    Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A Electronic T rip Unit s Unidades de disp aro electrónico Micrologic™ 2.0A, 3.0A, 5.0A y 6.0A Déclencheurs électroniques Micrologic MC 2.0A, 3.0A, 5.0A et 6.0A Instruction Bulletin Boletín de instrucciones Directives d'utilisation 48049-136-05  Rev . 01, 04/2012 Retain for Future Use. /  Cons ...

  • Schneider Electric 5.0A - page 2

    ...

  • Schneider Electric 5.0A - page 3

    Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0A Electronic T rip Unit s Instruction Bulletin 48049-136-05  Rev . 01, 07/2012 Retain for future use. ENGLISH ...

  • Schneider Electric 5.0A - page 4

    Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0 A Electronic Trip Units 48049-136-05 Rev. 01, 07/2012 © 1999–2012 Schneider Electric All Rights Reserved 2-EN ENGLISH Hazard Categories and Special Symbols Read these instructions carefully and look at the equipment to become familiar with the device before trying to install, operate, service or maintain i ...

  • Schneider Electric 5.0A - page 5

    © 1999–2012 Schneider Electric All Rights Reserved 3-EN 48049-136-05 Micrologic ® 2.0A , 3.0A, 5.0A and 6.0A Electronic Trip Units Rev. 01, 07/2012 Table of C ontents ENGLISH Table of Contents SECTION 1: GENERAL INFORMATION .............. .............. ........... .............. .............. .............. .............. .............. ..... ...

  • Schneider Electric 5.0A - page 6

    Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0 A Electronic Trip Units 48049-136-05 Table of Contents Rev. 01, 07/2012 © 1999–2012 Schneider Electric All Rights Reserved 4-EN ENGLISH Trip Unit Replacement ......... .............. ................. .............. ................. ....... 29 Battery Installation ....... ................. .............. ...

  • Schneider Electric 5.0A - page 7

    48049-136-05 Mic rologic™ 2.0A, 3.0A, 5.0A, and 6.0A Elect ronic Trip Units Rev. 01, 07/2012 Section 1—General Information © 1999–2012 Schneider Electric All Rights Reserved 5-EN ENGLISH Section 1— General Information Communications Micrologic trip units can communicate with other devices if the optional Circuit Breaker Communication Modul ...

  • Schneider Electric 5.0A - page 8

    Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0 A Electronic Trip Units 48049-136-05 Section 1—General Information Rev. 01, 07/2012 © 1999–2012 Schneider Electric All Rights Reserved 6-EN ENGLISH Micrologic 2.0A Tr ip Unit The Micrologic 2.0A trip unit provides basic IEC (LS0) protectio n and a built-in ammeter. A. Trip unit name B. Alphanumeric displ ...

  • Schneider Electric 5.0A - page 9

    48049-136-05 Mic rologic™ 2.0A, 3.0A, 5.0A, and 6.0A Elect ronic Trip Units Rev. 01, 07/2012 Section 1—General Information © 1999–2012 Schneider Electric All Rights Reserved 7-EN ENGLISH Micrologic 5.0A Trip Unit The Micrologic 5.0A trip uni t provides selective (LSI) protection and a built-in ammete r. A. Trip unit name B. Alphanumeric disp ...

  • Schneider Electric 5.0A - page 10

    Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0 A Electronic Trip Units 48049-136-05 Section 1—General Information Rev. 01, 07/2012 © 1999–2012 Schneider Electric All Rights Reserved 8-EN ENGLISH Micrologic 6.0A Tr ip Unit The Micrologic 6.0A trip unit provides selective and ground-fault protection for equipment ( d 1200 A) (LSIG) and a built-in am ...

  • Schneider Electric 5.0A - page 11

    48049-136-05 Mic rologic™ 2.0A, 3.0A, 5.0A, and 6.0A Elect ronic Trip Units Rev. 01, 07/2012 Section 1—General Information © 1999–2012 Schneider Electric All Rights Reserved 9-EN ENGLISH Zone-Selective Interlocking Short-time and ground-fault protection can be interlocked to provide zone-selective interlocking. Control wiring lin ks several ...

