Bedienungsanleitung Emerson Process Management 1F95-1291

16 Seiten 1.04 mb
Download

Zur Seite of 16

Summary
  • Emerson Process Management 1F95-1291 - page 1

    Model Programming Choices 1F95-1291 7 Day 5+1+1 Day Non-Programmab le www .white-rodgers .com www .emersonclimate .com Big Blue Humidity Univ er sal T her mostat with Humidity/Dehumidity Control and Automa tic Heat/Cool Changeo v er Option P ART NO . 37-7313B Replaces 37-7313A 1241 Single Stage, Multi-Stage, Heat Pump Installation and Operating Ins ...

  • Emerson Process Management 1F95-1291 - page 2

    2 Remove Old Thermostat Bef ore removing wires from old thermostat, mar k wires f or terminal identification so the proper connections will be made to the new thermostat. Installing New Thermostat 1. Pull the thermostat body off the ther mostat base. Forcing or pr ying on the thermostat will cause damage to the unit. 2. Place base ov er hole in wa ...

  • Emerson Process Management 1F95-1291 - page 3

    3 WIRING DIA GRAMS Figure 2 – Single Stage or Multi-Stage System (No Heat Pump) with Single T ransformer Single Stage 1 (SS1) Multi Stage 2 (MS2) System RC RH CY Y2 W/E W2 G O/B 6L CLASS II TRANSFORMER HO T 24V AC NEUTRAL 120V AC Call for heat Heat mode-1st stage Heat mode-2nd stage No output 24 vo lt po wer f or cooling 24 vo lt po wer f or heat ...

  • Emerson Process Management 1F95-1291 - page 4

    4 If you ha v e a single stage compressor system see the dia- gram belo w . A relay (customer provided) should be installed as shown in Fig 7 to s witch the fan speed to the ne xt lower speed on a call f or dehumidification from the ther mostat. The reduction in air flow allo ws the coil to remov e more humidity from the air . The rela y should b ...

  • Emerson Process Management 1F95-1291 - page 5

    5 Programming and Configuration Items 1 Displa ys and "Keypad Loc kout" when in ke ypad lock out mode. Displa ys and "T emperature Limit" and "Keypad Lock out" when limited range is activ ated and lock ed. Displa ys only "T emperature Limit" when limited range is activated. 2 Indicates per iod of da y being ...

  • Emerson Process Management 1F95-1291 - page 6

    6 INST ALLER/CONFIGURA TION MENU T o enter the menu: Press the Menu touch k ey . Press and hold f or 5 seconds the Installer Config touch ke y . This displays screen ref erence #1 in the table belo w . Screen Reference numbers appear in top right corner of display . Press to advance to the ne xt menu item or to return to a previous men u item. Pre ...

  • Emerson Process Management 1F95-1291 - page 7

    7 INST ALLER/CONFIGURA TION MENU 1. This control can be configured for: MS2 – Multi-Stage System (2 heat/2 cool) HP1 – Heat Pump with one stage of compressor (2 heat/1 cool) HP2 – Heat Pump with two stage compressor or two compressor system, Gas or Electric backup; (Dual Fuel see screen ref erence number 33) (4 heat/2 cool) SS1 – Single St ...

  • Emerson Process Management 1F95-1291 - page 8

    8 a time dela y built in and do not require this f eature to be activated in the thermostat. Y our compressor manuf actur- er can tell you if this loc kout f eature is already present in their system. When the ther mostat compressor time dela y is activated, it will flash the set point f or up to five minutes . 12. Select Continuous Displa y Ligh ...

  • Emerson Process Management 1F95-1291 - page 9

    9 Skip this step and continue through the remainder of the configuration menu if y ou require an Air Filter Change out indicator or Humidifier P ad Change out indicator by pressing the key to adv ance. Return to this point when you are ready to star t your selected lock-out and contin ue by: Pressing or k eys to select y our ke ypad lock out comb ...

  • Emerson Process Management 1F95-1291 - page 10

    10 “HM” terminal) if the actual humidity is below the humid- ity set point. The display indicates AH . Pressing the ke y will cycle the displa y from OFF to H (f eature enabled in Heat mode) to C (f eature enabled in Cool mode) to A (f eature enabled to A uto mode) and back to OFF . 42. Cycle Humidifier (CH) – This f eature provides an op- t ...

  • Emerson Process Management 1F95-1291 - page 11

    11 Emergency Mode Applies only to Heat Pump Systems Emergency Heat (System EM P osition) bypasses the Heat Pump to use the heat source wired to terminal W/E, W2 on the thermostat. EM is typically used when compressor opera- tion is not desired, or you pref er back-up heat only . 1. Press SYSTEM key to select EM . “EM Heat Mode” will flash on t ...

  • Emerson Process Management 1F95-1291 - page 12

    12 PR OGRAMMING Set Current Time and Day 1. Press Menu ke y to enter installer menu. Then press Set Time once to indicate hour & AM or PM designation in clock displa y . 2. Press and hold either the or touch k ey until y ou reach the correct hour and AM or PM designation. 3. Press Set Time again to displa y minutes only in clock displa y . 4. P ...

  • Emerson Process Management 1F95-1291 - page 13

    13 PR OGRAMMING Planning Y our Program – Important The Heating and Cooling Program schedules belo w allow y ou to pencil in your o wn program times and temper atures. The 1F95-1291 comes configured f or 7 day prog ramming and can also be configured f or 5+1+1 programming (see configur a- tion section). F actor y settings are listed on Monday , ...

