    SIMATIC NET Industrial Ethernet Electrical Lean Switch Installation Instructions Preface, Contents Introduction 1 Functions 2 Network Topologies 3 Ports and Displays 4 Installation 5 Diagnostics over Industrial Ethernet 6 Technical Specifications 7 Further Support 8 Notes on the CE Mark 9 Glossary 10 Index 11 References 12 Release 12/2002 A5E001520 ...

  • Siemens Electrical Lean Switch - page 2

    Industrial Ethernet 2 A5E00152007-03 Classification of Safety-Related Notices This document contains notices which you should observe to ensure your own personal safety, as well as to protec t the product and connected equipment. These notices are highlighted in the manual by a warning triangle and are marked as follows according to the level of da ...

  • Siemens Electrical Lean Switch - page 3

    Industrial Ethernet A5E00152007-03 3 Trademarks SIMATIC  , SIMATIC NET  and SINEC  are registered trademarks of Siemens AG. Third parties using for their own purposes any other names in this document which refer to trademarks might infringe upon the rights of the trademark owners. Safety Instructions Regarding your Product Before you use t ...

  • Siemens Electrical Lean Switch - page 4

    Industrial Ethernet 4 A5E00152007-03 Preface Purpose of the Installation Instructions These installation instructions suppor t you when commissioning in networks with the Electrical Lean Switch (ELS) . Consignment The ELS includes the following components: ● ELS device ● 3-pin plug-in terminal block ● Fittings (brackets, screws) for wall-moun ...

  • Siemens Electrical Lean Switch - page 5

    Preface Industrial Ethernet A5E00152007-03 5 Further Documentation The "SIMATIC NET Industrial Ethernet Twisted Pair and Fiber-Optic Networks" manual contains information on other SI MATIC NET products that you can operate in conjunction with ELS devices in an Industrial Ethernet network. You can download the electronic version of this ne ...

  • Siemens Electrical Lean Switch - page 6

    Preface Industrial Ethernet 6 A5E00152007-03 Personnel Qualification Requirements Only qualified personnel should be allowed to install and work on this equipment. Qualified personnel as referred to in the installation instructions or in the warning notes are defined as persons who are fam iliar with the installation, assembly, startup and operatio ...

  • Siemens Electrical Lean Switch - page 7

    Industrial Ethernet 7 A5E00152007-03 Contents 1 Introduc tion .................................................................................................................. ... 9 1.1 ELS TP40 .......................................................................................................... 10 1.2 ELS TP40M .............................. ...

  • Siemens Electrical Lean Switch - page 8

    Preface Industrial Ethernet 8 A5E00152007-03 6.3.5 Management Menus .......................................................................................... 60 6.3.6 Switch In formation ............................................................................................. 61 6.3.7 IP Address Informat ion ................................... ...

  • Siemens Electrical Lean Switch - page 9

    Industrial Ethernet 9 A5E00152007-03 1 Introduction 1 With the Electrical Lean Switch ELS pr oduct generation, you can set up powerful Fast Ethernet networks with a small number of ports in an industrial environment. Nodes can only be attached to the network over twisted-pair ports; in other words, electrical ports. ...

  • Siemens Electrical Lean Switch - page 10

    Introduction Industrial Ethernet 10 A5E00152007-03 1.1 ELS TP40 Possible Attachments ● Two RJ-45 jacks for connecting DTEs ● Two ports with insulation-piercing cont acts for the direct attachment of IE FastConnect (FC) cables Figure 1: ELS TP40 ...

  • Siemens Electrical Lean Switch - page 11

    Introduction Industrial Ethernet A5E00152007-03 11 Properties of the ELS TP40 Two electrical ports (RJ-45 jacks) 10/100 Mbps (half/full duplex) TP connector technology (RJ-45 jack with MDI-X pinning) Max. cable length 10 m (TP Cord or TP XP Cord) In conjunction with IE FC Outlet RJ-45, a total cable length of a maximum of 100 m is permitted. Two el ...

  • Siemens Electrical Lean Switch - page 12

    Introduction Industrial Ethernet 12 A5E00152007-03 1.2 ELS TP40M Possible Attachments ● Two RJ-45 jacks for connecting DTEs ● Two ports with insulation-piercing cont acts for the direct attachment of IE FastConnect (FC) cables Figure 2: ELS TP40M ...

  • Siemens Electrical Lean Switch - page 13

    Introduction Industrial Ethernet A5E00152007-03 13 Properties of the ELS TP40M Two electrical ports (RJ-45 jacks) 10/100 Mbps (half/full duplex) TP connector technology (RJ-45 jack with MDI-X pinning) Max. cable length 10 m (TP Cord or TP XP Cord) In conjunction with IE FC Outlet RJ-45, a total cable length of a maximum of 100 m is permitted. Two e ...

