    TECHNICAL GUIDE AFFINITY R-410A SPLIT -SYSTEM AIR CONDITIONERS 18 SEER MODELS: CZH024 THRU 060 (2 THRU 5 NOMINAL T ONS) Due to continuou s produc t improvement, specific a tions are subjec t to ch a nge without notice. Visit us on the web at www .york.com for the most up-to-date technical inform ation. Additional rati ng information ca n be found a ...

  • York CZH024 THRU 060 - page 2

    350154-YTG-C-0808 2 Johnson Controls Unitary Products All dimensions are in inches. They a re subject to change without notice. Certified dimensions will be provided upon requ est. Physical and Electr ical Dat a MODEL CZH0241 1 CZH0361 1 CZH0481 1 CZH0601 1 Unit Supply V oltage 208-230V , 1 φ, 60Hz Normal V oltage Range 1 187 to 252 Minimum Circui ...

  • York CZH024 THRU 060 - page 3

    350154-YTG -C-0808 Johnson Controls Unitary Products 3 PROCEDURES: 1. Unit factory charge listed on the unit nameplate includes refr igerant for the condenser , the sma llest evaporator and 15 feet of intercon- necting line tubing. 2. V erify the TXV and additional charge required for specific evaporator coil in the system using the above table. 3. ...

  • York CZH024 THRU 060 - page 4

    350154-YTG-C-0808 4 Johnson Controls Unitary Products COOLING CAP ACITY - With Air Handler Coils UNIT MODEL AIR HANDLER COIL MODEL 1 COOLING MODEL W ST AGE RA TED CFM NET MBH SEER EER 1 PH 18 SEER AC WITH MV CZH0241 1 MV12B 17 FC/MC/PC35B 1 620 18.2 13.8 17.05 14.50 2 800 23.6 17.2 13.80 MV12B 17 FC/MC/PC35C 1 620 18.2 13.8 17.05 14.50 2 800 23.6 1 ...

  • York CZH024 THRU 060 - page 5

    350154-YTG -C-0808 Johnson Controls Unitary Products 5 COOLING CAP ACITY - CZH0241 1 With V ariable S peed Furnaces V ARIABLE SPEED FURNACE MODEL COIL MODEL 1 W COOLING ST AGE RA TED CFM NET MBH SEER EER TOT AL SENSIBLE 1 PH 18 SEER AC WITH V ARIABLE SPEED FURNACES 2 PV8*A12 FC/MC/PC32A 14 1 470 17.2 13.0 16.70 14.15 2 750 23.2 16.9 13.55 PV9*A12 F ...

  • York CZH024 THRU 060 - page 6

    350154-YTG-C-0808 6 Johnson Controls Unitary Products Y*(8,L)C*B12 UC36B 17 1 525 16.6 1 1.9 16.00 13.50 2 765 22.2 15.5 13.25 Y*9C*B12 UC36B 17 1 590 17.0 12.8 16.00 13.75 2 815 22.4 15.7 13.00 G*9V*A12 FC/MC/PC30A 14 1 625 17.8 13.4 16.50 14.00 2 800 23.0 16.2 13.25 G*9V*A12 FC/MC/PC32A 14 1 625 17.8 13.4 16.25 14.00 2 800 23.0 16.3 13.00 G*9V*A1 ...

  • York CZH024 THRU 060 - page 7

    350154-YTG -C-0808 Johnson Controls Unitary Products 7 COOLING CAP ACITY - CZH0361 1With V ariable S peed Furnaces V ARIABLE SPEED FURNACE MODEL COIL MODEL 1 W COOLING ST AGE RA TED CFM NET MBH SEER EER TOT AL SENSIBLE 1 PH 18 SEER AC WITH V ARIABLE SPEED FURNACES 2 PV8*A12 FC/MC/PC37A 14 1 750 25.4 17.9 17.50 14.80 2 1 185 35.8 25.0 13.25 PV9*A12 ...

  • York CZH024 THRU 060 - page 8

    350154-YTG-C-0808 8 Johnson Controls Unitary Products Y*9C*C16 FC/MC/PC35C 21 1 790 25.0 17.5 17.25 14.25 2 1215 35.4 24.7 13.00 Y*9C*C20 FC/MC/PC35C 21 1 760 24.6 16.8 17.00 14.25 2 1330 35.6 25.3 12.75 Y*(8,L)C*A12 FC/MC/PC36A 14 1 815 24.8 17.3 16.75 14.00 2 1 190 34.6 23.7 12.50 Y*(8,L)C*B12 FC/MC/PC36B 17 1 745 24.6 16.7 17.00 14.25 2 1220 34. ...

