    EP A Wood-Burning Fireplace P/ N 85 0,0 38 M RE V . E 01 /20 08 MONTEST MODEL MONTECITO EST A TE™ This installation manual will enable you to obtain a safe, efficient and dependable installation of your fireplace system. Please read and understand these instructions before beginning your installation. Do not alter or modify the fireplace or it ...

  • Lexmark MONTEST - page 2

    W ARNING T o avoid the risk of damaging fireplace materials and increas- ing the risk of fire, do not use the fireplace to cook or warm food. W ARNING NEVER use gasoline, gasoline- type lantern fuel, kerosene, charcoal lighter fluid, naphtha, engine oil or similar liquids to start or “freshen up” a fire in this fireplace. Keep any flamma ...

  • Lexmark MONTEST - page 3

    T ABLE OF CONTENTS Safety Rules ...................................... Page 2 Introduction ...................................... Page 3 Parts Required ................................. Page 3 Optional Equipment ........................... Page 3 Operating The Mo nt ec it o Es ta te ......... Page 3 Fuel ............................................ ...

  • Lexmark MONTEST - page 4

    The combustion air control should be opened before opening the doors to minimize the possi- bility of back draft coming into the room ( Figure 1-A ) More details are available in Refueling For Best Performance on Page 5 . Time Delayed Air Boost System The time delayed air-boost system register is located underneath the door handles. Placed in the f ...

  • Lexmark MONTEST - page 5

    The unit will burn best with 2-3 pieces of cord wood spaced 1 to 2 inches apart and allowing air to get under the fuel. Criss-crossing or ar - ranging the fuel so that air can get underneath will help the fire to get started easily . The unit should be operated with the air control fully open long enough to get the cord wood well ignited. REFUELIN ...

  • Lexmark MONTEST - page 6

    Figure 5 IMPORT ANT CAUTIONS A. Do not block the hot air vents to the fire- place as this will cause the fireplace to overheat. B. Never use gasoline, kerosene, charcoal lighter fluid or similar liquids to start or rekindle a fire in this fireplace. Keep all such liquids well away from the fireplace at all times. C. Do not burn coal. The sulp ...

  • Lexmark MONTEST - page 7

    DOOR INST ALLA TION The doors must be put in place only when the installation of the Montecito Estate™ is completed. All you have to do is fit the male part of the hinge, already on the door , to the female part, which is on the fireplace. T o remove the doors, simply pull them up from the hinges. The door adjustment has been set at the factory ...

  • Lexmark MONTEST - page 8

    FIREPLACE INST ALLA TION Locating The Montecito Estate™ The best location to install your fireplace is determined by considering the location of windows, doors, and the traffic flow in the room where the fireplace is located, allowing space in front of the unit for the hearth extension and the mantel, and taking into consideration the locatio ...

  • Lexmark MONTEST - page 9

    Figure 11 Insulated Chase Construction 7 Ft. Min. Attic Radiation Shield Ro of Sup po rt Storm Collar Flashing Dr yw al l or An y Ri gi d Ma te ri al 2” x 4” 1/2” Plywood 6’ 8” Min. Firestop * Floor Ceiling Wall * Floor Ceiling Wall Fireplace Insulate Joists Same As Ceiling Draft Stops Firestop CTDT T ermination Note: Non- Combustible Cha ...

  • Lexmark MONTEST - page 10

    1. Combustible materia l must be installe d flush with the fireplace. It may not project in front of and on the fireplace (i.e. the steel facade of the fireplace) ( Figure 14 ) . 2. Non-combustible materials such as brick, stone or ceramic tile may project in front of and onto the fireplace facing ( Figure 13 ) . MANTEL & F ACING The mante ...

  • Lexmark MONTEST - page 11

    Figure 17 13” x 13” 10’ Max. 10’ Max. Rain Cap Flashing Collar Flashing Roof Support Attic Radiation Shield No n- Com bust ibl e Fl am epr oof Fa ci ng 56” Min. 68” Min. Figure 18 The duct system must be installed respecting the following: 1. Remove the plates closing up the 8” diameter holes on top of the fireplace. Then, cut the in ...

