    TECHNICAL GUIDE SPLIT -SYSTEM A IR CONDITIONERS 13 SEER – R-22 MODELS: H*RD018 THRU 060 (1.5 THRU 5 NOMINAL TONS, 1 PHASE) H*RD036 THRU 060 (2.5 THRU 5 NOMINAL TONS, 3 PHASE) Due to continuous produc t impr ovement, specifications are subject to change without notice. V isit us on th e web at www .york.com A dditional rating informa tion can be f ...

  • York H*RD036 THRU 060 - page 2

    254892-YTG-C-0606 2 Unitary Products Group All dimensions are in inches. They a re subject to change without notice. Ce rtif ied dimensio ns will be provide d upon request. PHYSICAL AND ELECTRICAL DA T A - 1 PHASE MODEL H2RD018S06 H2RD024S06 H2RD030S06 H 2RD036S06 H2RD042S06 H2RD048S06 H 2RD060S06 Unit Supply V olt age 208-230V , 1 φ, 60Hz Normal ...

  • York H*RD036 THRU 060 - page 3

    254892-YTG-C-0606 Unitary Products Group 3 Additional R-22 Charge / Orifice Size for V arious Ma tched Systems - 1 Phase Outdoor Unit H2RD018S06 H2RD024S06 H2RD030S06 H2RD036S06 H2RD042S06 H2RD048S06 H2RD060S06 Required TXV 1 TVM2A1 1 TVM2(A,B)1 1 TVM2A1 1 TVM2A1 1 TVM2C1 1 TVM2C1 1 TVM2C1 Factory R-22 Charge, lbs-oz 4 - 9 6 - 3 5 - 13 6 - 0 8 - 13 ...

  • York H*RD036 THRU 060 - page 4

    254892-YTG-C-0606 4 Unitary Products Group H C 1 8 A 3 X 0 2 B + 1 ––––– H C 3 0 A 3 X – 2 A + 0 0 –––– HC36B3X – – 0 0 – – – H C 4 2 C 3 X ––––0 0 – H C 6 0 C 3 X –––––0 0 H D 2 4 A 3 X 0 2 A + 0 ––––– HD36B3X – – 0 0 – – – H D 4 8 C 3 X ––––0 0 – H D 6 0 D 3 X ––? ...

  • York H*RD036 THRU 060 - page 5

    254892-YTG-C-0606 Unitary Products Group 5 PROCEDURES: 1. U nit factory charge listed on the unit nameplate includes refr igerant for the condenser , the smallest evaporator and for 15 feet of inter- connecting line tubing. 2. Verify the TXV and additional charge required for specific evaporator coil in the system using the above table. 3. Addition ...

  • York H*RD036 THRU 060 - page 6

    254892-YTG-C-0606 6 Unitary Products Group All dimensions are in inches. They a re subject to change without notice. Ce rtif ied dimensio ns will be provide d upon request. PHYSICAL AND ELECTRICAL DA T A - 3 PHASE MODEL H1RD 030S25 H1RD 036S25 H1RD 042S25 H1RD 048S25 H1RD 060S25 H1RD 030S46 H1RD 036S46 H1RD 042S46 H1RD 048S46 H1RD 060S46 Unit Suppl ...

  • York H*RD036 THRU 060 - page 7

    254892-YTG-C-0606 Unitary Products Group 7 Additional R-22 Charge / Orifice Size for V arious Ma tched Systems - 3 Phase Outdoor Unit H1RD030S(25,46) H1RD036S(25,46) H1RD042S(25,46) H1RD048S(25, 46) H1RD060S(25,46) Required TXV 1 TVM2A1 1 TVM2A1 1 TVM2C1 1 TVM2C1 1 TVM2C1 Factory R-22 Charge, lbs-oz 5 - 13 6 - 0 8 - 13 8 - 6 10 - 2 Indoor Coil 1 Ad ...

  • York H*RD036 THRU 060 - page 8

    254892-YTG-C-0606 8 Unitary Products Group PROCEDURES: 1. U nit factory charge listed on the unit nameplate include s refr iger ant for the condenser , the smallest evaporator and for 15 feet of inter- connecting line tubing. 2. Verify the TXV and additional charge required for specific evaporator coil in the system using the above table. 3. Additi ...

  • York H*RD036 THRU 060 - page 9

    254892-YTG-C-0606 Unitary Products Group 9 COOLING CAP ACITY - With Air Handler Coils UNIT MODEL AIR HANDLER COIL MODEL 1 COOLING MODEL ELECTRIC HEA T KW 2 W RA TED CFM NET MBH SEER EER TOT AL SENS. 1 & 3 PH 13 SEER AC WITH MA H2RD018S06 MA08B 2,5,8 17 FC/MC18B 600 17.5 1 1.7 13.00 1 1.00 MA08B 2,5,8 17 G*FD024H17 600 17.5 1 1.7 13.00 1 1.00 H2 ...