  • Siemens Electrical Lean Switch - page 14

    Introduction Industrial Ethernet 14 A5E00152007-03 1.3 ELS TP80 Possible Attachments ● Eight RJ-45 jacks for connecting DTEs Figure 3: ELS TP80 Properties of the ELS TP80 Eight electrical ports (RJ-45 jacks) 10/100 Mbps (half/full duplex) TP connector technology (RJ-45 jack with MDI-X pinning) Max. cable length 10 m (TP Cord or TP XP Cord) In con ...

  • Siemens Electrical Lean Switch - page 15

    Industrial Ethernet 15 A5E00152007-03 2 Functions 2 This section provides you with an overview of the functions of the Electrical Lean Switch (ELS) product generation. ...

  • Siemens Electrical Lean Switch - page 16

    Introduction Industrial Ethernet 16 A5E00152007-03 The Electrical Lean Switches (ELS) allow the cost-effective setup of Ethernet bus or star structures with switching functionality. The EL S switches are intended for use in a switching cubicle. Note If you use an ELS in a redundant OSM/ESM ring, the redundancy function is not supported. Note The re ...

  • Siemens Electrical Lean Switch - page 17

    Industrial Ethernet 17 A5E00152007-03 3 Network Topologies 3 The following network topologies can be implemented with Electrical Lean Switches. ...

  • Siemens Electrical Lean Switch - page 18

    Network Topologies Industrial Ethernet 18 A5E00152007-03 3.1 Network Topologies with ELS TP40 Attachment of individual remotely located DTEs over ELS TP40 to a TP network Figure 4: ELS TP40 Bus Topology Figure 5: ELS TP40 Star Topology ...

  • Siemens Electrical Lean Switch - page 19

    Network Topologies Industrial Ethernet A5E00152007-03 19 3.2 Network Topologies with ELS TP40M Attachment of individual remotely located DTEs over ELS TP40M to a twisted-pair network Figure 6: ELS TP40M Bus Topology Figure 7: ELS TP40M Star Topology ...

  • Siemens Electrical Lean Switch - page 20

    Network Topologies Industrial Ethernet 20 A5E00152007-03 3.3 Network Topologies with ELS TP80 Figure 8: ELS TP80 Star Topology ...

  • Siemens Electrical Lean Switch - page 21

    Industrial Ethernet 21 A5E00152007-03 4 Ports and Displays 4 This chapter provides you with an overvi ew of the ports and displays of the ELS. ...

  • Siemens Electrical Lean Switch - page 22

    Ports and Displays Industrial Ethernet 22 A5E00152007-03 4.1 Ports and Displays of the ELS TP40 4.1.1 TP Ports Pinning On the ELS TP40, the TP ports are im plemented as RJ-45 jacks and as insulation- piercing contacts with the MDI-X pinning (Medium-Dependent Interface Autocrossover) of a network component. Notice TP Cords or TP-XP Cords with a maxi ...

  • Siemens Electrical Lean Switch - page 23

    Ports and Displays Industrial Ethernet A5E00152007-03 23 Note Ports of partner stations not supporting autonegotiation must be set to 100 Mbps/ half duplex or 10 Mbps half duplex. ...

  • Siemens Electrical Lean Switch - page 24

    Ports and Displays Industrial Ethernet 24 A5E00152007-03 4.1.2 Power Supply The power supply is connected using a 3-pi n plug-in terminal block with a screw locking mechanism. L1+ M PE +24V DC Figure 9: ELS TP40 ...

  • Siemens Electrical Lean Switch - page 25

    Ports and Displays Industrial Ethernet A5E00152007-03 25 ! Warning Industrial Ethernet ELS TP40 switches are designed for operation with safety extra-low voltage. This means that only safety extra-low voltages (SELV) complying with IEC950/EN60950/ VDE0805 can be connected to the power supply terminals. The power supply unit to supply the ELS TP40 m ...

  • Siemens Electrical Lean Switch - page 26

    Ports and Displays Industrial Ethernet 26 A5E00152007-03 4.1.3 Displays Power display (green LED) The status of the power supply is signaled by a green LED: Status Meaning lit green Power supply L+ is connected Not lit Power supply L+ is not connected or <14 V Port status display (green/yellow LEDs) The status of the ports is signaled by four LE ...

  • Siemens Electrical Lean Switch - page 27

    Ports and Displays Industrial Ethernet A5E00152007-03 27 4.2 Ports and Displays of the ELS TP40M 4.2.1 TP Ports Pinning On the ELS TP40M, the TP ports are implemented as RJ-45 jacks and as insulation-piercing contacts with t he MDI-X pinning (Medium-Dependent Interface Autocrossover) of a network component. Notice TP Cords or TP-XP Cords with a max ...

