    GPC 13 SEER R-410A Package Air Conditioners with R-410A Copyright © 2008 - 2010 Goodman Manufacturing Company, L.P. RT6322006r6 September 2010 This manual is to be used by qualified, professionally trained HV AC technicians only . Goodman does not assume any responsibility for property damage or personal injury due to improper service procedures o ...

  • Goodmans GPC1324H41A - page 2

    PRODUCT IDENTIFICA TION 2 The model and manufacturing number are used for positive identification of component parts used in manufacturing. Please use these numbers when requesting service or parts information. WARNING WARNING HIGH VOLTAGE! Disconnect ALL power before servicing or installing this unit. Multiple power sources may be present. Failure ...

  • Goodmans GPC1324H41A - page 3

    PRODUCT IDENTIFICA TION 3 The model and manufacturing number are used for positive identification of component parts used in manufacturing. Please use these numbers when requesting service or parts information. The United States Environmental Protection Agency (“EPA”) has issued various regulations re- garding the introduction and disposal of r ...

  • Goodmans GPC1324H41A - page 4

    4 PRODUCT DESIGN GPC Package Cooling Units are designed for outdoor instal- lations only in either residential or light commercial applica- tions. The connecting ductwork (Supply and Return) can be con- nected for either horizontal or vertical airflow. In the vertical application a matching Roof Curb is recommended. A return air filter must be inst ...

  • Goodmans GPC1324H41A - page 5

    PRODUCT DESIGN 5 In installations where the unit is installed above ground level and not serviceable from the ground (Example: Roof Top in- stallations), the installer must provide service platform for ser- vice person with rails or guards in accordance with local codes or ordinances or in their absence with the latest edition of the Uniform Mechan ...

  • Goodmans GPC1324H41A - page 6

    6 PRODUCT DIMENSIONS GPC13[24-60]H41** B A 66” Ch ass i s M o d el A B G P C 132 4 33 3 0½ G P C 133 0 33 3 0½ G P C 133 6 33 3 5½ G P C 134 2 33 3 5½ G P C 134 9 33 3 5½ La rg e GPC 134 8 33 3 8½ G P C 136 0 33 3 8½ D i men s ions i n i nc he s Sm a ll Me d i u m ...

  • Goodmans GPC1324H41A - page 7

    ACCESSORIES 7 GPC13[24-60]H41** P a rt Nu m b e r De s cr i p t i on O T 18- 60 A O ut door T her mosta t Ki t w /Loc kout S t at O T /EHR18-60 Em e r genc y Heat Rel ay Ki t HKR El ectric Heat Ki t PCCP101- 103 Roof C ur b PCP 101- 103 Dow nflow Pl e num Ki t PCP 101- 103R8 Dow nflow Pl e num Ki t w / R - 8 In s ul ati on G PCED101- 103 Dow nflow ...

  • Goodmans GPC1324H41A - page 8

    8 PRODUCT DESIGN ELECTRICAL DA T A (*Blower Only , Heat Mode) All wires and overcurrent protection devices are sized for use with electric heaters only and without refrigeration. If heaters are not installed with above wire size, overheating and fire could occur. See PACKAGE COOLING SPECIFICATIONS section for minimum circuit ampacity and maximum ov ...

  • Goodmans GPC1324H41A - page 9

    BLOWER PERFORMANCE DA T A 9 Dry Coil Data NOTES: 1. Data shown is Dry Coil. Wet Coil Pressure Drop is approximate. 2. 0.1" H 2 O, for 2 row indoor coil; 0.2” H 2 O, for 3 row indoor coil; and 0.3” H 2 O, for 4 row indoor coil. 3. Data shown does not include filter pressure drop, approx. 0.08” H 2 O. 4. Reduce airflow by 2% for 208V opera ...

  • Goodmans GPC1324H41A - page 10

    10 BLOWER PERFORMANCE DA T A 30 40 50 60 70 80 90 110 1 2 0 100 13 0 140 15 0 100 90 80 70 60 50 40 30 20 10 OUT P UT B TU/ H R x 10 0 0 BT U OUTPUT vs TEMPER AT URE RISE CHART TEMPERAT URE RISE 600 C FM 700 900 1000 1100 1200 140 0 160 0 1800 2000 220 0 240 0 C F M FORMULA S BTU OUTPUT = CFM x 1.08 x RISE RISE = BTU OUTPUT 1.0 8 ÷ CF M 800 ...