  • York H*RD036 THRU 060 - page 10

    254892-YTG-C-0606 10 Unitary Products Group — = Not applicable. 1 PH 13 SEER AC WITH A V / SV - V ARIABLE SPEED H2RD018S06 A V24 2,5,8,10,15 17 – 600 18.0 1 1.7 14.00 1 1.50 H2RD024S06 A V24 2,5,8,10,15 17 – 800 23.2 16.5 14.00 1 1.50 H2RD030S06 A V36 5,8,10,15,18 21 – 1000 30.0 21.2 14.00 1 1.50 H2RD036S06 A V36 5,8,10,15,18 21 – 1200 35 ...

  • York H*RD036 THRU 060 - page 11

    254892-YTG-C-0606 Unitary Products Group 11 COOLING CAP ACITY - Up flow , Downflow & Horizont al Furnaces and Coils UNIT MODEL F URNACE** COIL MODEL COOLING CFM RANGE (MIN.-MAX.) W RA TED CFM NET MBH SEER 1 EER TOT AL SENS. H2RD018S06 450 750 14,17 FC/MC/PC/UC18 600 17.5 1 1.7 13.00 1 1.00 14,17 FC/MC/PC/UC24 600 17.7 1 1.9 13.00 1 1.00 14 G*F ...

  • York H*RD036 THRU 060 - page 12

    254892-YTG-C-0606 12 Unitary Products Group H2RD042S06 1200 1600 17,21 FC/MC/PC/UC42 1400 40.5 29.6 13.00 1 1.00 21,24 FC/MC/PC/UC48 1400 41.0 30.2 13.00 1 1.00 17 G*F A042S17 1400 40.5 29.6 13.00 1 1.00 21 G*F A048S21 1400 41.0 29.6 13.00 1 1.00 21 G*FD042H21 1400 40.5 29.6 13.00 1 1.00 17 G*FD046H17 1400 40.5 29.6 13.00 1 1.00 21,24 G*FD048H21,24 ...

  • York H*RD036 THRU 060 - page 13

    254892-YTG-C-0606 Unitary Products Group 13 COOLING CAP ACITY - With V ariable Speed Furnaces UNIT MODEL V ARIABLE SPEED FURNACE MODEL COIL MODEL 1 W COOLING RA TED CFM NET MBH SEER EER T OTAL SENS. 1 PH 13 SEER AC WITH V ARIABLE SPEED FURNACES 2 H2RD018S06 PV8*A12 FC/MC/PC18A 14 600 17.8 1 1.9 14 .00 1 1.50 PV9*A12 FC/MC/PC18A 14 600 17.8 1 1.8 14 ...

  • York H*RD036 THRU 060 - page 14

    254892-YTG-C-0606 14 Unitary Products Group H2RD036S06 PV8*A12 FC/MC/PC36A 14 1200 35.0 25.4 13.00 1 1.00 PV8*B16 FC/MC/PC36B 17 1200 35.2 25.6 13.75 1 1.00 PV8*C16 FC/MC/PC36C 21 1200 35.2 25.6 14.00 1 1.50 PV8*C20 FC/MC/PC36C 21 1200 35.2 25.6 14.00 1 1.50 PV9*A12 FC/MC/PC36A 14 1200 34.8 25.4 13.00 1 1.00 P(C,V)9*B12 FC/MC/PC36B 17 1200 35.0 25. ...

  • York H*RD036 THRU 060 - page 15

    254892-YTG-C-0606 Unitary Products Group 15 H2RD048S06 PV8*C16 FC/MC/PC48C 21 1500 46.5 34.2 13.00 1 1.00 PV8*C20 FC/MC/PC48C 21 1600 47.0 35.2 13.00 1 1.00 P(C,V)9*C16 FC/MC/PC48C 21 1600 47.0 35.2 13.00 1 1.00 P(C,V)9*C20 FC/MC/PC48C 21 1600 47.0 35.2 13.00 1 1.00 P(C,V)9*D20 FC/MC/PC48D 24 1600 47.0 35.2 13.25 1 1.00 PV8*C16 HC48 21 1500 46.5 33 ...

  • York H*RD036 THRU 060 - page 16

    254892-YTG-C-0606 16 Unitary Products Group ACCESSORIES Refer to Price Manual for specific model numbers. HARD ST ART KIT - Provides increased starting torque for areas with low voltage. COMPRESSOR BLANKET - Designed to furth er reduce the normal compressor operating sound. Refer to price pages for specific match-ups. OFF CYCLE TIMER DELA Y - Provi ...