  • Siemens Electrical Lean Switch - page 28

    Ports and Displays Industrial Ethernet 28 A5E00152007-03 Note Ports of partner stations not supporting autonegotiation must be set to 100 Mbps/ half duplex or 10 Mbps half duplex. ...

  • Siemens Electrical Lean Switch - page 29

    Ports and Displays Industrial Ethernet A5E00152007-03 29 4.2.2 Power Supply The power supply is connected using a 3-pi n plug-in terminal block with a screw locking mechanism. L1+ M PE +24V DC Figure 10: ELS TP40M ...

  • Siemens Electrical Lean Switch - page 30

    Ports and Displays Industrial Ethernet 30 A5E00152007-03 ! Warning Industrial Ethernet ELS TP40M switches are designed for operation with safety extra-low voltage. This means that only safety extra-low voltages (SELV) complying with IEC950/EN60950/ VDE0805 can be connected to the power supply terminals. The power supply unit to supply the ELS TP40M ...

  • Siemens Electrical Lean Switch - page 31

    Ports and Displays Industrial Ethernet A5E00152007-03 31 4.2.3 Displays Power Display (green and red LEDs) The status of the ELS TP40M is indicated by a green and a red LED: Status Meaning lit green Power supply L+ is connected not lit Power supply L+ is not connected or <14 V lit or flashing red The red LED should go off after "Pow er on&q ...

  • Siemens Electrical Lean Switch - page 32

    Ports and Displays Industrial Ethernet 32 A5E00152007-03 4.3 Ports and Displays of the ELS TP80 4.3.1 TP Ports Pinning On the ELS TP80, the TP ports are implement ed as RJ-45 jacks with the MDI-X pinning (Medium-Dependent Interface Auto crossover) of a network component. Notice TP Cords or TP-XP Cords with a maximum length of 10 m can be connected ...

  • Siemens Electrical Lean Switch - page 33

    Ports and Displays Industrial Ethernet A5E00152007-03 33 4.3.2 Power Supply The power supply is connected using a 3-pi n plug-in terminal block with a screw locking mechanism. Figure 11: ELS TP80 ! Warning Industrial Ethernet ELS TP80 switches are designed for operation with safety extra-low voltage. This means that only safety extra-low voltages ( ...

  • Siemens Electrical Lean Switch - page 34

    Ports and Displays Industrial Ethernet 34 A5E00152007-03 4.3.3 Displays Power display (green LED) The status of the power supply is signaled by a green LED: Status Meaning lit green Power supply L+ is connected Not lit Power supply L+ is not connected or <14 V Port status display (green/yellow LEDs) The status of the ports is signaled by eight L ...

  • Siemens Electrical Lean Switch - page 35

    Industrial Ethernet 35 A5E00152007-03 5 Installation and Maintenance 5 ...

  • Siemens Electrical Lean Switch - page 36

    Installation and Maintenance Industrial Ethernet 36 A5E00152007-03 5.1 Consignment Unpacking, Checking the Consignment 1. Check that the consignment includes the following components: – ELS device – Mounting brackets, screws and terminal block – Information on the Product – Manual Collection CD 2. Check each component for any damage. ! Warn ...

  • Siemens Electrical Lean Switch - page 37

    Installation and Maintenance Industrial Ethernet A5E00152007-03 37 5.2 Installation| There are several ways of installing the ELS: ● Installation on a 35 mm standard rail ● Installation on a SIMATIC S7-300 rail ● Installation in a 19" cabinet (along with other ELS modules in the 19" mounting system) ● Wall mounted Note • Remembe ...

  • Siemens Electrical Lean Switch - page 38

    Installation and Maintenance Industrial Ethernet 38 A5E00152007-03 DIN Rail Mounting 1. Install the ELS on a 35 mm standard rail complying with DIN EN 50022. 2. Fit the ELS on to the rail from above and press in the bottom of the device until the catch engages. 3. Connect the electrical cables and the terminal block for the power supply. Figure 12: ...

  • Siemens Electrical Lean Switch - page 39

    Installation and Maintenance Industrial Ethernet A5E00152007-03 39 Removing from a Standard Rail To remove the ELS from the rail, firs t disconnect the TP cables and pull off the terminal block. Then pull down the device and release it from the rail. Figure 13. Removing from the Standard Rail ...

  • Siemens Electrical Lean Switch - page 40

    Installation and Maintenance Industrial Ethernet 40 A5E00152007-03 Installation on a SIMATIC S7-300 Standard Rail 1. First secure the supplied brackets to the left and right of the ELS. 2. Fit the guide on the top of the ELS casing into the S7 rail. 3. Screw the ELS to the bottom of the standard rail. Figure 14. Installing an ELS TP40 on a SIMATI C ...

