    Model Programming Choices 1F95-1291 7 Day 5+1+1 Day Non-Programmab le www .white-rodgers .com www .emersonclimate .com Big Blue Humidity Univ er sal T her mostat with Humidity/Dehumidity Control and Automa tic Heat/Cool Changeo v er Option P ART NO . 37-7313B Replaces 37-7313A 1241 Single Stage, Multi-Stage, Heat Pump Installation and Operating Ins ...

  • Emerson Process Management 1F95-1291 - page 2

    2 Remove Old Thermostat Bef ore removing wires from old thermostat, mar k wires f or terminal identification so the proper connections will be made to the new thermostat. Installing New Thermostat 1. Pull the thermostat body off the ther mostat base. Forcing or pr ying on the thermostat will cause damage to the unit. 2. Place base ov er hole in wa ...

  • Emerson Process Management 1F95-1291 - page 3

    3 WIRING DIA GRAMS Figure 2 – Single Stage or Multi-Stage System (No Heat Pump) with Single T ransformer Single Stage 1 (SS1) Multi Stage 2 (MS2) System RC RH CY Y2 W/E W2 G O/B 6L CLASS II TRANSFORMER HO T 24V AC NEUTRAL 120V AC Call for heat Heat mode-1st stage Heat mode-2nd stage No output 24 vo lt po wer f or cooling 24 vo lt po wer f or heat ...

  • Emerson Process Management 1F95-1291 - page 4

    4 If you ha v e a single stage compressor system see the dia- gram belo w . A relay (customer provided) should be installed as shown in Fig 7 to s witch the fan speed to the ne xt lower speed on a call f or dehumidification from the ther mostat. The reduction in air flow allo ws the coil to remov e more humidity from the air . The rela y should b ...

  • Emerson Process Management 1F95-1291 - page 5

    5 Programming and Configuration Items 1 Displa ys and "Keypad Loc kout" when in ke ypad lock out mode. Displa ys and "T emperature Limit" and "Keypad Lock out" when limited range is activ ated and lock ed. Displa ys only "T emperature Limit" when limited range is activated. 2 Indicates per iod of da y being ...

  • Emerson Process Management 1F95-1291 - page 6

    6 INST ALLER/CONFIGURA TION MENU T o enter the menu: Press the Menu touch k ey . Press and hold f or 5 seconds the Installer Config touch ke y . This displays screen ref erence #1 in the table belo w . Screen Reference numbers appear in top right corner of display . Press to advance to the ne xt menu item or to return to a previous men u item. Pre ...

  • Emerson Process Management 1F95-1291 - page 7

    7 INST ALLER/CONFIGURA TION MENU 1. This control can be configured for: MS2 – Multi-Stage System (2 heat/2 cool) HP1 – Heat Pump with one stage of compressor (2 heat/1 cool) HP2 – Heat Pump with two stage compressor or two compressor system, Gas or Electric backup; (Dual Fuel see screen ref erence number 33) (4 heat/2 cool) SS1 – Single St ...

  • Emerson Process Management 1F95-1291 - page 8

    8 a time dela y built in and do not require this f eature to be activated in the thermostat. Y our compressor manuf actur- er can tell you if this loc kout f eature is already present in their system. When the ther mostat compressor time dela y is activated, it will flash the set point f or up to five minutes . 12. Select Continuous Displa y Ligh ...

  • Emerson Process Management 1F95-1291 - page 9

    9 Skip this step and continue through the remainder of the configuration menu if y ou require an Air Filter Change out indicator or Humidifier P ad Change out indicator by pressing the key to adv ance. Return to this point when you are ready to star t your selected lock-out and contin ue by: Pressing or k eys to select y our ke ypad lock out comb ...

  • Emerson Process Management 1F95-1291 - page 10

    10 “HM” terminal) if the actual humidity is below the humid- ity set point. The display indicates AH . Pressing the ke y will cycle the displa y from OFF to H (f eature enabled in Heat mode) to C (f eature enabled in Cool mode) to A (f eature enabled to A uto mode) and back to OFF . 42. Cycle Humidifier (CH) – This f eature provides an op- t ...

  • Emerson Process Management 1F95-1291 - page 11

    11 Emergency Mode Applies only to Heat Pump Systems Emergency Heat (System EM P osition) bypasses the Heat Pump to use the heat source wired to terminal W/E, W2 on the thermostat. EM is typically used when compressor opera- tion is not desired, or you pref er back-up heat only . 1. Press SYSTEM key to select EM . “EM Heat Mode” will flash on t ...

  • Emerson Process Management 1F95-1291 - page 12

    12 PR OGRAMMING Set Current Time and Day 1. Press Menu ke y to enter installer menu. Then press Set Time once to indicate hour & AM or PM designation in clock displa y . 2. Press and hold either the or touch k ey until y ou reach the correct hour and AM or PM designation. 3. Press Set Time again to displa y minutes only in clock displa y . 4. P ...

  • Emerson Process Management 1F95-1291 - page 13

    13 PR OGRAMMING Planning Y our Program – Important The Heating and Cooling Program schedules belo w allow y ou to pencil in your o wn program times and temper atures. The 1F95-1291 comes configured f or 7 day prog ramming and can also be configured f or 5+1+1 programming (see configur a- tion section). F actor y settings are listed on Monday , ...

