  • York CZH024 THRU 060 - page 1

    TECHNICAL GUIDE AFFINITY R-410A SPLIT -SYSTEM AIR CONDITIONERS 18 SEER MODELS: CZH024 THRU 060 (2 THRU 5 NOMINAL T ONS) Due to continuou s produc t improvement, specific a tions are subjec t to ch a nge without notice. Visit us on the web at www .york.com for the most up-to-date technical inform ation. Additional rati ng information ca n be found a ...

  • York CZH024 THRU 060 - page 2

    350154-YTG-C-0808 2 Johnson Controls Unitary Products All dimensions are in inches. They a re subject to change without notice. Certified dimensions will be provided upon requ est. Physical and Electr ical Dat a MODEL CZH0241 1 CZH0361 1 CZH0481 1 CZH0601 1 Unit Supply V oltage 208-230V , 1 φ, 60Hz Normal V oltage Range 1 187 to 252 Minimum Circui ...

  • York CZH024 THRU 060 - page 3

    350154-YTG -C-0808 Johnson Controls Unitary Products 3 PROCEDURES: 1. Unit factory charge listed on the unit nameplate includes refr igerant for the condenser , the sma llest evaporator and 15 feet of intercon- necting line tubing. 2. V erify the TXV and additional charge required for specific evaporator coil in the system using the above table. 3. ...

  • York CZH024 THRU 060 - page 4

    350154-YTG-C-0808 4 Johnson Controls Unitary Products COOLING CAP ACITY - With Air Handler Coils UNIT MODEL AIR HANDLER COIL MODEL 1 COOLING MODEL W ST AGE RA TED CFM NET MBH SEER EER 1 PH 18 SEER AC WITH MV CZH0241 1 MV12B 17 FC/MC/PC35B 1 620 18.2 13.8 17.05 14.50 2 800 23.6 17.2 13.80 MV12B 17 FC/MC/PC35C 1 620 18.2 13.8 17.05 14.50 2 800 23.6 1 ...

  • York CZH024 THRU 060 - page 5

    350154-YTG -C-0808 Johnson Controls Unitary Products 5 COOLING CAP ACITY - CZH0241 1 With V ariable S peed Furnaces V ARIABLE SPEED FURNACE MODEL COIL MODEL 1 W COOLING ST AGE RA TED CFM NET MBH SEER EER TOT AL SENSIBLE 1 PH 18 SEER AC WITH V ARIABLE SPEED FURNACES 2 PV8*A12 FC/MC/PC32A 14 1 470 17.2 13.0 16.70 14.15 2 750 23.2 16.9 13.55 PV9*A12 F ...

  • York CZH024 THRU 060 - page 6

    350154-YTG-C-0808 6 Johnson Controls Unitary Products Y*(8,L)C*B12 UC36B 17 1 525 16.6 1 1.9 16.00 13.50 2 765 22.2 15.5 13.25 Y*9C*B12 UC36B 17 1 590 17.0 12.8 16.00 13.75 2 815 22.4 15.7 13.00 G*9V*A12 FC/MC/PC30A 14 1 625 17.8 13.4 16.50 14.00 2 800 23.0 16.2 13.25 G*9V*A12 FC/MC/PC32A 14 1 625 17.8 13.4 16.25 14.00 2 800 23.0 16.3 13.00 G*9V*A1 ...

  • York CZH024 THRU 060 - page 7

    350154-YTG -C-0808 Johnson Controls Unitary Products 7 COOLING CAP ACITY - CZH0361 1With V ariable S peed Furnaces V ARIABLE SPEED FURNACE MODEL COIL MODEL 1 W COOLING ST AGE RA TED CFM NET MBH SEER EER TOT AL SENSIBLE 1 PH 18 SEER AC WITH V ARIABLE SPEED FURNACES 2 PV8*A12 FC/MC/PC37A 14 1 750 25.4 17.9 17.50 14.80 2 1 185 35.8 25.0 13.25 PV9*A12 ...

  • York CZH024 THRU 060 - page 8

    350154-YTG-C-0808 8 Johnson Controls Unitary Products Y*9C*C16 FC/MC/PC35C 21 1 790 25.0 17.5 17.25 14.25 2 1215 35.4 24.7 13.00 Y*9C*C20 FC/MC/PC35C 21 1 760 24.6 16.8 17.00 14.25 2 1330 35.6 25.3 12.75 Y*(8,L)C*A12 FC/MC/PC36A 14 1 815 24.8 17.3 16.75 14.00 2 1 190 34.6 23.7 12.50 Y*(8,L)C*B12 FC/MC/PC36B 17 1 745 24.6 16.7 17.00 14.25 2 1220 34. ...