  • Schneider Electric 5.0A - page 12

    Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0 A Electronic Trip Units 48049-136-05 Section 1—General Information Rev. 01, 07/2012 © 1999–2012 Schneider Electric All Rights Reserved 10-EN ENGLISH Trip Unit Switches Long-Time Protection Long-time protection protects equipment against overloads. • Long-time protectio n is standard on all trip units. ...

  • Schneider Electric 5.0A - page 13

    48049-136-05 Mic rologic™ 2.0A, 3.0A, 5.0A, and 6.0A Elect ronic Trip Units Rev. 01, 07/2012 Section 1—General Information © 1999–2012 Schneider Electric All Rights Reserved 11-EN ENGLISH Short-Time Protection Short-time protection protects eq uipment against short circuits. • Short-time protection is sta ndard on 2.0A, 5.0A and 6.0A trip ...

  • Schneider Electric 5.0A - page 14

    Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0 A Electronic Trip Units 48049-136-05 Section 1—General Information Rev. 01, 07/2012 © 1999–2012 Schneider Electric All Rights Reserved 12-EN ENGLISH Instantaneous Prot ection Instantaneous protection protects equipmen t against short circu its with no intention al time delay. • Instantaneous protec tio ...

  • Schneider Electric 5.0A - page 15

    48049-136-05 Mic rologic™ 2.0A, 3.0A, 5.0A, and 6.0A Elect ronic Trip Units Rev. 01, 07/2012 Section 1—General Information © 1999–2012 Schneider Electric All Rights Reserved 13-EN ENGLISH Indicator Lights Ground-Fault Protection Equipment ground-fault protection protects conductors against overheating and faults from ground-fault currents ( ...

  • Schneider Electric 5.0A - page 16

    Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0 A Electronic Trip Units 48049-136-05 Section 1—General Information Rev. 01, 07/2012 © 1999–2012 Schneider Electric All Rights Reserved 14-EN ENGLISH Trip Unit Testing Trip unit functions can be tested using primary injection testin g or secondary injection testing. Micrologic Trip Unit Configuration Cont ...

  • Schneider Electric 5.0A - page 17

    48049-136-05 Mic rologic™ 2.0A, 3.0A, 5.0A, and 6.0A Elect ronic Trip Units Rev. 01, 07/2012 Section 1—General Information © 1999–2012 Schneider Electric All Rights Reserved 15-EN ENGLISH The following will be powere d and functional with external power: • All of the above functions which are functional without external power. • Ammeter ...

  • Schneider Electric 5.0A - page 18

    Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0 A Electronic Trip Units 48049-136-05 Section 2—Ammeter Rev. 01, 07/2012 © 1999–2012 Schneider Electric All Rights Reserved 16-EN ENGLISH Section 2— Ammeter Display NOTE: The ammeter disp lay will function only if the trip unit is powered. The trip unit is powered by the circu it breaker carrying more t ...

  • Schneider Electric 5.0A - page 19

    48049-136-05 Mic rologic™ 2.0A, 3.0A, 5.0A, and 6.0A Elect ronic Trip Units Rev. 01, 07/2012 Section 2—Am meter © 1999–2012 Schneider Electric All Rights Reserved 17-EN ENGLISH To access the next menu, press the menu button (A). To access the next screen in a menu, press the scroll button (B). Figure 16: Navigation Buttons Current Menu The c ...

  • Schneider Electric 5.0A - page 20

    Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0 A Electronic Trip Units 48049-136-05 Section 2—Ammeter Rev. 01, 07/2012 © 1999–2012 Schneider Electric All Rights Reserved 18-EN ENGLISH Peak Menu To access the peak menu: 1. Current menu is displayed. 2. Press menu butt on. 3. Peak menu appears. To access menu screens, press scroll button. Figure 18: Ac ...