  • Siemens Electrical Lean Switch - page 41

    Installation and Maintenance Industrial Ethernet A5E00152007-03 41 Installation in a 19" Cubicle To install in the 19" cubicle, you require the two securing brackets supplied. You can achieve the 19'' width • with 3 ELS devices Follow the steps outlined below: 1. First screw the ELS switches to t he supplied mounting plates at ...

  • Siemens Electrical Lean Switch - page 42

    Installation and Maintenance Industrial Ethernet 42 A5E00152007-03 Wall Mounting Please note that the ELS must be grounded wi th low resistance via the two holding brackets. It is also possible to ground t he device suing the PE screw terminal on the terminal block. S7 Standard Rail The device is grounded either via the tw o mounting brackets or th ...

  • Siemens Electrical Lean Switch - page 43

    Installation and Maintenance Industrial Ethernet A5E00152007-03 43 6. Insert the wires of the IE FC TP cable in to the contact cover according to the color code. 7. Press down both contact covers to establish contact w ith the cores. 8. Close and screw dow n the cover of the TP ports with insulation piercing contacts. If you do not have an IE FastC ...

  • Siemens Electrical Lean Switch - page 44

    Installation and Maintenance Industrial Ethernet 44 A5E00152007-03 5.3 Maintenance If a fault develops, please send the modul e to your SIEMENS service department for repair. The devices cannot be repaired on site. ...

  • Siemens Electrical Lean Switch - page 45

    Industrial Ethernet 45 A5E00152007-03 6 Diagnostics over Industrial Ethernet 6 ...

  • Siemens Electrical Lean Switch - page 46

    Diagnostics over Industrial Ethernet Industrial Ethernet 46 A5E00152007-03 6.1 Introduction The ELS has a configuration and diagnostic interface. The device can be configured and its curr ent status displayed using a graphic interface. All configuration or status data is available as MIB objects and can be modified and displayed within the graphic ...

  • Siemens Electrical Lean Switch - page 47

    Diagnostics over Industrial Ethernet Industrial Ethernet A5E00152007-03 47 6.2 Configuration The ELS can be configured in the following ways: ● Automatic IP address assignment using DHCP (factory setting) ● Manual IP address assignment 6.2.1 Automatic IP Address Assignment using DHCP (Factory Setting) If a DHCP server is available in the netwo ...

  • Siemens Electrical Lean Switch - page 48

    Diagnostics over Industrial Ethernet Industrial Ethernet 48 A5E00152007-03 How to install the PST: 1. Start the installation program "pst_i nstall.exe" on the supplied CD. All the necessary files are then copied to the se lected folder (the default is the folder: "c:siemenspst"). 2. You can now start the application in the in ...

  • Siemens Electrical Lean Switch - page 49

    Diagnostics over Industrial Ethernet Industrial Ethernet A5E00152007-03 49 4. Once you have selected the language, the menu shown in Figure 6-2 opens. Select a network adapter with Settings -> Netw ork Adapter . All the network interfaces (maximum of four) found in your system will be listed. Select the network adapter you require by clicking on ...

  • Siemens Electrical Lean Switch - page 50

    Diagnostics over Industrial Ethernet Industrial Ethernet 50 A5E00152007-03 Windows 2000 – DLC Protocol Installation ● Select Start -> Settings -> Control Panel . ● Click on the "Network and Dial-up Connections" icon. ● From the list of network adapters, sele ct the adapter for which you are going to install the DLC protocol ...

  • Siemens Electrical Lean Switch - page 51

    Diagnostics over Industrial Ethernet Industrial Ethernet A5E00152007-03 51 User Interface of the PST After starting the PST, the menu shown in Figure 6-3 opens with the various areas. Figure 6-3 SIMATIC NET PST - User Interface ● Menu bar Here you can execute individual actions or specify the configuration of PST. The actions available in the men ...

  • Siemens Electrical Lean Switch - page 52

    Diagnostics over Industrial Ethernet Industrial Ethernet 52 A5E00152007-03 Changing the Language Package When you first started the PST, you were asked to select a specific language. You can also change the selected language after this first startup. To change the language, select Settings -> Language . Here you will find a list with all availab ...

  • Siemens Electrical Lean Switch - page 53

    Diagnostics over Industrial Ethernet Industrial Ethernet A5E00152007-03 53 Configuring the ELS To configure an ELS, follow the steps outlined below: 1. Select Netw ork -> Browse in the PST menu. The progress bar found in Figure 6-5 is displayed. Figure 6-5 Progress Bar "Brow sing Network". You can also start this action directly by cli ...

  • Siemens Electrical Lean Switch - page 54

    Diagnostics over Industrial Ethernet Industrial Ethernet 54 A5E00152007-03 2. The component tree now contains a list of all ELS devices that have been found. Select one of the ELS devices in t he component tree by double-clicking on it. The folder of this ELS is opened and a further icon appears. Click on this icon. The data of the interface is dis ...