  • York CZH024 THRU 060 - page 9

    350154-YTG -C-0808 Johnson Controls Unitary Products 9 Y*9C*C16 HC42 21 1 815 25.0 17.6 17.25 14.25 2 1240 35.6 24.9 13.00 Y*9C*C20 HC42 21 1 780 25.0 17.6 17.50 14.50 2 1200 35.8 25.1 13.25 Y*(8,L)C*B12 HD48 17 1 750 24.8 17.0 17.25 14.50 2 1210 35.8 25.1 13.25 Y*9C*B12 HD48 17 1 710 24.6 16.5 17.00 14.25 2 1 150 35.4 24.3 13.00 Y*(8,L)C*C16 HD48 ...

  • York CZH024 THRU 060 - page 10

    350154-YTG-C-0808 10 Johnson Controls Unitary Products G*9V*B12 FC/MC/PC35B 17 1 810 25.0 17.4 16.75 14.00 2 1 190 35.2 24.5 12.75 G*9V*C16 FC/MC/PC35C 21 1 790 25.0 17.5 17.25 14.25 2 1215 35.4 24.7 13.00 G*9V*C20 FC/MC/PC35C 21 1 760 24.6 16.8 17.00 14.25 2 1330 35.6 25.3 12.75 G*9V*B12 FC/MC/PC36B 17 1 800 25.0 17.3 17.00 14.25 2 1 165 34.8 23.9 ...

  • York CZH024 THRU 060 - page 11

    350154-YTG -C-0808 Johnson Controls Unitary Products 11 COOLING CAP ACITY - CZH0481 1With V ariable S peed Furnaces V ARIABLE SPEED FURNACE MODEL COIL MODEL 1 W COOLING ST AGE RA TED CFM NET MBH SEER EER TOT AL SENSIBLE 1 PH 18 SEER AC WITH V ARIABLE SPEED FURNACES 2 PV8*C16 FC/MC/PC48C 21 1 880 33.0 24.4 16.90 13.90 2 1500 45.0 34.4 1 1.95 PV8*C16 ...

  • York CZH024 THRU 060 - page 12

    350154-YTG-C-0808 12 Johnson Controls Unitary Products Y*(8,L)C*C20 HD48 21 1 1080 32.8 24.0 16.00 13.25 2 1640 45.5 33.7 1 1.75 Y*9C*C16 HD48 21 1 1050 33.0 24.0 16.25 13.25 2 1590 45.0 33.5 1 1.75 Y*9C*C20 HD48 21 1 1055 33.0 24.0 16.25 13.50 2 1655 45.0 33.5 1 1.75 Y*9C*D20 HD48 24 1 1060 32.8 24.0 16.25 13.25 2 1645 45.5 33.7 1 1.75 Y*(8,L)C*C1 ...

  • York CZH024 THRU 060 - page 13

    350154-YTG -C-0808 Johnson Controls Unitary Products 13 G*9V*C20 HD48 21 1 1055 33.0 24.0 16.25 13.50 2 1655 45.0 33.5 1 1.75 G*9V*D20 HD48 24 1 1060 32.8 24.0 16.25 13.25 2 1645 45.5 33.7 1 1.75 G*9V*C16 HD60 21 1 1050 33.4 24.6 16.25 13.50 2 1590 45.5 34.6 1 1.75 G*9V*C20 HD60 21 1 1055 33.6 24.6 16.50 13.75 2 1655 45.5 34.6 1 1.75 G*9V*D20 HD60 ...

  • York CZH024 THRU 060 - page 14

    350154-YTG-C-0808 14 Johnson Controls Unitary Products ACCESSORIES* Hard St a rt Kit (024-31994-000, 024-31995-000) - Provides increased starting torque for areas with low voltage. TXV Kits - 1 TVM9 series th ermal expansion valves precisely meter refrigerant for optimum performan ce Dehumidistat (2HU16700124) - Provides increased dehumidi- ficatio ...

  • York CZH024 THRU 060 - page 15

    350154-YTG -C-0808 Johnson Controls Unitary Products 15 Multipliers for determining the pe rformance with other indoor sect ions. NOTE: For dry bulb temperatures dif ferent than those listed ( bet ween 73-87 F), sensible capacity incr eases by 10 60 BTUH per 100 0 CFM per degree above the listed temperature and decrease s by 1060 BTUH per 1000 CFM ...