  • Goodmans GPC1324H41A - page 11

    P ACKAGE COOLING SPECIFICA TIONS 11 GPC13[24-30]H41AA IMPORTANT: While this data is presented as a guide, it is important to electrically connect the unit and properly size wires and fuses/circuit breakers in accordance with the National Electrical Code and/or all local codes. Data shown is w/o electric heaters. (1) Maximum Overcurrent Protection D ...

  • Goodmans GPC1324H41A - page 12

    P ACKAGE COOLING SPECIFICA TIONS 12 IMPORTANT: While this data is presented as a guide, it is important to electrically connect the unit and properly size wires and fuses/circuit breakers in accordance with the National Electrical Code and/or all local codes. Data shown is w/o electric heaters. (1) Maximum Overcurrent Protection Device: MUST use Ti ...

  • Goodmans GPC1324H41A - page 13

    P ACKAGE COOLING SPECIFICA TIONS 13 GPC13[48-60]H41BA IMPORTANT: While this data is presented as a guide, it is important to electrically connect the unit and properly size wires and fuses/circuit breakers in accordance with the National Electrical Code and/or all local codes. Data shown is w/o electric heaters. (1) Maximum Overcurrent Protection D ...

  • Goodmans GPC1324H41A - page 14

    14 COOLING PERFORMANCE DA T A GPC1324H41AA MOD E L: GP C1 324 H4 1A* EX PAN DE D P ER F O R MANC E D ATA C OOLI NG OP ER AT I ON De si g n S u b coo li n g , 1 2± 3 ° F @ th e l i q u i d a cce ss f i tti n g co n n ect i o n A H R I 95 t e st co n d i t i o n s . Des i g n S u p e r h e at 8± 3 ° F @ t h e co m p re s s or s uc tio n a c ce ss ...

  • Goodmans GPC1324H41A - page 15

    15 COOLING PERFORMANCE DA T A GPC1324H41AA MOD EL : GP C1 324 H4 1A* EX PAN DE D P ER F O R MANC E D ATA C OOL I NG OP ER ATI ON De si g n S u b coo li n g , 1 2± 3 ° F @ th e l i qu i d a cce ss fi tti ng co n n ect i o n A H R I 95 t e st co n d i ti o n s . Des i g n S u p e r h e at 8± 3 ° F @ th e co m p re s s or suc ti on ac c ess f i tt ...

  • Goodmans GPC1324H41A - page 16

    16 COOLING PERFORMANCE DA T A GPC1330H41AA MOD E L : G P C 1330H 4 1A* EX PAN DE D P ER F O R M AN C E D ATA C OOL ING OPER AT ION D es ign S ub c oo l ing , 1 2 ± 3 ° F @ t he li qu id ac c e s s f it t ing c o nn e c tio n A H R I 9 5 t es t c o nd itio ns. De s ig n Su p erh e a t 8 ± 3 °F @ t h e c omp r e s s o r s uc t io n a c ce ss f it ...

  • Goodmans GPC1324H41A - page 17

    17 COOLING PERFORMANCE DA T A GPC1330H41AA MOD E L : G P C 1330H 4 1A* EX PAN DE D P ER F O R M ANC E D ATA C OOL ING OPER AT ION D es ign S u bc oo l in g, 1 2 ± 3 ° F @ th e liqu id ac c e s s f it t ing c o nn e c tio n A H R I 9 5 t es t c on dit io n s. D e s ig n Sup e rh ea t 8 ±3 °F @ t h e c omp r e s s o r s uc t io n a c ce ss f it t ...

  • Goodmans GPC1324H41A - page 18

    18 COOLING PERFORMANCE DA T A GPC1336H41AA MOD E L : G P C 1336H41A * EX PAN DE D P ER F O R MANC E D ATA C OOLI NG OP ER AT I ON De si g n S u b coo li n g , 1 2± 3 ° F @ th e l i q u i d a cce ss f i tti n g co n n ect i o n A HR I 95 t e st co n d i t i o n s . Des i g n S u p e r h e at 8± 3 ° F @ t h e co m p re s s or s uc tio n a c c e s ...