  • York H*RD036 THRU 060 - page 17

    254892-YTG-C-0606 Unitary Products Group 17 Multipliers for determining the performance with other indoor sections . NOTE: For dry bulb temperatures dif ferent than t hose liste d (between 73-87 F), sensible cap acity incr eases by 1060 BTUH per 1000 CFM per degree above the listed temperature and decreases by 1060 BTUH per 1 000 CFM per degree bel ...

  • York H*RD036 THRU 060 - page 18

    254892-YTG-C-0606 18 Unitary Products Group Multipliers for determining the p erfo rman ce with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those liste d (bet ween 73-87 F), sensible capacit y incr eases by 1060 BTUH per 1000 CFM per deg ree above the listed temperatur e and decre ases by 1060 BTUH per 1000 CFM per degree ...

  • York H*RD036 THRU 060 - page 19

    254892-YTG-C-0606 Unitary Products Group 19 Multipliers for determining the performance with other indoor sections . NOTE: For dry bulb temperatures dif ferent than t hose liste d (between 73-87 F), sensible cap acity incr eases by 1060 BTUH per 1000 CFM per degree above the listed temperature and decreases by 1060 BTUH per 1 000 CFM per degree bel ...

  • York H*RD036 THRU 060 - page 20

    254892-YTG-C-0606 20 Unitary Products Group Multipliers for determining the p erfo rman ce with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those liste d (bet ween 73-87 F), sensible capacit y incr eases by 1060 BTUH per 1000 CFM per deg ree above the listed temperatur e and decre ases by 1060 BTUH per 1000 CFM per degree ...

  • York H*RD036 THRU 060 - page 21

    254892-YTG-C-0606 Unitary Products Group 21 Multipliers for determining the performance with other indoor sections . NOTE: For dry bulb temperatures dif ferent than t hose liste d (between 73-87 F), sensible cap acity incr eases by 1060 BTUH per 1000 CFM per degree above the listed temperature and decreases by 1060 BTUH per 1 000 CFM per degree bel ...

  • York H*RD036 THRU 060 - page 22

    254892-YTG-C-0606 22 Unitary Products Group Multipliers for determining the p erfo rman ce with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those liste d (bet ween 73-87 F), sensible capacit y incr eases by 1060 BTUH per 1000 CFM per deg ree above the listed temperatur e and decre ases by 1060 BTUH per 1000 CFM per degree ...

  • York H*RD036 THRU 060 - page 23

    254892-YTG-C-0606 Unitary Products Group 23 Multipliers for determining the performance with other indoor sections . NOTE: For dry bulb temperatures dif ferent than t hose liste d (between 73-87 F), sensible cap acity incr eases by 1060 BTUH per 1000 CFM per degree above the listed temperature and decreases by 1060 BTUH per 1 000 CFM per degree bel ...

  • York H*RD036 THRU 060 - page 24

    Subject to change without notice. Printe d in U .S.A. 254892-YTG-C-0606 Copyright © by York International Corp. 2006. All right s reserved. Supersedes: 254892 / 036-21339-002 Rev. B (020 6) Unitary 5005 Norman Product s Y ork O K Group Drive 73069 NOTES ...

Manufacturer York Category Air Conditioner

Documents that we receive from a manufacturer of a York H*RD036 THRU 060 can be divided into several groups. They are, among others:
- York technical drawings
- H*RD036 THRU 060 manuals
- York product data sheets
- information booklets
- or energy labels York H*RD036 THRU 060
All of them are important, but the most important information from the point of view of use of the device are in the user manual York H*RD036 THRU 060.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals York H*RD036 THRU 060, service manual, brief instructions and user manuals York H*RD036 THRU 060. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product York H*RD036 THRU 060.

Similar manuals

A complete manual for the device York H*RD036 THRU 060, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use York H*RD036 THRU 060 by users. Manuals are usually written by a technical writer, but in a language understandable to all users of York H*RD036 THRU 060.

A complete York manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual York H*RD036 THRU 060 - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the York H*RD036 THRU 060, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the York H*RD036 THRU 060, that we can find in the current document
3. Tips how to use the basic functions of the device York H*RD036 THRU 060 - which should help us in our first steps of using York H*RD036 THRU 060
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with York H*RD036 THRU 060
5. FAQ - Frequently Asked Questions
6. Contact detailsInformation about where to look for contact to the manufacturer/service of York H*RD036 THRU 060 in a specific country, if it was not possible to solve the problem on our own.

Do you have a question concerning York H*RD036 THRU 060?

Use the form below

If you did not solve your problem by using a manual York H*RD036 THRU 060, ask a question using the form below. If a user had a similar problem with York H*RD036 THRU 060 it is likely that he will want to share the way to solve it.

Copy the text from the picture

Comments (0)