTENTS Page SAFETY CONSIDERA T IONS . . . . . . . . . ...

  • Carrier AQUAZONE 50PSW036-360 - page 2

    2 Recognize safety information. This is the safety alert symbol ( ). When you see this symbol on the unit and in instructions or manuals, be al ert to the potential for personal injury . GENERAL The Aquazone™ 50PSW w ater source heat pump (WSHP) is a single-package vertically mo unted unit with electronic con- tr ol s designed for y ear-round coo ...

  • Carrier AQUAZONE 50PSW036-360 - page 3

    3 B C A M L K 2.5 cm 1 2 3 4 5 6 J H G F E D Req u ire d S ervice Acce ss Option a l S ervice Acce ss 2.5 cm 4.6 cm 1 2 3 4 5 6 Req u ired S ervice Acc e ss Option a l S ervice Acce ss B C A 3 . 3 cm 6.9 cm 1 8 .5 cm 4. 3 cm Fig. 1 — 50PSW036-1 20 Unit SIZES 036, 060 LEGEND NO TES: 1. Dimensions shown in centimeters unless noted otherwise. 2. HAC ...

  • Carrier AQUAZONE 50PSW036-360 - page 4

    4 PR O T EC T I O N — Once the units are properly positioned on the jobsite, they must be covered with either a shipping carton, vinyl film, or an equivalent protective covering. Open ends of pipes stored on the jobsite must be capped. This precaution is especially important in areas where painting, plastering, or spraying of fireproof material, ...

  • Carrier AQUAZONE 50PSW036-360 - page 5

    5 8. Remove any access panel screws that may be difficult to remove once unit is installed. Step 3 — Locate Unit — The following guidelines should be considered when choosing a location for the WSHP: • Units are for indoor use only . • Provide suf ficient space for water and electrical connections. • Locate unit in an area th at allows fo ...

  • Carrier AQUAZONE 50PSW036-360 - page 6

    6 Table 2 — Water Quality Guideline s LEGEND *Heat exchanger materials considered are copper , cupronickel, 304 SS (stainless steel), 316 SS, titanium. †Closed recirculating system is id entified by a closed pressurized piping system. **Recirculating open we lls should obser ve the open recirculating design considerations. ††If the concentr ...

  • Carrier AQUAZONE 50PSW036-360 - page 7

    7 Step 6 — Wire Electrical Connections All field-installed wiring, including the electrical ground, MUST comply with the National Electrical Code (NEC) as well as applicable local codes. In addition, all field wiring must conform to the Class II temperature limitations described in the NEC. Operating voltage must be th e same voltage and phase as ...

  • Carrier AQUAZONE 50PSW036-360 - page 8

    8 Solenoid Coil Thermistor Ground Indicator Light G=Green, R=Red (Comp On) (Alarm Light) Circuit Breaker High Pressure Switch Low Pressure Switch Fuse F a50-8621 Fig. 4 — T ypical Aquazone™ 50PSW036-060 Complete C Contr ol Wiring, Single-Phase RV S — Re versin g V alve Sol enoid TRANS — T ransf or mer F actor y Line V oltage Wiring F actor ...

  • Carrier AQUAZONE 50PSW036-360 - page 9

    9 Complete C Complete C Complete C Complete C 7 7 Fig. 5 — T ypical Aquazone™ 50PSW120 Complet e C Control Wiring, 3 -Phase Circuit Breaker High Pressure Switch Low Pressure Switch Fuse F NO TES: 1. Compressor ther mally protected internally . 2. All wir ing to the unit must comply with NEC and local codes. 3. T ransf or mer is wired to 380 v l ...

  • Carrier AQUAZONE 50PSW036-360 - page 10

    10 Fig. 6 — T ypical Aquazone™ 50PSW360 Complet e C Control Wiring, 3 -Phase Circuit Breaker High Pressure Switch Low Pressure Switch Fuse F Complete C Complete C 1 Complete C 2 Complete C 6 NO TES: 1. Compressor thermally protected internally . 2. All wir ing to the unit m u st comply with NEC and local codes. 3. T ransf or mer is wired to 380 ...