  • Goodmans GPC1324H41A - page 19

    19 COOLING PERFORMANCE DA T A GPC1336H41AA MOD E L : G P C 1336H41A * EX PAN DE D P ER F O R MANC E D AT A C OOLI NG OP ER AT I ON De si g n S u b coo li n g , 1 2± 3 ° F @ th e l i qu i d a cce ss fi tti ng co n n ect i o n A H R I 95 t e st co n d i ti o n s . Des i g n S u p e r h e at 8± 3 ° F @ th e co m p re s s or suc ti on ac c ess f i ...

  • Goodmans GPC1324H41A - page 20

    20 COOLING PERFORMANCE DA T A GPC1342H41AA MOD E L : G P C 1342H41A * EX PAN DE D P ER F O R M AN C E D ATA C OOL I NG OP ER ATI ON De si g n S u b coo li n g , 1 2± 3 ° F @ th e l i q u i d a cce ss f i tti n g co n n ect i o n A H R I 95 t e st co n d i t i o n s . Des i g n S u p e r h e at 8± 3 ° F @ t h e co m p re s s or s uc tio n a c ce ...

  • Goodmans GPC1324H41A - page 21

    21 COOLING PERFORMANCE DA T A GPC1342H41AA MOD E L : G P C 1342H41A * EX PAN DE D P ER F O R MANC E D AT A C OOLI NG OP ER AT I ON De si g n S u b coo li n g , 1 2± 3 ° F @ th e l i qu i d a cce ss fi tti ng co n n ect i o n A H R I 95 t e st co n d i ti o n s . Des i g n S u p e r h e at 8± 3 ° F @ th e co m p re s s or suc ti on ac c ess f i ...

  • Goodmans GPC1324H41A - page 22

    22 COOLING PERFORMANCE DA T A GPC1348H41BA MOD E L: GP C 1348H41** EX PAN DE D P ER F O R MANC E D ATA C OOLI NG OP ER AT I ON De si g n S u b coo li n g , 1 2± 3 ° F @ th e l i q u i d a cce ss f i tti n g co n n ect i o n A H R I 95 t e st co n d i t i o n s . Des i g n S u p e r h e at 8± 3 ° F @ t h e co m p re s s or s uc tio n a c ce ss f ...

  • Goodmans GPC1324H41A - page 23

    23 COOLING PERFORMANCE DA T A GPC1348H41BA MOD E L: GP C 1348H41** EX PAN DE D P ER FO R MANC E D ATA C OOL ING OP ER AT ION De si g n S u b coo li n g , 1 2± 3 ° F @ th e l i qu i d a cce ss fi tti ng co n n ect i o n A H R I 95 t e st co n d i ti o n s . Des i g n S u p e r h e at 8± 3 ° F @ th e co m p re s s or suc ti on ac c ess f i tting ...

  • Goodmans GPC1324H41A - page 24

    24 COOLING PERFORMANCE DA T A GPC1360H41BA MOD E L: GP C 1360H41** EX PAN DE D P ER F O R MANC E D ATA C OOLI NG OP ER AT I ON De si g n S u b coo li n g , 1 2± 3 ° F @ th e l i q u i d a cce ss f i tti n g co n n ect i o n A H R I 95 t e st co n d i t i o n s . Des i g n S u p e r h e at 8± 3 ° F @ t h e co m p re s s or s uc tio n a c ce ss f ...

  • Goodmans GPC1324H41A - page 25

    25 COOLING PERFORMANCE DA T A GPC1360H41BA MOD E L: GP C 1360H41** EX PAN DE D P ER FO R MANC E D ATA C OOL ING OP ER AT ION De si g n S u b coo li n g , 1 2± 3 ° F @ th e l i qu i d a cce ss fi tti ng co n n ect i o n A H R I 95 t e st co n d i ti o n s . Des i g n S u p e r h e at 8± 3 ° F @ th e co m p re s s or suc ti on ac c ess f i tting ...

  • Goodmans GPC1324H41A - page 26

    26 COOLING PERFORMANCE DA T A PERFORMANCE TEST All data based upon listed indoor dry bulb temperature. .00 inches external static pressure on coil of outdoor section. Indoo r air cubic feet per minute (CFM) as listed in the Performance Data Sheets: If conditions vary from this, results will change as follows: 1. As indoor dry bulb temperatures incr ...