  • Emerson Process Management 1F95-1291 - page 14

    14 PR OGRAMMING Cooling Program W ake Up (Morning) Fan Leave For W ork (Day) Fan Return Home (Evening) Fan Go T o Bed (Night) Fan MON 6:00 AM 75°F A uto 8:00 AM 83°F A uto 5:00 PM 75°F Auto 10:00 PM 78°F A uto TUE WED THU FRI S AT 6:00 AM 75°F A uto 8:00 AM 83°F A uto 5:00 PM 75°F Auto 10:00 PM 78°F A uto SUN 6:00 AM 75°F A uto 8:00 AM 83? ...

  • Emerson Process Management 1F95-1291 - page 15

    15 PR OGRAMMING TR OUBLESHOO TING A veraging or Weighting Remote Sensor s The thermostat will weight or av erage the temperature of the indoor remote sensor with the local sensor in the thermostat f or each program period. The av eraging will be active only when the local sensor and the indoor remote sensor are both functional and enabled in the In ...

  • Emerson Process Management 1F95-1291 - page 16

    White-Rodgers is a business of Emerson Electric Co. The Emerson logo is a trademark and ser vice mark of Emerson Electric Co. HOMEO WNER HELP LINE: 1-800-284-2925 Symptom P ossible Cause Corrective Action No Heat/No Cool/No Fan (common problems) 1. Blown fuse or tripped circuit breaker . 2. Fur nace power s witch to OFF . 3. Fur nace blo wer compar ...

Fabricant Emerson Process Management Catégorie Thermostat

Les documents que nous recevons du fabricant de l'appareilEmerson Process Management 1F95-1291 peuvent être divisés en plusieurs groupes. Ceux-ci sont, entre autres:
- dessins techniques Emerson Process Management
- manuels d’utilisations 1F95-1291
- fiches produit Emerson Process Management
- dépliants
- ou étiquettes-énergie Emerson Process Management 1F95-1291
Tous sont importants, mais les informations les plus importantes du point de vue de l'utilisation de l'appareil se trouvent dans le manuel d’utilisation Emerson Process Management 1F95-1291.

Un groupe de documents appelé manuels d’utilisation est également divisé en types plus spécifiques, tels que: Manuels d’installation Emerson Process Management 1F95-1291, manuels d’entretien, brefs manuels ou manuels de l’utilisateur Emerson Process Management 1F95-1291. Selon vos besoins, vous devriez chercher le document dont vous avez besoin. Sur notre site, vous pouvez voir le manuel le plus populaire d’utilisation du produit Emerson Process Management 1F95-1291.

Manuel d’utilisation complet de l’appareil Emerson Process Management 1F95-1291, quelle devrait-elle être?
Le manuel d’utilisation, également appelé le mode d’emploi, ou tout simplement le manuel, est un document technique destiné à aider à utiliser Emerson Process Management 1F95-1291 par les utilisateurs. Des manuels sont généralement écrits par un rédacteur technique, mais dans un langage accessible à tous les utilisateurs Emerson Process Management 1F95-1291.

Le manuel d’utilisation complet Emerson Process Management, devrait inclure plusieurs éléments de base. Certains d'entre eux sont moins importants, tels que: la couverture / page de titre ou pages d'auteur. Cependant, la partie restante, devrait nous fournir des informations importantes du point de vue de l'utilisateur.

1. Introduction et des conseils sur la façon d'utiliser le manuel Emerson Process Management 1F95-1291 - Au début de chaque manuel, nous devrions trouver des indices sur la façon d'utiliser le document. Il doit contenir des informations sur l'emplacement de la table des matières Emerson Process Management 1F95-1291, FAQ ou des problèmes les plus fréquents - les points qui sont les plus souvent recherchés par les utilisateurs de chaque manuel
2. Table des matières - index de tous les conseils pour lEmerson Process Management 1F95-1291 qui peuvent être trouvés dans le document courant
3. Conseils sur la façon d'utiliser les fonctions de base de l’appareil Emerson Process Management 1F95-1291 - qui devraient nous aider dans les premières étapes lors de l'utilisation Emerson Process Management 1F95-1291
4. Troubleshooting - séquence systématique des activités qui nous aideront à diagnostiquer et ensuite résoudre les principaux problèmes de Emerson Process Management 1F95-1291
5. FAQ - questions fréquemment posées
6. Détails du contact Informations sur l'endroit où chercher le contact avec le fabricant / service Emerson Process Management 1F95-1291 dans un pays donné, si le problème ne peut être résolu par nous-mêmes.

Avez-vous une question à propos de Emerson Process Management 1F95-1291?

Utiliser le formulaire ci-dessous

Si vous n’avez pas résolu votre problème avec Emerson Process Management 1F95-1291, avec l'aide du manuel que vous avez trouvé, posez une question en utilisant le formulaire ci-dessous. Si un utilisateur a eu un problème similaire avec Emerson Process Management 1F95-1291 il est probable qu’il a envie de partager la façon de le résoudre.

Réécrire le texte de l'image

Commentaires (0)