  • Carrier AQUAZONE 50PSW036-360 - page 11

    11 Fig. 7 — T ypical Aquazone™ 50PSW360 Delux e D Control Wiring, 3-Phase Circuit Breake r High Pressure Switch Low Pressure Switch Fuse F MS — Motor Switch NEC — Nat ional Electr ical Code P1 — Field Wiring T erminal Block RV S — Re versing V alve Solenoid S-WTR — Source Water TRANS — T ransf or mer F actor y Line V oltage Wiring F ...

  • Carrier AQUAZONE 50PSW036-360 - page 12

    12 EXTERNAL LOOP POWER CONNECTION — If th e u ni t is to be connected to an external loop pump or flow controller , connect the pump to the loop pump terminal block PB1. The maximum power handling is 4 amps at 240-v . The pumps will automatically cycle as required by the unit. 220-V OPERA TION — All 220/240-v units are factory wired for 220-v . ...

  • Carrier AQUAZONE 50PSW036-360 - page 13

    13 FIELD SELECT ABLE INPUTS Jumpers and DIP (dual in-line package) switches on the control board are used to customize unit operation and can be configured in the field. Complete C Contro l Jumper Settings (See Fig. 4-6) W A TER COIL FREEZE PROTECTION (FP 1) LIMIT SETTING — Se le ct ju mpe r 3 , ( JW3 -F P1 L ow T em p) t o choose FP1 limit of ? ...

  • Carrier AQUAZONE 50PSW036-360 - page 14

    14 Table 5 — DIP Switch Block S2 — Accessory 2 Re lay Options LEGEND NO TE : All other DIP s witch combinations are invalid. ST ART -UP Use the procedure outlined below to initiate proper unit start-up. NOTE: This equipment is designed for indoor installation only . Operating Limits (See T able 6) EN V I R ON M E N T — This equipment is desig ...

  • Carrier AQUAZONE 50PSW036-360 - page 15

    15 Table 7 — Heat Exchang e r Pressure Drop UNIT SIZES 036-120 UNIT SIZES 180,360 NO TE : Bold values indicate use of antifreeze is re q uired. Cleaning and Flushing — Cleaning and flushing of the piping system is the single most important step to ensure proper start-up and continued efficient operation of the system. Follow the instructions be ...

  • Carrier AQUAZONE 50PSW036-360 - page 16

    16 Table 8 — Approximate Fluid Volume (L) per 30 M of Pipe LEGEND NO TE: V olume of heat exchanger is approximately 1.0 gallon (3.78 liters). Table 9 — Antifree ze Percentages by Volume Cooling T ower/Boiler Systems — These syste ms typically use a common loop maintained at 15.6 to 32.2 C. The use of a closed circuit evapora tive cooling towe ...

  • Carrier AQUAZONE 50PSW036-360 - page 17

    17 Upon entering T est mode, the status LED (light-emitting di- ode) will flash a code representi ng the last fault. For diagnostic ease at the thermostat, the alarm will also cycle during T est mode. The alarm relay will cycle on and off similar to the sta- tus LED to indicate a code repr esenting the last fault, at the thermostat. T est mode can ...

  • Carrier AQUAZONE 50PSW036-360 - page 18

    18 Table 12 — Aquazone™ Deluxe D Control Current LED Status and Alar m Relay Operations LEGEND NO TES: 1. If there is no fault in memory , the F ault LED will flash code 1. 2. Codes will be displa yed with a 10- second F ault LED pause. 3. Slow flash is 1 flash e very 2 seconds. 4. F ast flash is 2 flashes ev er y 1 second. 5. EXAMPLE: “Flash ...

  • Carrier AQUAZONE 50PSW036-360 - page 19

    19 but take care to prevent liquid from being carried over by the gases. W arm solution acts faster , but cold solution is just as effec- tive if applied for a longer period. GRA VITY FLOW METHOD — Do n ot add sol ut ion fa ste r than vent can exhaus t the generated gases. When condenser is full, allow solution to remain overnight, then drain con ...