  • Emerson Process Management 1F95-1291 - page 14

    14 PR OGRAMMING Cooling Program W ake Up (Morning) Fan Leave For W ork (Day) Fan Return Home (Evening) Fan Go T o Bed (Night) Fan MON 6:00 AM 75°F A uto 8:00 AM 83°F A uto 5:00 PM 75°F Auto 10:00 PM 78°F A uto TUE WED THU FRI S AT 6:00 AM 75°F A uto 8:00 AM 83°F A uto 5:00 PM 75°F Auto 10:00 PM 78°F A uto SUN 6:00 AM 75°F A uto 8:00 AM 83? ...

  • Emerson Process Management 1F95-1291 - page 15

    15 PR OGRAMMING TR OUBLESHOO TING A veraging or Weighting Remote Sensor s The thermostat will weight or av erage the temperature of the indoor remote sensor with the local sensor in the thermostat f or each program period. The av eraging will be active only when the local sensor and the indoor remote sensor are both functional and enabled in the In ...

  • Emerson Process Management 1F95-1291 - page 16

    White-Rodgers is a business of Emerson Electric Co. The Emerson logo is a trademark and ser vice mark of Emerson Electric Co. HOMEO WNER HELP LINE: 1-800-284-2925 Symptom P ossible Cause Corrective Action No Heat/No Cool/No Fan (common problems) 1. Blown fuse or tripped circuit breaker . 2. Fur nace power s witch to OFF . 3. Fur nace blo wer compar ...

Produzent Emerson Process Management Kategorie Thermostat

Dokumente, die wir vom Produzenten des Geräts Emerson Process Management 1F95-1291 erhalten, können wir in mehrere Gruppen teilen. Unteranderem in:
- technische Zeichnungen Emerson Process Management
- Bedienungsanleitungen 1F95-1291
- Produktkarten Emerson Process Management
- Informationsbroschüren
- oder Energieetiketten Emerson Process Management 1F95-1291
Jede von ihnen ist wichtig, jedoch finden wir die wichtigsten Informationen für den Nutzer des Geräts in der Bedienungsanleitung Emerson Process Management 1F95-1291.

Die Dokumentengruppe, die als Bedienungsanleitungen bezeichnet wird, wird ebenfalls in detaillierte Arten geteilt, solche wie: Montageanleitungen Emerson Process Management 1F95-1291, Wartungsanleitungen, Kurzanleitungen oder Benutzeranleitungen Emerson Process Management 1F95-1291. Abhängig vom Bedarf, sollten Sie das Dokument finden, das Sie brauchen. In unserem Service können Sie sich die populärste Bedienungsanleitung des Produkts Emerson Process Management 1F95-1291 ansehen.

Die komplette Bedienungsanleitung des Geräts Emerson Process Management 1F95-1291, wie sollte sie aussehen?
Die Bedienungsanleitung, auch bezeichnet als Benutzerhandbuch, oder einfach nur „Anleitung”, ist ein technisches Dokument, das dem Benutzer bei der Nutzung von Emerson Process Management 1F95-1291 hilfreich sein soll. Die Bedienungsanleitungen werden in der Regel von technischen Schriftstellern geschrieben, aber in einer Sprache, die für alle Nutzer von Emerson Process Management 1F95-1291 verständlich ist.

Eine gänzliche Bedienungsanleitung von Emerson Process Management sollte einige Grundelemente enthalten. Ein Teil von ihnen ist nicht so wichtig, wie z.B.: die Titelseite oder Autorenseiten. Die restlichen von ihnen jedoch, sollten Informationen liefern, die für den Nutzer von enormer Wichtigkeit sind.

1. Einführung und Hinweise, wie man sich in einer Bedienungsanleitung von Emerson Process Management 1F95-1291 bewegt - Am Anfang jeder Bedienungsanleitung sollten wir Hinweise bezüglich der Nutzungsart eines bestimmten Ratgebers finden. In ihr sollten sich Informationen über die Lokalisierung des Inhaltsverzeichnisses von Emerson Process Management 1F95-1291 befinden, FAQ oder über oft auftretende Probleme – also Stellen, die von den Benutzern in jeder Bedienungsanleitung am meisten gesucht werden
2. Inhaltsverzeichnis - Index aller Ratschläge bezüglich Emerson Process Management 1F95-1291, die wir im aktuellen Dokument finden
3. Ratschläge zur Nutzung der Grundfunktionen des Geräts Emerson Process Management 1F95-1291 - die uns die ersten Schritte während der Nutzung von Emerson Process Management 1F95-1291 erleichtern sollten
4. Troubleshooting - geordneter Tätigkeitslauf, der uns bei der Diagnose und als nächstes bei der Lösung wichtiger Probleme mit Emerson Process Management 1F95-1291 hilft
5. FAQ - häufig gestellte Fragen
6. Kontaktdaten Informationen darüber, wo man Kontakt zum Produzenten / Service von Emerson Process Management 1F95-1291 im bestimmten Land suchen kann, wenn es nicht gelingt, das Problem selbst zu lösen.

Haben Sie eine Frage bezüglich Emerson Process Management 1F95-1291?

Nutzen Sie das untere Formular

Wenn Sie mit Hilfe der gefundenen Bedienungsanleitung Ihr Problem mit Emerson Process Management 1F95-1291 nicht gelöst haben, stellen Sie eine Frage, indem Sie das untere Formular nutzen. Wenn einer der Nutzer ein ähnliches Problem mit Emerson Process Management 1F95-1291 hatte, ist es möglich, dass er mit Ihnen die Lösung teilen möchte.

Text vom Bild übertragen

Kommentare (0)