  • Schneider Electric 5.0A - page 21

    48049-136-05 Mic rologic™ 2.0A, 3.0A, 5.0A, and 6.0A Elect ronic Trip Units Rev. 01, 07/2012 Section 2—Am meter © 1999–2012 Schneider Electric All Rights Reserved 19-EN ENGLISH Switch Settings Menu The switch settings menu displays the value s at which the switches are set. To access the switch settings menu: 1. Peak menu is displayed. 2. Pr ...

  • Schneider Electric 5.0A - page 22

    Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0 A Electronic Trip Units 48049-136-05 Section 3—Operation Rev. 01, 07/2012 © 1999–2012 Schneider Electric All Rights Reserved 20-EN ENGLISH Section 3— Operation Switch Setting Adjustment 1. Open switch cover (A). 2. Adjust the appropriate switches (B) to desired values. 3. Replace switch cover. Use wire ...

  • Schneider Electric 5.0A - page 23

    48049-136-05 Mic rologic™ 2.0A, 3.0A, 5.0A, and 6.0A Elect ronic Trip Units Rev. 01, 07/2012 Section 3—Operation © 1999–2012 Schneider Electric All Rights Reserved 21-EN ENGLISH 2. Set time delay. Figure 26: Set Time Delay Micrologic 3.0A Trip Unit 1. Set pickup levels. Figure 27: Set Pickup Levels 2. Set time delay. Figure 28: Set Time Dela ...

  • Schneider Electric 5.0A - page 24

    Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0 A Electronic Trip Units 48049-136-05 Section 3—Operation Rev. 01, 07/2012 © 1999–2012 Schneider Electric All Rights Reserved 22-EN ENGLISH 2. Set time delay. Figure 30: Set Time Delays Micrologic 6.0A Tr ip Unit 1. Set pick up levels. Figure 31: Set Pickup Levels 2. Set time delays. Figure 32: Set Pickup ...

  • Schneider Electric 5.0A - page 25

    48049-136-05 Mic rologic™ 2.0A, 3.0A, 5.0A, and 6.0A Elect ronic Trip Units Rev. 01, 07/2012 Section 3—Operation © 1999–2012 Schneider Electric All Rights Reserved 23-EN ENGLISH Zone-Selective Interlocking (ZSI) The number of devices which can be interlocked are shown in Table 8. Table 8: ZSI Combinations Micrologic #.0x Trip Units Square D ...

  • Schneider Electric 5.0A - page 26

    Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0 A Electronic Trip Units 48049-136-05 Section 3—Operation Rev. 01, 07/2012 © 1999–2012 Schneider Electric All Rights Reserved 24-EN ENGLISH Wire circuit breakers for zone-selective interlocking. Figure 34: ZSI Wiring Example Communication Module values If the optional circuit breaker commu nication module ...

  • Schneider Electric 5.0A - page 27

    48049-136-05 Mic rologic™ 2.0A, 3.0A, 5.0A, and 6.0A Elect ronic Trip Units Rev. 01, 07/2012 Section 3—Operation © 1999–2012 Schneider Electric All Rights Reserved 25-EN ENGLISH Set communication module values: 1. Press and release scroll button to sequence addresses (1 through 47). When the co rrect address number is reache d, enter the val ...

  • Schneider Electric 5.0A - page 28

    Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0 A Electronic Trip Units 48049-136-05 Section 3—Operation Rev. 01, 07/2012 © 1999–2012 Schneider Electric All Rights Reserved 26-EN ENGLISH Trip Unit Settings Check Use the ammeter switch setting menu to check the trip unit settings. 1. Press menu butt on twice. 2. Switch settings menu will appear. 3. Pre ...

  • Schneider Electric 5.0A - page 29

    48049-136-05 Mic rologic™ 2.0A, 3.0A, 5.0A, and 6.0A Elect ronic Trip Units Rev. 01, 07/2012 Section 3—Operation © 1999–2012 Schneider Electric All Rights Reserved 27-EN ENGLISH Equipment Ground-Fault Trip Functions Testing Paragraph 230-95 (c) of the National Electri cal Code requires that all equipment gro und-fault protection systems be t ...