  • Carrier AQUAZONE 50PSW036-360 - page 20

    20 S UCTIO N COMPRE SS OR DI S CHARGE COAX EXP AN S ION VA LV E FP 2 FP 1 LIQUI D LIN E WA TER IN WA TER OUT CONDEN S A TE OVERFLO W (CO) AIR COI L FREEZ E PROTECTIO N WA TE R COI L PROTECTIO N THERMI S T OR ( ° C) ( ° C) AI R COI L AIRFLOW AIRFLO W a50-8163 LEGEND Fig. 15 — FP1 and FP2 Thermistor Locat ion CO AX — Coaxial Heat Exchanger Airf ...

  • Carrier AQUAZONE 50PSW036-360 - page 21

    21 Table 13 — Troubleshooting LEGEND F A UL T HEA TING COOLING PO SSIBLE CA USE SOLUTION Main P ower Pr oblems X X Green Status L ED Off Chec k line v oltage circuit breaker and disconnect. Check f or line volta ge between L1 and L2 on th e contactor . Check for 24-vac between R and C on contro ller. Check primary/secondary voltage on tr ansf or ...

  • Carrier AQUAZONE 50PSW036-360 - page 22

    Manufacturer reserves the right to disco ntinue, or change at any time, specificatio ns or designs without notice and without inc urring obligations. Catalog No . 04-53500073-01 Pr inted in U .S.A. Form 50PSW -C1SI Pg 22 10-10 Replaces: New Copy right 2010 Carrier Cor poration ...

  • Carrier AQUAZONE 50PSW036-360 - page 23

    CL-1 50PSW ST ART -UP CH ECKLIST CUSTOMER: ___________________________ JOB NAME: _______________________________________ MODEL NO.:___________________________ SERIAL NO.: ____________________ DA TE: _________ LOOP TYPE: __________________________ _ ANTIFREEZE TYPE AND %: _________________________ I. PRE-ST ART -U P DOES THE UNIT VOL T AGE CORRESPON ...

  • Carrier AQUAZONE 50PSW036-360 - page 24

    Manufacturer reserves the right to disco ntinue, or change at any time, specificatio ns or designs without notice and without inc urring obligations. Catalog No . 04-53500073-01 Pr inted in U .S.A. Form 50PSW -C1SI Pg CL-2 10-10 Replaces: New Copy right 2010 Carrier Cor poration - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - - ...

Manufacturer Carrier Category Heat Pump

Documents that we receive from a manufacturer of a Carrier AQUAZONE 50PSW036-360 can be divided into several groups. They are, among others:
- Carrier technical drawings
- AQUAZONE 50PSW036-360 manuals
- Carrier product data sheets
- information booklets
- or energy labels Carrier AQUAZONE 50PSW036-360
All of them are important, but the most important information from the point of view of use of the device are in the user manual Carrier AQUAZONE 50PSW036-360.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals Carrier AQUAZONE 50PSW036-360, service manual, brief instructions and user manuals Carrier AQUAZONE 50PSW036-360. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product Carrier AQUAZONE 50PSW036-360.

A complete manual for the device Carrier AQUAZONE 50PSW036-360, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use Carrier AQUAZONE 50PSW036-360 by users. Manuals are usually written by a technical writer, but in a language understandable to all users of Carrier AQUAZONE 50PSW036-360.

A complete Carrier manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual Carrier AQUAZONE 50PSW036-360 - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the Carrier AQUAZONE 50PSW036-360, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the Carrier AQUAZONE 50PSW036-360, that we can find in the current document
3. Tips how to use the basic functions of the device Carrier AQUAZONE 50PSW036-360 - which should help us in our first steps of using Carrier AQUAZONE 50PSW036-360
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with Carrier AQUAZONE 50PSW036-360
5. FAQ - Frequently Asked Questions
6. Contact detailsInformation about where to look for contact to the manufacturer/service of Carrier AQUAZONE 50PSW036-360 in a specific country, if it was not possible to solve the problem on our own.

Do you have a question concerning Carrier AQUAZONE 50PSW036-360?

Use the form below

If you did not solve your problem by using a manual Carrier AQUAZONE 50PSW036-360, ask a question using the form below. If a user had a similar problem with Carrier AQUAZONE 50PSW036-360 it is likely that he will want to share the way to solve it.

Copy the text from the picture

Comments (0)