  • York CZH024 THRU 060 - page 9

    350154-YTG -C-0808 Johnson Controls Unitary Products 9 Y*9C*C16 HC42 21 1 815 25.0 17.6 17.25 14.25 2 1240 35.6 24.9 13.00 Y*9C*C20 HC42 21 1 780 25.0 17.6 17.50 14.50 2 1200 35.8 25.1 13.25 Y*(8,L)C*B12 HD48 17 1 750 24.8 17.0 17.25 14.50 2 1210 35.8 25.1 13.25 Y*9C*B12 HD48 17 1 710 24.6 16.5 17.00 14.25 2 1 150 35.4 24.3 13.00 Y*(8,L)C*C16 HD48 ...

  • York CZH024 THRU 060 - page 10

    350154-YTG-C-0808 10 Johnson Controls Unitary Products G*9V*B12 FC/MC/PC35B 17 1 810 25.0 17.4 16.75 14.00 2 1 190 35.2 24.5 12.75 G*9V*C16 FC/MC/PC35C 21 1 790 25.0 17.5 17.25 14.25 2 1215 35.4 24.7 13.00 G*9V*C20 FC/MC/PC35C 21 1 760 24.6 16.8 17.00 14.25 2 1330 35.6 25.3 12.75 G*9V*B12 FC/MC/PC36B 17 1 800 25.0 17.3 17.00 14.25 2 1 165 34.8 23.9 ...

  • York CZH024 THRU 060 - page 11

    350154-YTG -C-0808 Johnson Controls Unitary Products 11 COOLING CAP ACITY - CZH0481 1With V ariable S peed Furnaces V ARIABLE SPEED FURNACE MODEL COIL MODEL 1 W COOLING ST AGE RA TED CFM NET MBH SEER EER TOT AL SENSIBLE 1 PH 18 SEER AC WITH V ARIABLE SPEED FURNACES 2 PV8*C16 FC/MC/PC48C 21 1 880 33.0 24.4 16.90 13.90 2 1500 45.0 34.4 1 1.95 PV8*C16 ...

  • York CZH024 THRU 060 - page 12

    350154-YTG-C-0808 12 Johnson Controls Unitary Products Y*(8,L)C*C20 HD48 21 1 1080 32.8 24.0 16.00 13.25 2 1640 45.5 33.7 1 1.75 Y*9C*C16 HD48 21 1 1050 33.0 24.0 16.25 13.25 2 1590 45.0 33.5 1 1.75 Y*9C*C20 HD48 21 1 1055 33.0 24.0 16.25 13.50 2 1655 45.0 33.5 1 1.75 Y*9C*D20 HD48 24 1 1060 32.8 24.0 16.25 13.25 2 1645 45.5 33.7 1 1.75 Y*(8,L)C*C1 ...

  • York CZH024 THRU 060 - page 13

    350154-YTG -C-0808 Johnson Controls Unitary Products 13 G*9V*C20 HD48 21 1 1055 33.0 24.0 16.25 13.50 2 1655 45.0 33.5 1 1.75 G*9V*D20 HD48 24 1 1060 32.8 24.0 16.25 13.25 2 1645 45.5 33.7 1 1.75 G*9V*C16 HD60 21 1 1050 33.4 24.6 16.25 13.50 2 1590 45.5 34.6 1 1.75 G*9V*C20 HD60 21 1 1055 33.6 24.6 16.50 13.75 2 1655 45.5 34.6 1 1.75 G*9V*D20 HD60 ...

  • York CZH024 THRU 060 - page 14

    350154-YTG-C-0808 14 Johnson Controls Unitary Products ACCESSORIES* Hard St a rt Kit (024-31994-000, 024-31995-000) - Provides increased starting torque for areas with low voltage. TXV Kits - 1 TVM9 series th ermal expansion valves precisely meter refrigerant for optimum performan ce Dehumidistat (2HU16700124) - Provides increased dehumidi- ficatio ...

  • York CZH024 THRU 060 - page 15

    350154-YTG -C-0808 Johnson Controls Unitary Products 15 Multipliers for determining the pe rformance with other indoor sect ions. NOTE: For dry bulb temperatures dif ferent than those listed ( bet ween 73-87 F), sensible capacity incr eases by 10 60 BTUH per 100 0 CFM per degree above the listed temperature and decrease s by 1060 BTUH per 1000 CFM ...

  • York CZH024 THRU 060 - page 16

    350154-YTG-C-0808 16 Johnson Controls Unitary Products Multipliers for determining th e performance with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (betwe en 73-87 F), sensible cap acity increases by 1060 BTUH per 100 0 CFM per degree above the listed temperature and decreases by 1060 BTUH per 1000 CFM per d ...