  • Goodmans GPC1324H41A - page 27

    WIRING DIAGRAMS 27 WARN I NG HIGH V OLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT . MULTI PLE PO WER S OUR CES MA Y BE PRESENT . F AILURE TO DO SO MAY CAUSE PROPERTY DAM AGE, PERSONAL INJURY OR DEATH. Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring. NOTE #4 FC NOTE # ...

  • Goodmans GPC1324H41A - page 28

    28 WIRING DIAGRAMS Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring. WARN I NG HIGH V OLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT . MULTI PLE PO WER S OUR CES MA Y BE PRESENT . F AILURE TO DO SO MAY CAUSE PROPERTY DAM AGE, PERSONAL INJURY OR DEATH. GPC1360H41BA 2 3 ...

  • Goodmans GPC1324H41A - page 29

    29 GPC1324H41AB GPC1330H41AB GPC1336H41AB GPC 13 SEER R-410A 5 mm Package Air Conditioners GPC Package Cooling Units are designed for outdoor instal- lations only in either residential or light commercial applica- tions. The connecting ductwork (Supply and Return) can be con- nected for either horizontal or vertical airflow. In the vertical applica ...

  • Goodmans GPC1324H41A - page 30

    30 PRODUCT DESIGN Location and Clearances NOTE: To ensure proper condensate drainage, unit must be installed in a level position. 36" 36" 10" UNIT WALL 36" Outside Slab Installation - Horizontal (H) Minimum clearances are required to avoid air recirculation and keep the unit operating at peak efficiency. 36" 36" 24&quo ...

  • Goodmans GPC1324H41A - page 31

    P ACKAGE COOLING SPECIFICA TIONS 31 MODELS WITH 5MM COILS GPC13[24-36]H41AB IMPORTANT: While this data is presented as a guide, it is important to electrically connect the unit and properly size wires and fuses/circuit breakers in accordance with the National Electrical Code and/or all local codes. Data shown is w/o electric heaters. (1) Maximum Ov ...

  • Goodmans GPC1324H41A - page 32

    P ACKAGE COOLING SPECIFICA TIONS 32 MODELS WITH 5MM COILS GPC1342H41AB GPC1349H41AA GPC1360H41BB IMPORTANT: While this data is presented as a guide, it is important to electrically connect the unit and properly size wires and fuses/circuit breakers in accordance with the National Electrical Code and/or all local codes. Data shown is w/o electric he ...

  • Goodmans GPC1324H41A - page 33

    33 COOLING PERFORMANCE DA T A 5MM COILS GPC1324H41AB MOD E L : GPC 1324H 41A * EX PAN DE D P ER FO R M ANC E D AT A C OOL ING OP ER AT IO N Ou t doo r A m bi en t Te mpera ture 65 75 8 5 95 10 5 115 E nt e ri n g In d o o r W et B u lb T em p e r at ur e I D B * A i r f l o w 5 96 36 77 15 9 6 36 77 15 96 36 7 7 15 9 6 3 6 7 7 1 5 96 36 77 15 9 6 3 ...

  • Goodmans GPC1324H41A - page 34

    34 COOLING PERFORMANCE DA T A 5MM COILS GPC1324H41AB MOD E L : GP C 1324H41 A * EX PAN DE D P ER F O R MANC E D ATA CO O LI N G O PE RA TI O N O ut d o or A m b i en t T em per atu r e 65 75 8 5 95 10 5 115 E nte ri ng I nd oor Wet Bul b T e m pe r a ture I D B * A i r f l o w 5 96 36 77 15 9 6 36 77 15 96 36 7 7 15 9 6 3 6 7 7 1 5 96 36 77 15 9 6 ...

  • Goodmans GPC1324H41A - page 35

    35 COOLING PERFORMANCE DA T A 5MM COILS GPC1330H41AB MOD EL: GPC 1330H41A * EX PAN DE D P E R F O R M ANC E D ATA C OOL ING OP ER AT I ON Ou t doo r A m bi e nt Te mpera ture 65 75 8 5 9 5 10 5 115 E nt e ri n g In d oo r W e t B ulb T e m per a tu re I D B * A i r f l o w 5 96 36 77 15 9 6 36 77 15 96 36 7 7 15 9 6 3 6 7 7 1 5 96 36 77 15 9 6 36 7 ...

