    Affix this manual and Users Information Manual adjacent to the unit. INST ALLA TION & OPERA TING INSTRUCTIONS for A/GPG13 M SERIES W/R410A SINGLE P ACKAGE GAS-ELECTRIC HEA TING & COOLING UNIT C US ® Goodman Manufacturing Company , L.P . IO-357A 5151 San Felipe, Suite 500, Houston, TX 77056 3/10 www .goodmanmfg.com © 2009 - 2010 Goodman Ma ...

  • Goodman Mfg A/GPG13 M - page 2

    2 Index Replacement Parts ...................................................................................................................................................................... 3 O RDERING P ARTS .......................................................................................................................................... ...

  • Goodman Mfg A/GPG13 M - page 3

    3 REPLACEMENT PAR TS O RDERING P ARTS When reporting shortages or damages, or ordering repair parts, give the complete unit model and serial numbers as stamped on the unit’s nameplate. Replacement part s for this appliance are available through your contractor or local distributor . For the location of your nearest distributor , consult the white ...

  • Goodman Mfg A/GPG13 M - page 4

    4 WARNIN G T O PREVE N T THE RISK O F PROPERTY DAMAGE, P ERSONAL INJUR Y , O R DE ATH, DO NOT STORE COMB USTIBLE MATERIALS OR USE GASOLI NE OR OTHER FLAM MABLE LIQ U I DS OR VAPO RS I N TH E VICIN ITY OF TH IS A PPLI ANC E. CA RBON M ONOXIDE POISON ING HA ZA RD B10259-216 Carbo n monox ide produc ing devi ces (s uch as an aut omobil e, spac e heate ...

  • Goodman Mfg A/GPG13 M - page 5

    5 Outside Slab Installation R OOFTOP I NSTALLATIONS O NLY : NOTE: To ensure proper condensate drainage, unit must be installed in a level position. • T o avoid possible property damage or personal injury , the roof must have sufficient structural strength to carry the weight of the unit(s) and snow or water loads as required by local codes. Consu ...

  • Goodman Mfg A/GPG13 M - page 6

    6 The heating and cooling capacities of the unit should be greater than or equal to the design heating and cooling loads of the area to be conditioned. The loads should be calculated by an approved method or in accordance with A.S.H.R.A.E. Guide or Manual J - Load Calculations published by the Air Conditioning Contractors of America. Obtain from: A ...

  • Goodman Mfg A/GPG13 M - page 7

    7 P IPING IMPORT ANT NOTE: T o avoid possible unsatisfactory operation or equipment damage due to under firing of equipment, do not un- dersize the natural/propane gas piping from the meter/tank to the unit. When sizing a trunk line, include all appliances on that line that could be operated simultaneously . The rating plate is stamped with the mod ...

  • Goodman Mfg A/GPG13 M - page 8

    8 Sizing Between Fi rst and Second S tage Regulator Maximum Prop ane Capacities listed a re based on 1 P SIG Pressure Drop at 10 PSIG Settin g. Capacities in 1,000 BT U/HR 3/8" 1/2" 5/ 8" 3/4" 7/8" 1/2" 3/4" 30 309 700 1,303 2, 205 3,394 1,843 3,854 40 265 599 1,115 1, 887 2,904 1,577 3,298 50 235 531 988 1,672 2, ...

  • Goodman Mfg A/GPG13 M - page 9

    9 CAUTION T O PREVENT IMPROPE R A ND DANGEROUS OPERAT I ON DUE TO WIRING ERRORS, LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICI NG CONTROLS. V ERI FY PROPER OPERATION AFTER SERVICI NG. For unit protection, use a time delay fuse or HACR circuit breaker that is in excess of the circuit ampacity , but less than or equal to the maximum overcurrent ...

  • Goodman Mfg A/GPG13 M - page 10

    10 G Y W R R W Y G Fr o m Unit Typical Thermostat and Unit 24 V Wiring Hookup CIRCULA TING AIR AND FIL TERS A IRFLOW C ONVERSION Units can easily be converted from horizontal to down- discharge airflow delivery . In down-discharge or high static installations, the installer should measure the total external static and review the blower performance ...

  • Goodman Mfg A/GPG13 M - page 11

    11 VENTING NOTE: V enting is self-contained. Do not modify or block. F LUE H OOD I NSTALLATION Install the exhaust flue hood and combustion air intake hood prior to operation of the unit. T o install the flue hood cover , please refer to IO-653*, included in the flue hood assembly box located in the blower compartment. Flue Hood and Bug Screen Inst ...