  • Siemens Electrical Lean Switch - page 55

    Diagnostics over Industrial Ethernet Industrial Ethernet A5E00152007-03 55 ● IP address IP address of the ELS (maximum range per field: 0 to 255). If you enter an invalid IP address, a warning is displayed and the input is rejected. ● Subnet mask Subnet mask of the ELS (maximum r ange of numbers per field: 0 to 255). ● Router (default gatew a ...

  • Siemens Electrical Lean Switch - page 56

    Diagnostics over Industrial Ethernet Industrial Ethernet 56 A5E00152007-03 4. Start the Web Based Management (WBM) if you require the full range of functions (including settings). Select Module -> Start INC Brow ser . You can also start this action directly using the appropriate icons in the toolbar (see Figure 6-9). Figure 6-9 Direct Start: &qu ...

  • Siemens Electrical Lean Switch - page 57

    Diagnostics over Industrial Ethernet Industrial Ethernet A5E00152007-03 57 6.3 Web Based Management (WBM) 6.3.1 General The ELS includes integrated Web-Based Management; in other words, it can be operated using an Internet browser (such as Microsoft Internet Explorer or Netscape). The modules are operated usi ng a Java applet stored on the ELS that ...

  • Siemens Electrical Lean Switch - page 58

    Diagnostics over Industrial Ethernet Industrial Ethernet 58 A5E00152007-03 6.3.3 Access using WBM How to Access WBM on the ELS 1. Open the Internet browser. 2. Enter the IP address or the URL of the ELS in the address field of the Internet Browser as follows: http://<IP address of ELS> for example http://141.73.10.89 and confirm with [RETURN] ...

  • Siemens Electrical Lean Switch - page 59

    Diagnostics over Industrial Ethernet Industrial Ethernet A5E00152007-03 59 6.3.4 User Interface of the WBM The dialogs of the ELS are made up of a device status field, a menu tree, and a data window. Figure 6-11 SIMATIC NET Network Managem ent User Interface of the ELS ● Device status field The display in the device status field r epresents the L ...

  • Siemens Electrical Lean Switch - page 60

    Diagnostics over Industrial Ethernet Industrial Ethernet 60 A5E00152007-03 6.3.5 Management Menus The WBM of the ELS has the following menu structure: Function Explanation Switch Info Hardware Version Software Version System Contact System Location System Name System Up Time IP Address Info MAC Address IP Address Subnet Mask Default Gateway DHCP E- ...

  • Siemens Electrical Lean Switch - page 61

    Diagnostics over Industrial Ethernet Industrial Ethernet A5E00152007-03 61 6.3.6 Switch Information Clicking the Sw itch Info menu opens the window shown in Figure 6-12. Figure 6-12 Switch Information Window ● Hardw are Version Hardware version of the ELS ● Firmw are Version Version of the ELS firmware ● System Contact In this box, you can en ...

  • Siemens Electrical Lean Switch - page 62

    Diagnostics over Industrial Ethernet Industrial Ethernet 62 A5E00152007-03 ● Get Current Values/Set New Values If you click the "Get Current Values" button, you obtain the values currently stored on the ELS. To transfer the entries in this window to the ELS and to save them there, click on "Set New Values". ...

  • Siemens Electrical Lean Switch - page 63

    Diagnostics over Industrial Ethernet Industrial Ethernet A5E00152007-03 63 6.3.7 IP Address Information Clicking the IP Address Info menu opens the window shown in Figure 6-13. Figure 6-13 IP Address Information Window ● IP Address IP address of the ELS ● Subnet Mask Subnet mask of the ELS ● Default Gatew ay Displays the IP address of the def ...

  • Siemens Electrical Lean Switch - page 64

    Diagnostics over Industrial Ethernet Industrial Ethernet 64 A5E00152007-03 Note The IP address, the subnet mask, and t he default gateway of the ELS can be modified using the PST tool. Automatic IP configuration is possible using DHCP. If the IP address of the ELS is changed, the browser link to the ELS is lost. Close the ELS window in the Internet ...

  • Siemens Electrical Lean Switch - page 65

    Diagnostics over Industrial Ethernet Industrial Ethernet A5E00152007-03 65 6.3.8 E-Mail Configuration Clicking the E-Mail Config menu opens the window shown in Figure 6-14. Figure 6-14 E-Mail Configuration Window When certain faults occur and are detected by the ELS, it can automatically send an E-mail to a selected E-mail address containing an err ...

  • Siemens Electrical Lean Switch - page 66

    Diagnostics over Industrial Ethernet Industrial Ethernet 66 A5E00152007-03 ● Subject In this field, you can enter a subj ect for the E-mail (a maximum of 63 characters). ● SMTP Server IP-Address Here, you enter the IP address of the SM TP server via which the E-mail will be sent. Make sure that the ELS can a ccess the SMTP server (maximum range ...

