    V F C R a d i a n t & C o n v e c t o r F i r e R a n g e With upgradeable control valve I ns t r uc t io n s f or U se , I ns t a ll a ti o n a nd S er v i ci n g Fo r use i n G B, IE (G re at Br it ain a nd Ei re ) PR0641 Issue 7 (December 2006 ) IMPORTANT The chimney must be swept before installation. Do not attempt to burn rubbish on this f ...

  • Stovax VFC Radiant & Convector Fire Range - page 2

    2 CONTENTS PAGE Commissioning Check List 3 USER INSTRUCTIONS 4 INSTALLATION INSTRUCTIONS Technical Specifications 8 Site Requirements 9 Installation 11 Commissioning 16 SERVICING INSTRUCTIONS Servicing Requirements 17 Fault Finding 18 How to replace parts 19 Basic spare parts list 22 ...

  • Stovax VFC Radiant & Convector Fire Range - page 3

    3 FLUE CHECK PASS FAIL 1. Flue is correct for appliance 2. Flue flow test 3. Spillage test GAS CHECK 1. Gas soundness & let by test 2. Standing pressure test mb 3. Appliance working pressure (on High Setting) mb NB All other gas appliances must be operating on full 4. Gas rate m 3 /h 5. Does ventilation meet appliance requirements 6. Have contr ...

  • Stovax VFC Radiant & Convector Fire Range - page 4

    4 USER INSTRUCTIONS 1.1 Installation and servicing must only be carried out by a competent person. 1.2 In your own interest, and those of safety, this appliance must be installed by a competent person in accordance with local and national codes of practice. Failure to install the appliance correctly could lead to prosecution. 1.3 In all corresponde ...

  • Stovax VFC Radiant & Convector Fire Range - page 5

    7.2 Position the front coal, make sure it sits flat onto the burner skin. See diagram 3 arrow C. 7.3 Place the coals following the appropriate diagrams and instructions 16” AND REDUCED DRAUGHT COAL LAYOUT 7.4 Curved fronts (Holyrood and Richmond) -place 5 large coals onto the front coal moulding ensuing that they rest against the front, place 2 s ...

  • Stovax VFC Radiant & Convector Fire Range - page 6

    7. 11 Pla ce 6 la rg e co al s on to the fl ame ba ffl e f in ger s. See di agr am 11. 7.12 Place 5 large coals so that they form a bridge between the other 2 rows, and 2 small coals, 1 at each end. Place 5 large coals at the back of the fire. See diagram 12. 7.13 Place the remaining 5 small coals on top of the others so that they form a bridge bet ...

  • Stovax VFC Radiant & Convector Fire Range - page 7

    7 USER INSTRUCTIONS 22” COAL LAYOUT 7.14 All fronts - place 8 large coals onto the front coal moulding ensuring that they rest against the front, place 2 small coals on to the front coal, 1 at each end. See diagram 14. 7.15 Place 8 large coals onto the flame baffle fingers. See diagram 15. 7.16 Place 7 large coals so that they form a bridge betwe ...

  • Stovax VFC Radiant & Convector Fire Range - page 8

    8 TECHNICAL SPECIFICATION THESE INSTRUCTIONS COVER THE FOLLOWING MODELS: VFC RADIANT VFC COVECTOR VFC LOW CONVECTOR 8300UC 16” 8420UC 16” 8461UC 16”LL P8300UC 16” P8420UC 16” P8461UC 16”LL 8301UC 16”RD 8421UC 16”RD 8463UC 16”RD LL P8301UC 16”RD P8421UC 16”RD P8463UC 16”RD LL 8305UC 18” 8425UC 18” 8466UC 18”LL P8305UC 1 ...

  • Stovax VFC Radiant & Convector Fire Range - page 9

    9 The flue must be installed in accordance with all local and national regulation and the current rules in force. 1.FLUE AND CHIMNEY REQUIREMENTS 1.1 The chimney or flue system must comply with the rules in force, and must be a minimum of 178mm (7î) in diameter. 1.2 The minimum effective height of the flue or chimney must be 3 m (10ft). 1.3 The ch ...

  • Stovax VFC Radiant & Convector Fire Range - page 10

    10 4.4 The appliance must be firmly fixed to the hearth. Fasteners are provided for this purpose. 4.5 Ensure that no naked flame or incandescent part of the fire bed projects beyond the vertical plane of the fireplace opening. 4.6 The appliance must not be installed in any room that contains a bath or shower. 4.7 Ensure clearances to combustible ma ...