  • Schneider Electric 5.0A - page 30

    Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0 A Electronic Trip Units 48049-136-05 Section 4—Trip Unit Replac ement Rev. 01, 07/2012 © 1999–2012 Schneider Electric All Rights Reserved 28-EN ENGLISH Section 4— Trip Unit Replacement Required Tools • Torque-controlled screwdriver, set at 7 in-lbs (0.8 N•m) ± 10% (Lindstrom torque driver MAL500-2 ...

  • Schneider Electric 5.0A - page 31

    48049-136-05 Mic rologic™ 2.0A, 3.0A, 5.0A, and 6.0A Elect ronic Trip Units Rev. 01, 07/2012 Section 4—Trip Unit Re placement © 1999–2012 Schneider Electric All Rights Reserved 29-EN ENGLISH Trip Unit Replacement Rating Plug Removal A small Phillips screwdriver i s needed to remove the adjustable rating plug. 1. Open switch cover (A). 2. Uns ...

  • Schneider Electric 5.0A - page 32

    Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0 A Electronic Trip Units 48049-136-05 Section 4—Trip Unit Replac ement Rev. 01, 07/2012 © 1999–2012 Schneider Electric All Rights Reserved 30-EN ENGLISH Trip Unit Installation 1. Inspect trip unit conne ctor pins and surfaces. If there is any damage, misaligned pins, or contamination, stop in stallation a ...

  • Schneider Electric 5.0A - page 33

    48049-136-05 Mic rologic™ 2.0A, 3.0A, 5.0A, and 6.0A Elect ronic Trip Units Rev. 01, 07/2012 Section 4—Trip Unit Re placement © 1999–2012 Schneider Electric All Rights Reserved 31-EN ENGLISH Circuit Breaker Accessory Cover Replacement Replace circuit breaker accessory cover as directed in the Install Accessories section of the circuit breake ...

  • Schneider Electric 5.0A - page 34

    Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0 A Electronic Trip Units 48049-136-05 Section 4—Trip Unit Replac ement Rev. 01, 07/2012 © 1999–2012 Schneider Electric All Rights Reserved 32-EN ENGLISH Trip Unit Installation Ch eck Trip Unit Setup 1. If an auxiliary power supply is being used for the Micrologic trip unit, reconnect the auxil iary power ...

  • Schneider Electric 5.0A - page 35

    48049-136-05 Mic rologic™ 2.0A, 3.0A, 5.0A, and 6.0A Elect ronic Trip Units Rev. 01, 07/2012 Section 5—Adjustab le Rating Plug Replacement © 1999–2012 Schneider Electric All Rights Reserved 33-EN ENGLISH Section 5— Adjustable Rating Plug Replacement NOTE: To select correct replacement rating plug, see the product catalog. NOTE: If adjustab ...

  • Schneider Electric 5.0A - page 36

    Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0 A Electronic Trip Units 48049-136-05 Section 6—Battery Replacement Rev. 01, 07/2012 © 1999–2012 Schneider Electric All Rights Reserved 34-EN ENGLISH Section 6— Battery Replacement Circuit Breaker Disconnection Disconnect circuit breaker as directed in the circuit breaker instruction bul letin shipped w ...

  • Schneider Electric 5.0A - page 37

    48049-136-05 Mic rologic™ 2.0A, 3.0A, 5.0A, and 6.0A Elect ronic Trip Units Rev. 01, 07/2012 Section 6—Battery Re placement © 1999–2012 Schneider Electric All Rights Reserved 35-EN ENGLISH Circuit Breaker Accessory Cover Replacement Replace circuit breaker accessory cover as directed in the Install Accessories section of the circuit breaker ...

  • Schneider Electric 5.0A - page 38

    Micrologic™ 2.0A, 3.0A, 5.0A, and 6.0 A Electronic Trip Units 48049-136-05 Appendix A—Register List Rev. 01, 07/2012 © 1999–2012 Schneider Electric All Rights Reserved 36-EN ENGLISH Appendix A—Register List List of Registers The quantities are listed in alphabetical order according to the SMS topic name. NOTE: A system scan rate of 500 ms ...