  • Goodmans GPC1324H41A - page 36

    36 COOLING PERFORMANCE DA T A 5MM COILS GPC1330H41AB MOD EL: GPC 1330H41A * EX PAN DE D P E R F O R M ANC E D AT A C OOL I NG OP E R AT ION Ou t doo r A m bi e nt Te mpera ture 65 75 8 5 9 5 10 5 115 E nt eri ng Ind oo r W e t B ulb T e m per a tu re I D B * A i r f l o w 5 96 36 77 15 9 6 36 77 15 96 36 7 7 15 9 6 3 6 7 7 1 5 96 36 77 15 9 6 36 77 ...

  • Goodmans GPC1324H41A - page 37

    37 COOLING PERFORMANCE DA T A 5MM COILS GPC1336H41AB MOD E L: GPC 1336H 41A * EX PA N DE D P ER F O R M AN C E D AT A C OOL ING OP ER AT I ON Ou t doo r A mbi e nt Te m pera ture 65 75 8 5 95 10 5 115 E nt eri ng Ind oo r W et B ulb T e m per atu re I D B * A i r f l o w 5 9 6 36 77 15 9 6 3 6 7 7 15 96 36 7 7 1 5 9 6 3 6 7 7 1 5 96 36 77 15 9 6 36 ...

  • Goodmans GPC1324H41A - page 38

    38 COOLING PERFORMANCE DA T A 5MM COILS GPC1336H41AB MOD E L: GP C 1336H41A * EX PA N DE D P ER F O R M AN C E D ATA C OOLI NG OP ER ATI ON O ut d o o r A m b i ent T em p er atu r e 65 75 8 5 95 10 5 115 E n ter i n g Ind oo r W e t Bu lb T em p e r at u re I D B * A i r f l o w 5 96 36 77 15 9 6 36 77 15 96 36 7 7 15 9 6 3 6 7 7 1 5 96 36 77 15 9 ...

  • Goodmans GPC1324H41A - page 39

    39 COOLING PERFORMANCE DA T A 5MM COILS GPC1342H41AB MOD E L: GP C 1342H41A * EX PA N DE D P ER FO R MANC E D ATA C OOL ING OP ER AT ION O ut d o o r A m b i ent T em p er atu r e 65 75 8 5 95 10 5 115 E n ter i ng In d o o r W e t Bu lb T em p er a t u r e I D B * A i r f l o w 5 96 36 77 15 9 6 36 77 15 96 36 7 7 15 9 6 3 6 7 7 1 5 96 36 77 15 9 ...

  • Goodmans GPC1324H41A - page 40

    40 COOLING PERFORMANCE DA T A 5MM COILS GPC1342H41AB MOD EL: GP C 1342H41A * EX PAN DE D P ER F O R MAN C E D ATA C O OL ING OP ER AT I ON Ou t doo r A mbi e nt Tempe r a ture 65 75 8 5 95 10 5 115 E nte r i ng I nd oor W e t Bul b T e m pe r a tur e I D B * A i r f l o w 5 96 36 77 15 9 6 36 77 15 96 36 7 7 15 9 6 3 6 7 7 1 5 96 36 77 15 9 6 36 77 ...

  • Goodmans GPC1324H41A - page 41

    41 COOLING PERFORMANCE DA T A 5MM COILS GPC1349H41AA MOD EL: GP C 1349H41A * E XP A ND E D PE RF O RM A N CE DA T A C OO LIN G OP E R ATION O ut d o o r A m b i en t T em p er at u r e 65 75 8 5 95 10 5 115 E nte r i ng I nd oor We t Bul b T e m pe r a ture I D B * A i r f l o w 5 96 36 77 15 9 6 36 77 15 96 36 7 7 15 9 6 3 6 7 7 1 5 96 36 77 15 9 ...

  • Goodmans GPC1324H41A - page 42

    42 COOLING PERFORMANCE DA T A 5MM COILS GPC1349H41AA MOD E L: GP C 1349H41A * EX PA N DE D P ER F O R M AN C E D ATA C OOLI NG OP ER ATI ON O ut d o o r A m b i ent T em p er atu r e 65 75 8 5 95 10 5 115 E n ter i n g Ind oo r W e t Bu lb T em p e r at u re I D B * A i r f l o w 5 96 36 77 15 9 6 36 77 15 96 36 7 7 15 9 6 3 6 7 7 1 5 96 36 77 15 9 ...