  • Goodman Mfg A/GPG13 M - page 12

    12 WARNING T O AVOI D P ROPERTY DAMAGE, PERSONAL INJURY OR DEATH DUE TO FIRE OR EXPLOSION, A QUALIFIED SERVICER MUST INVESTIG ATE THE RE ASON FOR THE R OLLOUT PROTECTION DEVICE TO OP E N BEFORE MANUALLY RE S E TTING THE R OLLOUT PROTECTION DEVICE . Rol lou t Pro t ect ion Rollout Protection on Burner Bracket Secondary Limit Control The secondary li ...

  • Goodman Mfg A/GPG13 M - page 13

    13 8. Measure the gas supply pressure with burners firing. Adjust supply pressure using the Inlet Gas Supply Pressure table shown below . If supply pressure reading differs from the table, make necessary adjustments to pressure regulator , gas piping size, etc., and/or consult with local gas utility . Propane Gas Natural Gas Inlet Gas Supply Pressu ...

  • Goodman Mfg A/GPG13 M - page 14

    14 6. Turn ON power and close thermostat “R” and “W” contacts to provide a call for heat. 7. Using a leak detection solution or soap suds, check for leaks at outlet pressure boss plug (Honeywell valve) or screw (White-Rodgers valve). Bubbles forming indicate a leak. SHUT OFF GAS AND REP AIR ALL LEAKS IMMEDIA TEL Y! 8. Measure the gas manifo ...

  • Goodman Mfg A/GPG13 M - page 15

    15 Adjust the thermostat setting below room temperature. 1. Main burners must go OFF . 2. Circulating Air Blower will continue to run for 120, 135 or 150 seconds, depending on the setting. 1 2 3 10 11 12 9 6 23 6 5 8 9 11 12 L2 L2 L2 L2 D1 L1 L1 UNUSED HEAT COOL FS K2 K1 R8 R10 R3 K4 K3 R31 LE D 1 0 6 8 - 8 3 - 4 0 0 A C27 D3 R38 D9 D10 R34 R3 5 R4 ...

  • Goodman Mfg A/GPG13 M - page 16

    16 The diagnostic fault code is 1 flash for a lockout due to failed ignition attempts or flame dropouts. The integrated control will automatically reset after one hour , or it can be reset by removing the thermostat signal or disconnecting the electrical power supply for over five seconds. If the diagnostic LED indicates an external lockout, perfor ...

  • Goodman Mfg A/GPG13 M - page 17

    17 C ABINET F INISH M AINTENANCE Use a fine grade automotive wax on the cabinet finish to maintain the finish’ s original high luster . This is especially important in installations with extended periods of direct sunlight. C LEAN O UTSIDE C OIL ( Q UALIFIED S ERVICER O NLY ) The coil with the outside air flowing over it should be inspected annua ...

  • Goodman Mfg A/GPG13 M - page 18

    18 5 . Replace burners and manifold, inspect the burner assembly for proper seating of burners in retention slots. 6. Reconnect electrical power and gas supply . CAUTION L ABEL ALL W IRES PRIO R TO DISC ONNECTION WHEN SERVICING CONTROLS. W IRING ERRORS CAN CAUSE I MPROPER AND DANGEROUS OPERA TION. CAUTION A LWAYS V ERIFY PROP ER OPERATIO N AFTER S ...

  • Goodman Mfg A/GPG13 M - page 19

    19 Un it Stati c CFM W ATT S AM PS RISE C F M W AT TS AMPS RI SE C F M W ATT S AMPS R ISE 0. 1 1 , 056 350 1 . 5 1 33 1, 26 1 4 52 1.95 NR 1 ,3 70 509 2 . 2 3 NR 0. 2 1 , 010 339 1 . 4 3 34 1, 22 1 4 42 1.90 NR 1 ,3 10 492 2 . 1 3 NR 0. 3 971 343 1 . 4 5 36 1, 17 4 4 28 1. 84 NR 1 ,2 62 489 2 . 0 9 NR 0. 4 937 329 1 .4 1 37 1, 12 5 4 14 1. 80 31 1, ...