  • Stovax VFC Radiant & Convector Fire Range - page 11

    4. INSTALLATION - RADIANT FIRES 4.1 Fix the rear leg strap. See diagram 1. 4.2 Position the fire with the rear leg fully engaged under the rear leg strap. Fasten the front legs using the fixings supplied. 4.3 “HAVE YOU PURGED THE GAS SUPPLY PIPES”. This is essential to expel any foreign matter that might get blown into the valve assembly causin ...

  • Stovax VFC Radiant & Convector Fire Range - page 12

    12 4.8 Fit the fret to the fire front using two screws. See diagram 4. 5. INSTALLATION - CONVECTOR FIRES 5.1 Make any necessary alterations to fireplace opening. Ensure that the lintel does not obstruct the flue outlet into the flue, and that there is a clear space for debris of at least 90mm. See diagram 5. 5.2 Gas pipe entry must be through one o ...

  • Stovax VFC Radiant & Convector Fire Range - page 13

    Protective clothing is not required when handling these articles, but we recommend you follow normal hygiene rules of not smoking, eating or drinking in the work area and always wash your hands before eating or drinking. To ensure that the release of RCF fibres are kept to a minimum, during installation and servicing a HEPA filtered vacuum is recom ...

  • Stovax VFC Radiant & Convector Fire Range - page 14

    14 6.5 Flat fronts (All others) - Place 3 large coals and 4 small coals onto the front coal moulding ensuring that they rest against the decorative front, these should run intermittently small, large, small etc. See diagram 15. 6.6 Place 5 large coals onto the flame baffle fingers. See diagram 16. 6.7 Place 4 large coals so that they form a bridge ...

  • Stovax VFC Radiant & Convector Fire Range - page 15

    15 5.13 Place the remaining 5 small coals on top of the others so that they form a bridge between the second and third rows. See diagram 23. 22” COAL LAYOUT 5.14 All fronts - place 8 large coals onto the front coal moulding ensuring that they rest against the front, place 2 small coals on to the front coal, 1 at each end. See diagram 24. 5.16 Pla ...

  • Stovax VFC Radiant & Convector Fire Range - page 16

    16 1. COMMISSIONING 1.1 Close all windows and doors to the room, check all controls, and allow fire to burn on maximum for 5 minutes. Test for spillage of flue products using a smoke match. For standard VFC fires, pass the lighted smoke match along the top front edge just inside the opening or canopy. For the RD VFC only, hold the lighted smoke mat ...

  • Stovax VFC Radiant & Convector Fire Range - page 17

    17 This appliance must be serviced at least one a year by a competent person. 1. SERVICING REQUIREMENTS 1.1 As part of the annual service, the space behind the convector must be inspected for any debris, which may have fallen down the chimney. 1.2 Remove the gas fire from the convect or as detai led in sect ion 4 1.3 Remove the convector box from t ...

  • Stovax VFC Radiant & Convector Fire Range - page 18

    18 FAULT FINDING IGNITION FUNCTIONAL CHECK 1 PILOT WILL NOT LIGHT Ensure there is no debris around the pilot assembly, e.g coal, soot, etc which could short the spark, clean the area. Check for fluff in the pilot aeration hole. See diagram 7, arrow A. There is a blockage in the system, check the inlet test point, the mag seating, valve and pilot fi ...

  • Stovax VFC Radiant & Convector Fire Range - page 19

    19 INSTALLATION INSTRUCTIONS REPLACING PARTS 2. IGNITION LEAD The following part can be serviced without removing the fire. 2.1 Turn off the gas supply at the isolation device. 2.2 Remove the fret. See diagram 1. 2.3 Undo the single screw that secures the left hand side of the control cover. See diagram 2. 2.4 To release the right hand side of the ...

  • Stovax VFC Radiant & Convector Fire Range - page 20

    20 5. ODS PILOT UNIT Note: The pilot unit on the appliance is a non serviceable unit due to the complex nature of its manufacture. Replacement of the complete unit must be carried out when one of the following items becomes faulty: Pilot injector Ignition electrode Thermocouple 5.1 Carry out operations (a) to (d), section 4. 5.2 Gently pull the ign ...

  • Stovax VFC Radiant & Convector Fire Range - page 21

    21 6.5 Disconnect the ignition lead from the gas valve, refer to section 27. 6.6 Undo the two bolts securing the gas valve to the appliance and remove the valve. 6.7 Replace in reverse order. 6.8 Check all joints for gas leaks, check operation of the thermocouple and ignition lead. 8. MAG UNIT 7.1 Carry out operations (a) to (d), section 4. 7.2 Und ...