  • York CZH024 THRU 060 - page 16

    350154-YTG-C-0808 16 Johnson Controls Unitary Products Multipliers for determining th e performance with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (betwe en 73-87 F), sensible cap acity increases by 1060 BTUH per 100 0 CFM per degree above the listed temperature and decreases by 1060 BTUH per 1000 CFM per d ...

  • York CZH024 THRU 060 - page 17

    350154-YTG -C-0808 Johnson Controls Unitary Products 17 Multipliers for determining the pe rformance with other indoor sect ions. NOTE: For dry bulb temperatures dif ferent than those listed ( bet ween 73-87 F), sensible capacity incr eases by 10 60 BTUH per 100 0 CFM per degree above the listed temperature and decrease s by 1060 BTUH per 1000 CFM ...

  • York CZH024 THRU 060 - page 18

    350154-YTG-C-0808 18 Johnson Controls Unitary Products P(C,V)9*C20 FC/MC/PC48D 1.01 1.01 1.02 P(C,V)9*C20 UC48D 1.01 1.01 1.02 P(C,V)9*D20 FC/MC/PC48D 1.01 1.01 1.01 P(C,V)9*D20 UC48D 1.01 1.01 1.01 PV8*C20 FC/MC62D 1.01 1.01 1.01 P(C,V)9*C20 FC/MC62D 1.01 1.01 1.02 P(C,V)9*D20 FC/MC62D 1.01 1.01 1.02 PV8*C16 HC42C 0.96 0.96 0.99 PV8*C20 HC42C 1.00 ...

  • York CZH024 THRU 060 - page 19

    350154-YTG -C-0808 Johnson Controls Unitary Products 19 Multipliers for determining the pe rformance with other indoor sect ions. NOTE: For dry bulb temperatures dif ferent than those listed ( bet ween 73-87 F), sensible capacity incr eases by 10 60 BTUH per 100 0 CFM per degree above the listed temperature and decrease s by 1060 BTUH per 1000 CFM ...

  • York CZH024 THRU 060 - page 20

    350154-YTG-C-0808 20 Johnson Controls Unitary Products P(C,V)9*C20 FC/MC/PC48D 0.99 0.99 1.03 P(C,V)9*C20 UC48D 0.99 0.99 1.03 P(C,V)9*D20 FC/MC/PC48D 0.99 0.99 1.02 P(C,V)9*D20 UC48D 0.99 0.99 1.02 PV8*C20 FC/MC62D 1.00 1.00 1.04 P(C,V)9*C20 FC/MC62D 1.00 1.00 1.03 P(C,V)9*D20 FC/MC62D 1.01 1.00 1.02 PV8*C16 HC42C 0.99 0.99 1.02 PV8*C20 HC42C 0.98 ...

  • York CZH024 THRU 060 - page 21

    350154-YTG -C-0808 Johnson Controls Unitary Products 21 Multipliers for determining the pe rformance with other indoor sect ions. NOTE: For dry bulb temperatures dif ferent than those listed ( bet ween 73-87 F), sensible capacity incr eases by 10 60 BTUH per 100 0 CFM per degree above the listed temperature and decrease s by 1060 BTUH per 1000 CFM ...

  • York CZH024 THRU 060 - page 22

    350154-YTG-C-0808 22 Johnson Controls Unitary Products Va r i a b l e S p e e d Furnace Coil T .C. S.C. KW PV8*C16 FC/MC/PC48C 0.97 0.97 0.98 PV8*C16 FC/MC/PC48D 0.97 0.97 0.98 PV8*C16 UC48D 0.97 0.97 0.98 PV8*C20 FC/MC/PC48C 1.00 1.00 0.99 PV8*C20 FC/MC/PC48D 1.00 1.00 0.99 PV8*C20 UC48D 1.00 1.00 0.99 P(C,V)9*C16 FC/MC/PC48C 1.01 1.02 0.98 P(C,V) ...

  • York CZH024 THRU 060 - page 23

    350154-YTG -C-0808 Johnson Controls Unitary Products 23 Multipliers for determining the pe rformance with other indoor sect ions NOTE: For dry bulb temperatures dif ferent than those listed ( bet ween 73-87 F), sensible capacity incr eases by 10 60 BTUH per 100 0 CFM per degree above the listed temperature and decrease s by 1060 BTUH per 1000 CFM p ...

  • York CZH024 THRU 060 - page 24

    350154-YTG-C-0808 24 Johnson Controls Unitary Products Va r i a b l e S p e e d Furnace Coil T .C. S.C. KW PV8*C16 FC/MC/PC48C 0.97 0.97 1.01 PV8*C16 FC/MC/PC48D 0.97 0.97 1.01 PV8*C16 UC48D 0.97 0.97 1.01 PV8*C20 FC/MC/PC48C 0.98 0.98 1.02 PV8*C20 FC/MC/PC48D 0.98 0.98 1.02 PV8*C20 UC48D 0.98 0.98 1.02 P(C,V)9*C16 FC/MC/PC48C 0.98 0.98 1.03 P(C,V) ...