  • Goodman Mfg A/GPG13 M - page 20

    20 BLOWER PERFORMANCE DA T A - SINGLE PHASE NR = Heating T emperature Rise Not Recommended. NOTE: The shaded area indicates ranges in excess of maximum external static pressure allowable when heating. For satisfactory operation, external static pressure should not exceed 0.5" w .c. Un it St ati c CFM W ATTS AMPS RISE CFM W ATTS AMPS R I SE CFM ...

  • Goodman Mfg A/GPG13 M - page 21

    21 Un it St ati c CFM W ATTS AMPS R I SE C F M W AT T S AMPS R I SE CF M W ATT S AMPS RISE 0 . 1 ------ -- -------- ------ -- -------- -------- -------- - ------- --- ----- --- --- -- -------- -------- ----- --- 0. 2 914 125 1 . 0 7 56 1, 10 5 1 86 1. 56 46 1 ,3 97 323 2 . 5 7 NR 0. 3 822 134 1 . 1 4 62 1, 02 4 1 93 1. 60 50 1 ,3 46 331 2 . 6 7 NR ...

  • Goodman Mfg A/GPG13 M - page 22

    22 NR = Heating T emperature Rise Not Recommended. NOTE: The shaded area indicates ranges in excess of maximum external static pressure allowable when heating. For satisfactory operation, external static pressure should not exceed 0.5" w .c. BLOWER PERFORMANCE DA T A - SINGLE PHASE Un i t Stati c C F M W ATT S AMPS RISE CFM W AT TS AMPS R I SE ...

  • Goodman Mfg A/GPG13 M - page 23

    23 BLOWER PERFORMANCE DA T A - HEA TING SPEEDS THREE PHASE NR = Heating T emperature Rise Not Recommended. NOTE: The shaded area indicates ranges in excess of maximum external static pressure allowable when heating. For satisfactory operation, external static pressure should not exceed 0.5" w .c. Un it St a ti c C FM W AT T S AMPS R I SE C F M ...

  • Goodman Mfg A/GPG13 M - page 24

    24 NR = Heating T emperature Rise Not Recommended. NOTE: The shaded area indicates ranges in excess of maximum external static pressure allowable when heating. For satisfactory operation, external static pressure should not exceed 0.5" w .c. BLOWER PERFORMANCE DA T A - COOLING SPEEDS THREE PHASE Un it S t at i c CF M W a t t s RP M Amp s C F M ...

  • Goodman Mfg A/GPG13 M - page 25

    25 Light Signal Refer to Abnormal Heating or Cooling Operation Sections of this Manual Off Internal Control Failure 1 Flash External Lockout 2 Flashes Pressure Switch S tuck Open 3 Flashes Pressure Switch S tuck Closed 4 Flashes Thermal Protection Device Open 5 Flashes Flame Detected with Gas V alve Closed 6 Flashes Short Cycle Compressor Delay (Co ...

  • Goodman Mfg A/GPG13 M - page 26

    26 APPENDIX UNIT DIMENSIONS EXHAUST FLUE HO OD CO NTROL W I R E EN TRANC E POWER W IRE ENTRA NC E HEA T EXCHAN GE ACCESS P A N EL B B A FLUE EXHAU ST BLOWER ACCESS PAN EL FLUE EXHAU ST HO OD ...

  • Goodman Mfg A/GPG13 M - page 27

    27 Y NO TE 3 CONNECTED A T L1, L 2 CH OPTI ONAL BL /P K BL / PK HPS 01 40G 01 23 3 RE V . A NOTE 4 PU R VM IGN FS GA S V A LV E BL PU PU NO TE 5 ( A L T . ) HONEYW ELL GV BL W. R. PU GV MV GAS V A L VE MV RS PL PU Y 1 4 G 3 2 5 6 BL Y Y1 Y/Y2 CR PU Y BL R WG G W PU PS Y Y ALS MOT OR 4S P E E D PU B BL CAP BR Y F C H R 10 O R 7 4 1 FS 11 12 89 2 56 ...

  • Goodman Mfg A/GPG13 M - page 28

    28 6. U SE C OPP ER W IR E HP S BL/ PK BLU E/ PIN K HPS HIGH PRESS U RE SW I T CH 1. R EPLA C EMEN T W I RE MU ST BE THE SAM E SIZ E A ND TYPE OF 3B L I N K S 6B L I N K S 2B L I N K S ST A T U S LIG H T 4B L I N K S 5B L I N K S IN SU L A TIO N AS OR IGI N AL.(U SE COP PER CONDUC TOR ON L Y). 3. C R A N KC ASE H EA T ER ( O PT IONA L ). 2. FOR 208 ...