  • Stovax VFC Radiant & Convector Fire Range - page 22

    MANUAL FIRES RD 16 18 22 CERAMIC PARTS Front Coal LH CE0151 CE0152 CEO153/54 Flame Baffle CE0119 CE0120 CEO121 Burner Skin CE0155 CE0156 CEO157 Coal Set CE0394 CE0395 CEO396 Convector Side Cheek LH CEO158 Low Convector Side Cheek LH CEO160 Convector Side Cheek RH CEO159 Low Convector Side Cheek RH CEO161 NATURAL GAS PARTS Main Injector IN0007 IN000 ...

  • Stovax VFC Radiant & Convector Fire Range - page 23

    23 SERVICE RECORDS 1ST SERVICE Date of Service:........................................................................... Next Service Due:....................................................................... Signed:........................................................................................ 3RD SERVICE Date of Service:.............. ...

  • Stovax VFC Radiant & Convector Fire Range - page 24

    Gazco Limited, Osprey Road, Sowton Industrial Estate, Exeter, Devon, England EX2 7JG Tel: (01392) 261999 Fax: (01392) 444148 E-mail: info@gazco.com A member of the Stovax Group ...

Производитель Stovax Категория Indoor Fireplace

Документы, которые мы получаем от производителя устройства Stovax VFC Radiant & Convector Fire Range мы можем разделить на несколько групп. Это в частности:
- технические чертежи Stovax
- инструкции обслуживания VFC Radiant & Convector Fire Range
- паспорта изделия Stovax
- информационные брошюры
- энергетические этикетки Stovax VFC Radiant & Convector Fire Range
Все из них важны, однако самую важную информацию с точки зрения пользователя мы найдем в инструкции обслуживания Stovax VFC Radiant & Convector Fire Range.

Группа документов, определяемая как инструкции обслуживания, делится также на более подробные типы, такие как: Инструкции монтажа Stovax VFC Radiant & Convector Fire Range, инструкции обслуживания, короткие инструкции или инструкции пользователя Stovax VFC Radiant & Convector Fire Range. В зависимости от потребностей, Вам необходимо поискать требуемый документ. На нашем сайте Вы можете просмотреть самую популярную инструкцию использования изделия Stovax VFC Radiant & Convector Fire Range.

Похожие инструкции обслуживания

Полная инструкция обслуживания устройства Stovax VFC Radiant & Convector Fire Range, как должна выглядеть?
Инструкция обслуживания, определяемая также как пособие пользователя, или просто "руководство" - это технический документ, цель которого заключается в использовании Stovax VFC Radiant & Convector Fire Range пользователями. Инструкции пишет, как правило технический писатель, языком, доступным для всех пользователей Stovax VFC Radiant & Convector Fire Range.

Полная инструкция обслуживания Stovax, должна заключать несколько основных элементов. Часть из них менее важная, как например: обложка / титульный лист или авторские страницы. Однако остальная часть, должна дать нам важную с точки зрения пользователя информацию.

1. Вступление и рекомендации, как пользоваться инструкцией Stovax VFC Radiant & Convector Fire Range - В начале каждой инструкции, необходимо найти указания, как пользоваться данным пособием. Здесь должна находится информация, касающаяся местонахождения содержания Stovax VFC Radiant & Convector Fire Range, FAQ и самых распространенных проблем - то есть мест, которые чаще всего ищут пользователи в каждой инструкции обслуживания
2. Содержание - индекс всех советов, касающихся Stovax VFC Radiant & Convector Fire Range, которое найдем в данном документе
3. Советы по использованию основных функций устройства Stovax VFC Radiant & Convector Fire Range - которые должны облегчить нам первые шаги во время использования Stovax VFC Radiant & Convector Fire Range
4. Troubleshooting - систематизированный ряд действия, который поможет нам диагностировать а в дальнейшем очередность решения важнейших проблем Stovax VFC Radiant & Convector Fire Range
5. FAQ - чаще всего задаваемые вопросы
6. Контактные данные Информация о том, где искать контактные данные производителя / сервисного центра Stovax VFC Radiant & Convector Fire Range в данной стране, если самостоятельно не получится решить проблему.

У вас вопрос, касающийся Stovax VFC Radiant & Convector Fire Range?

Воспользуйтесь формуляром, находящимся ниже

Если с помощью найденной инструкции Вы не решили свою проблему с Stovax VFC Radiant & Convector Fire Range, задайте вопрос, заполнив следующий формуляр. Если у какого то из пользователей была похожая проблема с Stovax VFC Radiant & Convector Fire Range со всей вероятностью он захочет поделиться методом ее решения.