  • York CZH024 THRU 060 - page 25

    350154-YTG -C-0808 Johnson Controls Unitary Products 25 Multipliers for determining the pe rformance with other indoor sect ions. NOTE: For dry bulb temperatures dif ferent than those listed ( bet ween 73-87 F), sensible capacity incr eases by 10 60 BTUH per 100 0 CFM per degree above the listed temperature and decrease s by 1060 BTUH per 1000 CFM ...

  • York CZH024 THRU 060 - page 26

    Subject to change without notice. Printe d in U.S.A. 350154-YTG-C-0808 Copyright © 2008 by Johnson Controls, Inc. All ri ghts reserved. Supersedes: 350154-YTG-B-0408 Johnson Controls Unit ary Produ cts 5005 Y ork Drive Norman, OK 73069 Multipliers for determining th e performance with other indoor sections. NOTE: For dry bulb temperatures dif fere ...

Fabricant York Catégorie Air Conditioner

Les documents que nous recevons du fabricant de l'appareilYork CZH024 THRU 060 peuvent être divisés en plusieurs groupes. Ceux-ci sont, entre autres:
- dessins techniques York
- manuels d’utilisations CZH024 THRU 060
- fiches produit York
- dépliants
- ou étiquettes-énergie York CZH024 THRU 060
Tous sont importants, mais les informations les plus importantes du point de vue de l'utilisation de l'appareil se trouvent dans le manuel d’utilisation York CZH024 THRU 060.

Un groupe de documents appelé manuels d’utilisation est également divisé en types plus spécifiques, tels que: Manuels d’installation York CZH024 THRU 060, manuels d’entretien, brefs manuels ou manuels de l’utilisateur York CZH024 THRU 060. Selon vos besoins, vous devriez chercher le document dont vous avez besoin. Sur notre site, vous pouvez voir le manuel le plus populaire d’utilisation du produit York CZH024 THRU 060.

Manuels d’utilsiation similaires

Manuel d’utilisation complet de l’appareil York CZH024 THRU 060, quelle devrait-elle être?
Le manuel d’utilisation, également appelé le mode d’emploi, ou tout simplement le manuel, est un document technique destiné à aider à utiliser York CZH024 THRU 060 par les utilisateurs. Des manuels sont généralement écrits par un rédacteur technique, mais dans un langage accessible à tous les utilisateurs York CZH024 THRU 060.

Le manuel d’utilisation complet York, devrait inclure plusieurs éléments de base. Certains d'entre eux sont moins importants, tels que: la couverture / page de titre ou pages d'auteur. Cependant, la partie restante, devrait nous fournir des informations importantes du point de vue de l'utilisateur.

1. Introduction et des conseils sur la façon d'utiliser le manuel York CZH024 THRU 060 - Au début de chaque manuel, nous devrions trouver des indices sur la façon d'utiliser le document. Il doit contenir des informations sur l'emplacement de la table des matières York CZH024 THRU 060, FAQ ou des problèmes les plus fréquents - les points qui sont les plus souvent recherchés par les utilisateurs de chaque manuel
2. Table des matières - index de tous les conseils pour lYork CZH024 THRU 060 qui peuvent être trouvés dans le document courant
3. Conseils sur la façon d'utiliser les fonctions de base de l’appareil York CZH024 THRU 060 - qui devraient nous aider dans les premières étapes lors de l'utilisation York CZH024 THRU 060
4. Troubleshooting - séquence systématique des activités qui nous aideront à diagnostiquer et ensuite résoudre les principaux problèmes de York CZH024 THRU 060
5. FAQ - questions fréquemment posées
6. Détails du contact Informations sur l'endroit où chercher le contact avec le fabricant / service York CZH024 THRU 060 dans un pays donné, si le problème ne peut être résolu par nous-mêmes.

Avez-vous une question à propos de York CZH024 THRU 060?

Utiliser le formulaire ci-dessous

Si vous n’avez pas résolu votre problème avec York CZH024 THRU 060, avec l'aide du manuel que vous avez trouvé, posez une question en utilisant le formulaire ci-dessous. Si un utilisateur a eu un problème similaire avec York CZH024 THRU 060 il est probable qu’il a envie de partager la façon de le résoudre.

Réécrire le texte de l'image

Commentaires (0)