  • Schneider Electric 5.0A - page 39

    48049-136-05 Mic rologic™ 2.0A, 3.0A, 5.0A, and 6.0A Elect ronic Trip Units Rev. 01, 07/2012 Append ix A—Register List © 1999–2012 Schneider Electric All Rights Reserved 37-EN ENGLISH TU_BATT_PCT Trip Unit % Battery 1 8843 PM % Unity TU_SN Trip Unit Serial Number 4 8700 PM ASCII text TUCommStatus Trip Unit Internal Comms Status 1 552 BCM Bit ...

  • Schneider Electric 5.0A - page 40

    Electrical equipment should be instal led, operated, serviced, and maint ained only by qualified personnel. No re sponsibility is assumed by Schneider Electric for an y consequences arising out of the use of this material. Square D™, Schneider Elect ric™, Micrologic™, Modbus, and Masterp a ct™ are trademarks or registered tra demarks of Sch ...

Производитель Schneider Electric Категория Gas Grill

Документы, которые мы получаем от производителя устройства Schneider Electric 5.0A мы можем разделить на несколько групп. Это в частности:
- технические чертежи Schneider Electric
- инструкции обслуживания 5.0A
- паспорта изделия Schneider Electric
- информационные брошюры
- энергетические этикетки Schneider Electric 5.0A
Все из них важны, однако самую важную информацию с точки зрения пользователя мы найдем в инструкции обслуживания Schneider Electric 5.0A.

Группа документов, определяемая как инструкции обслуживания, делится также на более подробные типы, такие как: Инструкции монтажа Schneider Electric 5.0A, инструкции обслуживания, короткие инструкции или инструкции пользователя Schneider Electric 5.0A. В зависимости от потребностей, Вам необходимо поискать требуемый документ. На нашем сайте Вы можете просмотреть самую популярную инструкцию использования изделия Schneider Electric 5.0A.

Похожие инструкции обслуживания

Полная инструкция обслуживания устройства Schneider Electric 5.0A, как должна выглядеть?
Инструкция обслуживания, определяемая также как пособие пользователя, или просто "руководство" - это технический документ, цель которого заключается в использовании Schneider Electric 5.0A пользователями. Инструкции пишет, как правило технический писатель, языком, доступным для всех пользователей Schneider Electric 5.0A.

Полная инструкция обслуживания Schneider Electric, должна заключать несколько основных элементов. Часть из них менее важная, как например: обложка / титульный лист или авторские страницы. Однако остальная часть, должна дать нам важную с точки зрения пользователя информацию.

1. Вступление и рекомендации, как пользоваться инструкцией Schneider Electric 5.0A - В начале каждой инструкции, необходимо найти указания, как пользоваться данным пособием. Здесь должна находится информация, касающаяся местонахождения содержания Schneider Electric 5.0A, FAQ и самых распространенных проблем - то есть мест, которые чаще всего ищут пользователи в каждой инструкции обслуживания
2. Содержание - индекс всех советов, касающихся Schneider Electric 5.0A, которое найдем в данном документе
3. Советы по использованию основных функций устройства Schneider Electric 5.0A - которые должны облегчить нам первые шаги во время использования Schneider Electric 5.0A
4. Troubleshooting - систематизированный ряд действия, который поможет нам диагностировать а в дальнейшем очередность решения важнейших проблем Schneider Electric 5.0A
5. FAQ - чаще всего задаваемые вопросы
6. Контактные данные Информация о том, где искать контактные данные производителя / сервисного центра Schneider Electric 5.0A в данной стране, если самостоятельно не получится решить проблему.

У вас вопрос, касающийся Schneider Electric 5.0A?

Воспользуйтесь формуляром, находящимся ниже

Если с помощью найденной инструкции Вы не решили свою проблему с Schneider Electric 5.0A, задайте вопрос, заполнив следующий формуляр. Если у какого то из пользователей была похожая проблема с Schneider Electric 5.0A со всей вероятностью он захочет поделиться методом ее решения.

Перепишите текст с картинки

Комментарии (0)