  • Siemens Electrical Lean Switch - page 67

    Diagnostics over Industrial Ethernet Industrial Ethernet A5E00152007-03 67 6.3.9 Trap Configuration Clicking the Trap Config menu opens the window shown in Figure 6-15. Figure 6-15 Trap Configuration Window If an alarm occurs, the ELS can send traps (alarm messages) to up to two different (network management) stations at the same time. In this menu ...

  • Siemens Electrical Lean Switch - page 68

    Diagnostics over Industrial Ethernet Industrial Ethernet 68 A5E00152007-03 Construction of the Trap report The ELS knows 2 kinds of traps: ● Coldstart ● Change of port status In case of Power On a Coldstart-trap will be sent . If the link-status of a port changes the cu rrent contents of the LED-STATUS Re- gister will be sent. LED-Status: Byte ...

  • Siemens Electrical Lean Switch - page 69

    Diagnostics over Industrial Ethernet Industrial Ethernet A5E00152007-03 69 6.3.10 Event Configuration Clicking the Event Config menu opens the window shown in Figure 6-16. Here, you can set link up/down and cold restart events for E-mail and/or trap recipients. Figure 6-16 Event Configuration Window Select, for example, the first box to m onitor li ...

  • Siemens Electrical Lean Switch - page 70

    Diagnostics over Industrial Ethernet Industrial Ethernet 70 A5E00152007-03 6.3.11 Statistic Information Clicking the Statistic Information menu opens the window shown in Figure 6-17. The ELS has internal statistical counter s that count the number of bad received frames and collisions for each port. The statistical counters have a numeric range fro ...

  • Siemens Electrical Lean Switch - page 71

    Diagnostics over Industrial Ethernet Industrial Ethernet A5E00152007-03 71 6.4 Diagnostics Using SNMP With SNMP (Simple Network Management Protocol), a network management station can configure and monitor SNMP-c ompliant nodes such as the ELS. To make this possible, a management agent is installed in the DTE with which the management station exchan ...

  • Siemens Electrical Lean Switch - page 72

    Diagnostics over Industrial Ethernet Industrial Ethernet 72 A5E00152007-03 6.5 Internet Browser Settings To use the WBM of the ELS, you must ma ke the correct settings in the Internet browser. This section contains inform ation about setting the Internet browsers listed in the following table and the Java Virtual Machines used. You can use this pro ...

  • Siemens Electrical Lean Switch - page 73

    Diagnostics over Industrial Ethernet Industrial Ethernet A5E00152007-03 73 6.5.1 Microsoft Internet Explorer 5.5 or 6.0 1. You can check whether or not you hav e the update version 5.5 or 6.0 of the Internet Explorer as follows: Open the Internet Explorer and select Help (?) -> About Internet Explorer to open the window shown in Figure 6-18. Fig ...

  • Siemens Electrical Lean Switch - page 74

    Diagnostics over Industrial Ethernet Industrial Ethernet 74 A5E00152007-03 2. Select Tools -> Internet Options -> Advanced , to open the window shown in Figure 6-19. Figure 6-19 Microsoft Internet Explorer 6.0 – Advanced Internet Options 3. Make sure that the option "Use Java 2 v1.x.x for <applet>" is selected under the menu ...

  • Siemens Electrical Lean Switch - page 75

    Diagnostics over Industrial Ethernet Industrial Ethernet A5E00152007-03 75 4. If you use a proxy server that onl y accepts DNS registered IP addresses and your ELS is not DNS registered, you may need to connect directly to the ELS. To do this, select Tools -> Internet Options -> Connections . The dialog shown in Figure 6-20 opens. Figure 6-20 ...

  • Siemens Electrical Lean Switch - page 76

    Diagnostics over Industrial Ethernet Industrial Ethernet 76 A5E00152007-03 Select the "LAN Settings" button. The dialog shown in Figure 6-21 opens. Figure 6-21 Microsoft Internet Explorer 6.0 – LAN Settings ...

  • Siemens Electrical Lean Switch - page 77

    Diagnostics over Industrial Ethernet Industrial Ethernet A5E00152007-03 77 5. In this window, disable the proxy server by clicking the "Use a proxy server for your LAN" check box or click the "A dvance" button to open the dialog shown in Figure 6-22. Here you can enter the addresses for which the proxy server is not used. Enter ...

  • Siemens Electrical Lean Switch - page 78

    Diagnostics over Industrial Ethernet Industrial Ethernet 78 A5E00152007-03 6.5.2 Netscape 6.1 or 6.2 In Netscape Communicator, select Edit -> Preferences -> Advanced , to open the window shown in Figure 6-23. Figure 6-23 Netscape 6.2 – Advanced Preferences Window 1. Select "Enable Java" and "Enable JavaScript for Navigator&qu ...