  • Lexmark MONTEST - page 12

    OUTSIDE AIR KIT It is mandatory to install an outside air connection to the Montecito Estate™. The following components are required and are included with the fireplace: - Outside air kit (includes 40 inch flex that goes up to ten (10) feet long) - 4” Adaptor for fireplace connection Outside Air Installation The outside air assembly may be i ...

  • Lexmark MONTEST - page 13

    8. A rain cap must be installed on top of the chimney . Failure to install a rain cap may cause corrosion problems. 9. Cut and frame square holes in all floors, ceilings, and roof that the chimney will go through to provide a 2” (50 mm) clearance between the chimney and any combustible materials. Do not fill this 2” space with insulation or a ...

  • Lexmark MONTEST - page 14

    CHIMNEY INST ALLA TION INSTRUC- TIONS 1. Cut and frame the holes in the ceiling, floor and roof where the chimney will pass (see Figure 22 ). Use a plumb-bob to line up the center of the holes. The sizes are indicated in T able 2 for the floor and ceiling holes and T able 3 ( Page 15 ) for the roof holes. Fro m belo w , inst all a firest op in e ...

  • Lexmark MONTEST - page 15

    Roof Down Slope Hole Size D EG R E E O F S L O P E S ec u r e T e m p ™ S 21 0 0 + N ov a T e m p ™ HT 6 0 00 + S ec u r e T e m p GX A CB I R oo f Pi t c h 7 ” 7 ” 0 * 1 5” ( 38 0 mm ) 1 5” ( 38 0 mm ) 2 /1 2 1 5- 3 / 8” ( 39 0 m m) 1 5- 3 / 8” ( 39 0 m m) 4 /1 2 1 6- 1 / 8” ( 41 0 m m) 1 6- 1 / 8” ( 41 0 m m) 6 /1 2 1 6- 7 / 8 ...

  • Lexmark MONTEST - page 16

    OFFSET CHIMNEY INST ALLA TION The minimum chimney height when using elbows is: C h i m n ey Elbow Offset & Height T wo Lengths Between Elbows 8” 12” 18” 24” 36” 8” & 36” 1 2” & 36 ” 1 8” & 3 6 ” 2 4” & 3 6 ” 36” & 36” GX S2 10 0+ HT 60 00 + 7” 15º A 3” (7 6 m m) 4- 1/4 ” (1 08 mm) 5- 3/4 ...

  • Lexmark MONTEST - page 17

    Figure 28 OFFSET CHIMNEY INST ALLA TION Rain Cap Collar Roof Flashing Offset Support Insulated Wall Radiation Shield Framing 2” x 3” Figure 29 Roof Support Note: In cold areas it is recommended to protect the chimney in a insulated chase. Straps Chimney ACBI ACBI Starter Section Straps Outside Wall OFFSET CHIMNEY INST ALLA TION WITH WALL PENETR ...

  • Lexmark MONTEST - page 18

    ANGLED WALL RADIA TION SHIELD (XRSMI30 and AC10RSMI30) When traversing a combustible wall with the chimney at a 30º or 45º angle, an angled firestop or wall radiation shield must be installed. Only one is required. Note: 45º angle for Canada only (XRSMI45). In cold climate locations (climates where temperatures will fall below 32º F / 0º C), ...

  • Lexmark MONTEST - page 19

    INST ALLA TION INSTRUCTIONS FOR MASONRY APPLICA TION WARNING: Before starting the installation, the masonry chimney must be inspected by a qualified chimney sweep. The following requirements must be respected: 1. The chimney must be absolutely clear of any soot residue or creosote. Check for cracks, loose or missing bricks that could inhibit corre ...

  • Lexmark MONTEST - page 20

    CHIMNEY - P ARTS AND COMPONENTS LISTS Secure T emp GX - 2” Insulated Galvanized Chimney System (Recommended Insulated System) Galvanized (7” ID & 11” OD) U.S.A. ONL Y Description Cat./Part No. Lengths & Misc. Chimney Components Length 8”, 7GXL8 7GXL8 Length 12”, 7GXL12 7GXL12 Length 18”, 7GXL18 7GXL18 Length 24”, 7GXL24 7GXL24 ...