  • York CZH024 THRU 060 - page 17

    350154-YTG -C-0808 Johnson Controls Unitary Products 17 Multipliers for determining the pe rformance with other indoor sect ions. NOTE: For dry bulb temperatures dif ferent than those listed ( bet ween 73-87 F), sensible capacity incr eases by 10 60 BTUH per 100 0 CFM per degree above the listed temperature and decrease s by 1060 BTUH per 1000 CFM ...

  • York CZH024 THRU 060 - page 18

    350154-YTG-C-0808 18 Johnson Controls Unitary Products P(C,V)9*C20 FC/MC/PC48D 1.01 1.01 1.02 P(C,V)9*C20 UC48D 1.01 1.01 1.02 P(C,V)9*D20 FC/MC/PC48D 1.01 1.01 1.01 P(C,V)9*D20 UC48D 1.01 1.01 1.01 PV8*C20 FC/MC62D 1.01 1.01 1.01 P(C,V)9*C20 FC/MC62D 1.01 1.01 1.02 P(C,V)9*D20 FC/MC62D 1.01 1.01 1.02 PV8*C16 HC42C 0.96 0.96 0.99 PV8*C20 HC42C 1.00 ...

  • York CZH024 THRU 060 - page 19

    350154-YTG -C-0808 Johnson Controls Unitary Products 19 Multipliers for determining the pe rformance with other indoor sect ions. NOTE: For dry bulb temperatures dif ferent than those listed ( bet ween 73-87 F), sensible capacity incr eases by 10 60 BTUH per 100 0 CFM per degree above the listed temperature and decrease s by 1060 BTUH per 1000 CFM ...

  • York CZH024 THRU 060 - page 20

    350154-YTG-C-0808 20 Johnson Controls Unitary Products P(C,V)9*C20 FC/MC/PC48D 0.99 0.99 1.03 P(C,V)9*C20 UC48D 0.99 0.99 1.03 P(C,V)9*D20 FC/MC/PC48D 0.99 0.99 1.02 P(C,V)9*D20 UC48D 0.99 0.99 1.02 PV8*C20 FC/MC62D 1.00 1.00 1.04 P(C,V)9*C20 FC/MC62D 1.00 1.00 1.03 P(C,V)9*D20 FC/MC62D 1.01 1.00 1.02 PV8*C16 HC42C 0.99 0.99 1.02 PV8*C20 HC42C 0.98 ...

  • York CZH024 THRU 060 - page 21

    350154-YTG -C-0808 Johnson Controls Unitary Products 21 Multipliers for determining the pe rformance with other indoor sect ions. NOTE: For dry bulb temperatures dif ferent than those listed ( bet ween 73-87 F), sensible capacity incr eases by 10 60 BTUH per 100 0 CFM per degree above the listed temperature and decrease s by 1060 BTUH per 1000 CFM ...

  • York CZH024 THRU 060 - page 22

    350154-YTG-C-0808 22 Johnson Controls Unitary Products Va r i a b l e S p e e d Furnace Coil T .C. S.C. KW PV8*C16 FC/MC/PC48C 0.97 0.97 0.98 PV8*C16 FC/MC/PC48D 0.97 0.97 0.98 PV8*C16 UC48D 0.97 0.97 0.98 PV8*C20 FC/MC/PC48C 1.00 1.00 0.99 PV8*C20 FC/MC/PC48D 1.00 1.00 0.99 PV8*C20 UC48D 1.00 1.00 0.99 P(C,V)9*C16 FC/MC/PC48C 1.01 1.02 0.98 P(C,V) ...

  • York CZH024 THRU 060 - page 23

    350154-YTG -C-0808 Johnson Controls Unitary Products 23 Multipliers for determining the pe rformance with other indoor sect ions NOTE: For dry bulb temperatures dif ferent than those listed ( bet ween 73-87 F), sensible capacity incr eases by 10 60 BTUH per 100 0 CFM per degree above the listed temperature and decrease s by 1060 BTUH per 1000 CFM p ...

  • York CZH024 THRU 060 - page 24

    350154-YTG-C-0808 24 Johnson Controls Unitary Products Va r i a b l e S p e e d Furnace Coil T .C. S.C. KW PV8*C16 FC/MC/PC48C 0.97 0.97 1.01 PV8*C16 FC/MC/PC48D 0.97 0.97 1.01 PV8*C16 UC48D 0.97 0.97 1.01 PV8*C20 FC/MC/PC48C 0.98 0.98 1.02 PV8*C20 FC/MC/PC48D 0.98 0.98 1.02 PV8*C20 UC48D 0.98 0.98 1.02 P(C,V)9*C16 FC/MC/PC48C 0.98 0.98 1.03 P(C,V) ...