  • Siemens Electrical Lean Switch - page 79

    Diagnostics over Industrial Ethernet Industrial Ethernet A5E00152007-03 79 To do this select Edit -> Preferences -> Advanced -> Proxies to open the window shown in Figure 6-24 and set Direct connection to the Internet. Figure 6-24 Netscape 6.2 – Proxy Preferences Window ...

  • Siemens Electrical Lean Switch - page 80

    Industrial Ethernet 80 A5E00152007-03 7 Technical Specifications 7 ...

  • Siemens Electrical Lean Switch - page 81

    Technical Specifications Industrial Ethernet A5E00152007-03 81 7.1 Technical Specifications of the ELS TP40 Attachments Attachment of DTEs or Network Components over Twisted Pair 2 x RJ-45 jacks with MDI-X pinning 10/100 Mbps (half/full duplex) Attachment of Industrial Ethernet FC TP cables 2 x insulation piercing contacts with MDI-X 10/100 Mbps (h ...

  • Siemens Electrical Lean Switch - page 82

    Technical Specifications Industrial Ethernet 82 A5E00152007-03 Permitted Ambient Conditions/EMC Operating temperature 0°C to +60°C Storage/transport temperature -40°C to +80°C Relative humidity in operation ‹ 95% (no condensation) Operating altitude 2000 m at max. 56 °C ambient temperature 3000 m at max. 50 °C ambient temperature Noise emis ...

  • Siemens Electrical Lean Switch - page 83

    Technical Specifications Industrial Ethernet A5E00152007-03 83 MTBF MTBF 108.85 years Construction Dimensions (W x H x D) in mm 145 x 136.5 x 69 Weight in g 950 Installation options Standard rail S7-300 rail Wall mounted Installation in 19" cubicle Only horizontal installation permitted (ventilation slits top/bottom) Consignment ELS TP40 ● E ...

  • Siemens Electrical Lean Switch - page 84

    Technical Specifications Industrial Ethernet 84 A5E00152007-03 7.2 Technical Specifications of the ELS TP40M Attachments Attachment of DTEs or Network Components over Twisted Pair 2 x RJ-45 jacks with MDI-X pinning 10/100 Mbps (half/full duplex) Attachment of Industrial Ethernet FC TP cables 2 x insulation piercing contacts with MDI-X 10/100 Mbps ( ...

  • Siemens Electrical Lean Switch - page 85

    Technical Specifications Industrial Ethernet A5E00152007-03 85 Aging Time 5 minutes Permitted Ambient Conditions/EMC Operating temperature 0°C to +60°C Storage/transport temperature -40°C to +80°C Relative humidity in operation ‹ 95% (no condensation) Operating altitude 2000 m at max. 56 °C ambient temperature 3000 m at max. 50 °C ambient t ...

  • Siemens Electrical Lean Switch - page 86

    Technical Specifications Industrial Ethernet 86 A5E00152007-03 MTBF MTBF 51 years Construction Dimensions (W x H x D) in mm 145 x 136.5 x 69 Weight in g 950 Installation options Standard rail S7-300 rail Wall mounted Installation in 19" cubicle Only horizontal installation permitted (ventilation slits top/bottom) Consignment ELS TP40M ● ELS ...

  • Siemens Electrical Lean Switch - page 87

    Technical Specifications Industrial Ethernet A5E00152007-03 87 7.3 Technical Specifications of the ELS TP80 Attachments Attachment of DTEs or Network Components over Twisted Pair RJ-45 jacks with MDI-X pinning 10/100 Mbps (half/full duplex) Electrical Data Power Supply 24 V dc supply (18 to 32 V dc) safety extra-low voltage (SELV) Power loss at DC ...

  • Siemens Electrical Lean Switch - page 88

    Technical Specifications Industrial Ethernet 88 A5E00152007-03 Permitted Ambient Conditions/EMC Operating temperature 0°C to +60°C Storage/transport temperature -40°C to +80°C Relative humidity in operation ‹ 95% (no condensation) Operating altitude 2000 m at max. 56°C am bient temperature 3000 m at max. 50°C am bient temperature Noise emis ...

  • Siemens Electrical Lean Switch - page 89

    Industrial Ethernet 89 A5E00152007-03 8 Further Support 8 Who to Contact If you have technical questions about using the described product and your problem is not dealt with in the document ation or in the integrated help system, please contact your Siemens representative or dealer. You will find the addresses: ● in our catalog IK PI ● on the W ...

  • Siemens Electrical Lean Switch - page 90

    Further Support Industrial Ethernet 90 A5E00152007-03 Automation and Drives, Service & Support Service & Support from A&D is available round the clock worldwide. The languages spoken are German and English. French, Italian, and Spanish are also spoken on the authorization hotline. Technical Support Authorization Hotline Europe and A fri ...