  • Lexmark MONTEST - page 21

    ACBI Chimney* (7” I.D., 13” O.D. AC - Air Cooled) * AC C h im ne y i s NO T re co m me nd e d at e le va ti o ns a bo ve 4 ,0 0 0 fe e t or i n co ld c li ma te s ( cl im at es w he re t em p er at u re s w il l fa ll b el ow 3 2° F / 0 ° C) . Description Cat./Part No. One of the following adaptors is required if installing an AC chimney syst ...

  • Lexmark MONTEST - page 22

    CLEARANCE TO COMBUSTIBLES The following clearances meet the minimum requirements for a safe installation: • Side wall (fireplace front): 24” (457 mm) measured from the fireplace side. • Ceiling: 6’ 8” (2,032 mm) measured from the base of the fireplace • Fireplace enclosure: Bottom: 0” Side: 0” Back: 0” • T op: Do not fill th ...

  • Lexmark MONTEST - page 23

    NOTES 23 ...

  • Lexmark MONTEST - page 24

    Printed in Canada © 2006 by LENNOX HEARTH PRODUCTS P/N 850,038M REV . E 01/2008 Y our Fireplace's Model Number ________________________________________ Y our Fireplace's Serial Number ________________________________________ The Date On Which Y our Fireplace Was Installed ___________________________ Y our Dealer's Name _____________ ...

Производитель Lexmark Категория Indoor Fireplace

Документы, которые мы получаем от производителя устройства Lexmark MONTEST мы можем разделить на несколько групп. Это в частности:
- технические чертежи Lexmark
- инструкции обслуживания MONTEST
- паспорта изделия Lexmark
- информационные брошюры
- энергетические этикетки Lexmark MONTEST
Все из них важны, однако самую важную информацию с точки зрения пользователя мы найдем в инструкции обслуживания Lexmark MONTEST.

Группа документов, определяемая как инструкции обслуживания, делится также на более подробные типы, такие как: Инструкции монтажа Lexmark MONTEST, инструкции обслуживания, короткие инструкции или инструкции пользователя Lexmark MONTEST. В зависимости от потребностей, Вам необходимо поискать требуемый документ. На нашем сайте Вы можете просмотреть самую популярную инструкцию использования изделия Lexmark MONTEST.

Похожие инструкции обслуживания

Полная инструкция обслуживания устройства Lexmark MONTEST, как должна выглядеть?
Инструкция обслуживания, определяемая также как пособие пользователя, или просто "руководство" - это технический документ, цель которого заключается в использовании Lexmark MONTEST пользователями. Инструкции пишет, как правило технический писатель, языком, доступным для всех пользователей Lexmark MONTEST.

Полная инструкция обслуживания Lexmark, должна заключать несколько основных элементов. Часть из них менее важная, как например: обложка / титульный лист или авторские страницы. Однако остальная часть, должна дать нам важную с точки зрения пользователя информацию.

1. Вступление и рекомендации, как пользоваться инструкцией Lexmark MONTEST - В начале каждой инструкции, необходимо найти указания, как пользоваться данным пособием. Здесь должна находится информация, касающаяся местонахождения содержания Lexmark MONTEST, FAQ и самых распространенных проблем - то есть мест, которые чаще всего ищут пользователи в каждой инструкции обслуживания
2. Содержание - индекс всех советов, касающихся Lexmark MONTEST, которое найдем в данном документе
3. Советы по использованию основных функций устройства Lexmark MONTEST - которые должны облегчить нам первые шаги во время использования Lexmark MONTEST
4. Troubleshooting - систематизированный ряд действия, который поможет нам диагностировать а в дальнейшем очередность решения важнейших проблем Lexmark MONTEST
5. FAQ - чаще всего задаваемые вопросы
6. Контактные данные Информация о том, где искать контактные данные производителя / сервисного центра Lexmark MONTEST в данной стране, если самостоятельно не получится решить проблему.

У вас вопрос, касающийся Lexmark MONTEST?

Воспользуйтесь формуляром, находящимся ниже

Если с помощью найденной инструкции Вы не решили свою проблему с Lexmark MONTEST, задайте вопрос, заполнив следующий формуляр. Если у какого то из пользователей была похожая проблема с Lexmark MONTEST со всей вероятностью он захочет поделиться методом ее решения.

Перепишите текст с картинки

Комментарии (0)