  • York CZH024 THRU 060 - page 25

    350154-YTG -C-0808 Johnson Controls Unitary Products 25 Multipliers for determining the pe rformance with other indoor sect ions. NOTE: For dry bulb temperatures dif ferent than those listed ( bet ween 73-87 F), sensible capacity incr eases by 10 60 BTUH per 100 0 CFM per degree above the listed temperature and decrease s by 1060 BTUH per 1000 CFM ...

  • York CZH024 THRU 060 - page 26

    Subject to change without notice. Printe d in U.S.A. 350154-YTG-C-0808 Copyright © 2008 by Johnson Controls, Inc. All ri ghts reserved. Supersedes: 350154-YTG-B-0408 Johnson Controls Unit ary Produ cts 5005 Y ork Drive Norman, OK 73069 Multipliers for determining th e performance with other indoor sections. NOTE: For dry bulb temperatures dif fere ...

Produzent York Kategorie Air Conditioner

Dokumente, die wir vom Produzenten des Geräts York CZH024 THRU 060 erhalten, können wir in mehrere Gruppen teilen. Unteranderem in:
- technische Zeichnungen York
- Bedienungsanleitungen CZH024 THRU 060
- Produktkarten York
- Informationsbroschüren
- oder Energieetiketten York CZH024 THRU 060
Jede von ihnen ist wichtig, jedoch finden wir die wichtigsten Informationen für den Nutzer des Geräts in der Bedienungsanleitung York CZH024 THRU 060.

Die Dokumentengruppe, die als Bedienungsanleitungen bezeichnet wird, wird ebenfalls in detaillierte Arten geteilt, solche wie: Montageanleitungen York CZH024 THRU 060, Wartungsanleitungen, Kurzanleitungen oder Benutzeranleitungen York CZH024 THRU 060. Abhängig vom Bedarf, sollten Sie das Dokument finden, das Sie brauchen. In unserem Service können Sie sich die populärste Bedienungsanleitung des Produkts York CZH024 THRU 060 ansehen.

Ähnliche Bedienungsanleitungen

Die komplette Bedienungsanleitung des Geräts York CZH024 THRU 060, wie sollte sie aussehen?
Die Bedienungsanleitung, auch bezeichnet als Benutzerhandbuch, oder einfach nur „Anleitung”, ist ein technisches Dokument, das dem Benutzer bei der Nutzung von York CZH024 THRU 060 hilfreich sein soll. Die Bedienungsanleitungen werden in der Regel von technischen Schriftstellern geschrieben, aber in einer Sprache, die für alle Nutzer von York CZH024 THRU 060 verständlich ist.

Eine gänzliche Bedienungsanleitung von York sollte einige Grundelemente enthalten. Ein Teil von ihnen ist nicht so wichtig, wie z.B.: die Titelseite oder Autorenseiten. Die restlichen von ihnen jedoch, sollten Informationen liefern, die für den Nutzer von enormer Wichtigkeit sind.

1. Einführung und Hinweise, wie man sich in einer Bedienungsanleitung von York CZH024 THRU 060 bewegt - Am Anfang jeder Bedienungsanleitung sollten wir Hinweise bezüglich der Nutzungsart eines bestimmten Ratgebers finden. In ihr sollten sich Informationen über die Lokalisierung des Inhaltsverzeichnisses von York CZH024 THRU 060 befinden, FAQ oder über oft auftretende Probleme – also Stellen, die von den Benutzern in jeder Bedienungsanleitung am meisten gesucht werden
2. Inhaltsverzeichnis - Index aller Ratschläge bezüglich York CZH024 THRU 060, die wir im aktuellen Dokument finden
3. Ratschläge zur Nutzung der Grundfunktionen des Geräts York CZH024 THRU 060 - die uns die ersten Schritte während der Nutzung von York CZH024 THRU 060 erleichtern sollten
4. Troubleshooting - geordneter Tätigkeitslauf, der uns bei der Diagnose und als nächstes bei der Lösung wichtiger Probleme mit York CZH024 THRU 060 hilft
5. FAQ - häufig gestellte Fragen
6. Kontaktdaten Informationen darüber, wo man Kontakt zum Produzenten / Service von York CZH024 THRU 060 im bestimmten Land suchen kann, wenn es nicht gelingt, das Problem selbst zu lösen.

Haben Sie eine Frage bezüglich York CZH024 THRU 060?

Nutzen Sie das untere Formular

Wenn Sie mit Hilfe der gefundenen Bedienungsanleitung Ihr Problem mit York CZH024 THRU 060 nicht gelöst haben, stellen Sie eine Frage, indem Sie das untere Formular nutzen. Wenn einer der Nutzer ein ähnliches Problem mit York CZH024 THRU 060 hatte, ist es möglich, dass er mit Ihnen die Lösung teilen möchte.

Text vom Bild übertragen

Kommentare (0)