  • Siemens Electrical Lean Switch - page 91

    Further Support Industrial Ethernet A5E00152007-03 91 Service & Support on the Internet On the World Wide Web, you will find the very latest information on the entire SIMATIC product range, forexample, answers to frequently asked questions (FAQs), Tips and Tricks, software updates, manuals, and user information. In addition to this free informa ...

  • Siemens Electrical Lean Switch - page 92

    Further Support Industrial Ethernet 92 A5E00152007-03 Training for SIMATIC NET Who to Contact about Training Courses: Siemens AG Trainings-Center für Automati sierungs- und Antriebstechnik A&D PT 49 Kursbüro Östliche Rheinbrückenstraße 50 76181 Karlsruhe Germany Phone: +49 - (0) 721 - 595 - 2917 Fax: +49 - (0) 721 - 595 - 6087 Internet: ht ...

  • Siemens Electrical Lean Switch - page 93

    Industrial Ethernet 93 A5E00152007-03 9 Notes on the CE Mark 9 Product name: SIMATIC NET ELS TP40 6GK1102-6AA00 SIMATIC NET ELS TP40M 6GK1102-6AB00 SIMATIC NET ELS TP80 6GK1102-7AA00 The SIMATIC NET product listed above meet s the requirements of the following EU directives: EMC Directive Directive 89/336/EEC “Elect romagnetic Compatibility" ...

  • Siemens Electrical Lean Switch - page 94

    Notes on the CE Mark Industrial Ethernet 94 A5E00152007-03 Requirements Area of Application Noise emission Noise immunity Industry EN 50081-2 : 1993 EN 50082-2 : 1995 Installation Guidelines ● The product meets the requirements if you adhere to the installation and safety instructions contained in this descrip tion and in the "SIMATIC NET In ...

  • Siemens Electrical Lean Switch - page 95

    Industrial Ethernet 95 A5E00152007-03 10 Glossary 10 Autonegotiation Procedure standardized by IEEE 802.3 in which the transmission parameters (for example 10/100 M bps, full/half duplex) are negotiated automatically between the devices. Autosensing See Autonegotiation ELS Electrical Lean Switch ESM Electrical Switch Module EMC Electromagnetic comp ...

  • Siemens Electrical Lean Switch - page 96

    Industrial Ethernet 96 A5E00152007-03 A Ambient conditions, permitted ..... 81, 84, 86 Authorizati on hotlin e ................................ 89 C Cable lengths, permi tted ............. 81, 84, 86 Consignment ..................... 4, 36, 82, 85, 87 Customer Support ................................... 89 D Displays ............................... ...

  • Siemens Electrical Lean Switch - page 97

    Industrial Ethernet 97 A5E00152007-03 12 References 12 /1/ SIMATIC NET Industrial Ethernet OSM/ESM Network Management, Release 08/2001 supplied with every device on CD and available at http://www4.ad.siemens .de/view/cs/de/8677203 on the Web. /2/ SIMATIC NET Industrial Twisted Pair and Fiber-Optic Networks, Release 05/2001 Order numbers: 6GK1970-1B ...

Manufacturer Siemens Category Switch

Documents that we receive from a manufacturer of a Siemens Electrical Lean Switch can be divided into several groups. They are, among others:
- Siemens technical drawings
- Electrical Lean Switch manuals
- Siemens product data sheets
- information booklets
- or energy labels Siemens Electrical Lean Switch
All of them are important, but the most important information from the point of view of use of the device are in the user manual Siemens Electrical Lean Switch.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals Siemens Electrical Lean Switch, service manual, brief instructions and user manuals Siemens Electrical Lean Switch. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product Siemens Electrical Lean Switch.

Similar manuals

A complete manual for the device Siemens Electrical Lean Switch, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use Siemens Electrical Lean Switch by users. Manuals are usually written by a technical writer, but in a language understandable to all users of Siemens Electrical Lean Switch.

A complete Siemens manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual Siemens Electrical Lean Switch - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the Siemens Electrical Lean Switch, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the Siemens Electrical Lean Switch, that we can find in the current document
3. Tips how to use the basic functions of the device Siemens Electrical Lean Switch - which should help us in our first steps of using Siemens Electrical Lean Switch
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with Siemens Electrical Lean Switch
5. FAQ - Frequently Asked Questions
6. Contact detailsInformation about where to look for contact to the manufacturer/service of Siemens Electrical Lean Switch in a specific country, if it was not possible to solve the problem on our own.

Do you have a question concerning Siemens Electrical Lean Switch?

Use the form below

If you did not solve your problem by using a manual Siemens Electrical Lean Switch, ask a question using the form below. If a user had a similar problem with Siemens Electrical Lean Switch it is likely that he will want to share the way to solve it.

Copy the text from the picture

Comments (0)