  • Goodmans GPC1324H41A - page 43

    43 COOLING PERFORMANCE DA T A GPC1360H41BB 5MM COILS MOD E L: GP C 1360H41B* EX PAN DE D P ER F O R M AN C E D ATA C OOLI NG OP ER AT I ON O ut d o o r A m b i ent T em p er atu r e 65 75 8 5 95 10 5 115 E n ter i ng In d o o r W e t Bu lb T em p er a t u r e I D B * A i r f l o w 5 96 36 77 15 9 6 36 77 15 96 36 7 7 15 9 6 3 6 7 7 1 5 96 36 77 15 ...

  • Goodmans GPC1324H41A - page 44

    44 COOLING PERFORMANCE DA T A GPC1360H41BB 5MM COILS MOD E L: GP C 1360H41B* EX PAN DE D P ER F O R M AN C E D ATA C OOLI NG OP ER ATI ON O ut d o o r A m b i ent T em p er atu r e 65 75 8 5 95 10 5 115 E n ter i ng In d o o r W e t B u lb T em p er at ur e I D B * A i r f l o w 5 96 36 77 15 9 6 36 77 15 96 36 7 7 15 9 6 3 6 7 7 1 5 96 36 77 15 9 ...

  • Goodmans GPC1324H41A - page 45

    45 COOLING PERFORMANCE DA T A PERFORMANCE TEST All data based upon listed indoor dry bulb temperature. .00 inches external static pressure on coil of outdoor section. Indoo r air cubic feet per minute (CFM) as listed in the Performance Data Sheets: If conditions vary from this, results will change as follows: 1. As indoor dry bulb temperatures incr ...

  • Goodmans GPC1324H41A - page 46

    46 WIRING DIAGRAMS Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring. WARN I NG HIGH V OLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT . MULTI PLE PO WER S OUR CES MA Y BE PRESENT . F AILURE TO DO SO MAY CAUSE PROPERTY DAM AGE, PERSONAL INJURY OR DEATH. GPC13[24-42]H41AB ...

  • Goodmans GPC1324H41A - page 47

    WIRING DIAGRAMS 47 WARN I NG HIGH V OLTAGE! DISCONNECT ALL POWER BEFORE SERVICING OR INSTALLING THIS UNIT . MULTI PLE PO WER S OUR CES MA Y BE PRESENT . F AILURE TO DO SO MAY CAUSE PROPERTY DAM AGE, PERSONAL INJURY OR DEATH. Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring. GPC1360H41BB 2 3 ...

Manufacturer Goodmans Category Air Conditioner

Documents that we receive from a manufacturer of a Goodmans GPC1324H41A can be divided into several groups. They are, among others:
- Goodmans technical drawings
- GPC1324H41A manuals
- Goodmans product data sheets
- information booklets
- or energy labels Goodmans GPC1324H41A
All of them are important, but the most important information from the point of view of use of the device are in the user manual Goodmans GPC1324H41A.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals Goodmans GPC1324H41A, service manual, brief instructions and user manuals Goodmans GPC1324H41A. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product Goodmans GPC1324H41A.

A complete manual for the device Goodmans GPC1324H41A, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use Goodmans GPC1324H41A by users. Manuals are usually written by a technical writer, but in a language understandable to all users of Goodmans GPC1324H41A.

A complete Goodmans manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual Goodmans GPC1324H41A - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the Goodmans GPC1324H41A, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the Goodmans GPC1324H41A, that we can find in the current document
3. Tips how to use the basic functions of the device Goodmans GPC1324H41A - which should help us in our first steps of using Goodmans GPC1324H41A
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with Goodmans GPC1324H41A
5. FAQ - Frequently Asked Questions
6. Contact detailsInformation about where to look for contact to the manufacturer/service of Goodmans GPC1324H41A in a specific country, if it was not possible to solve the problem on our own.

Do you have a question concerning Goodmans GPC1324H41A?

Use the form below

If you did not solve your problem by using a manual Goodmans GPC1324H41A, ask a question using the form below. If a user had a similar problem with Goodmans GPC1324H41A it is likely that he will want to share the way to solve it.

Copy the text from the picture

Comments (0)