  • Goodman Mfg A/GPG13 M - page 29

    29 *PG13(48,60)1** WIRING DIAGRAM Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring. HIGH VOL T A GE! DISCONNECT ALL POWER BEFORE SERVICING OR INS T A LLING THIS UNIT . MUL T IPLE POW ER SOURCES M A Y BE P RESENT . F A ILURE T O DO SO MA Y CAUS E PROPERTY DAMA GE, PERSONAL INJURY OR DEA TH . ...

  • Goodman Mfg A/GPG13 M - page 30

    30 *PG13(48,60)1** WIRING DIAGRAM Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring. HI GH VO L T AGE! DISC ONNECT AL L POWER BEFORE SERVICING OR INST A LLING THIS UNIT . MUL T IPLE POW ER S OURCES MA Y BE PRESENT . F AI LURE TO DO SO MA Y CAUS E PROPERTY DAMAG E, PERSONAL INJURY OR DEA TH . ...

  • Goodman Mfg A/GPG13 M - page 31

    31 GPG13(36)3** WIRING DIAGRAM HIGH VOL T A GE! DISCONNECT ALL POWER BEFORE SERVICING OR INS T A LLING THIS UNIT . MUL T IPLE POW ER SOURCES M A Y BE PR ESENT . F AI LURE T O DO SO MA Y CAUS E PROP ERTY DAMAGE, PERSO NAL INJUR Y OR DEA TH . Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring. Y ...

  • Goodman Mfg A/GPG13 M - page 32

    32 GPG13(36)3** WIRING DIAGRAM Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring. HIGH VOL T A GE! DISCONNECT ALL POWER BEFORE SERVICING OR INS T A LLING THIS UNIT . MUL T IPLE POW ER SOURCES M A Y BE PR ESENT . F AI LURE T O DO SO MA Y CAUS E PROP ERTY DAMAGE, PERSONAL INJUR Y OR DEA TH . 2 ...

  • Goodman Mfg A/GPG13 M - page 33

    33 GPG13(48,60)3** WIRING DIAGRAM Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring. HIGH VOL T A GE! DISCONNECT ALL POWER BEFORE SERVICING OR INS T A LLING THIS UNIT . MUL T IPLE POW ER SOURCES M A Y BE PR ESENT . F AI LURE T O DO SO MA Y CAUS E PROP ERTY DAMAGE, PERSONAL INJUR Y OR DEA TH . ...

  • Goodman Mfg A/GPG13 M - page 34

    34 GPG13(48,60)3** WIRING DIAGRAM Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring. HIGH VOL T A GE! DISCONNECT ALL POWER BEFORE SERVICING OR INS T A LLING THIS UNIT . MUL T IPLE POW ER SOURCES M A Y BE PR ESENT . F AI LURE T O DO SO MA Y CAUS E PROP ERTY DAMAGE, PERSONAL INJUR Y OR DEA TH . ...

  • Goodman Mfg A/GPG13 M - page 35

    35 RECOMMENDED FIL TER SIZES UNIT 2 Ton 2 1/2 Ton 3 Ton 3 1/2 / 4 Ton 5 Ton Min. Filter Size (1)20 x 20 x 1 (1)20 x 25 x 1 (1)25 x 25 x1 (2)20 x 20 x 1 (2)20 x 25 x 1 MINIMUM CLEARANCES - NOTE: Roof overhang should be no more than 36". 3" MI N 12" MIN 12" MIN 36" MI N (FOR SERVICE ) . 48" MI N ...

  • Goodman Mfg A/GPG13 M - page 36

    36 NOTE: SPECIFICA TIONS AND PERFORMANCE DA T A LISTED HEREIN ARE SUBJECT T O CHANGE WITHOUT NOTICE Quality Makes the Difference! All of our systems are designed and manufactured with the same high quality standards regardless of size or efficiency . We have designed these units to significantly reduce the most frequent causes of product failure. T ...

Produzent Goodman Mfg Kategorie Air Conditioner

Dokumente, die wir vom Produzenten des Geräts Goodman Mfg A/GPG13 M erhalten, können wir in mehrere Gruppen teilen. Unteranderem in:
- technische Zeichnungen Goodman Mfg
- Bedienungsanleitungen A/GPG13 M
- Produktkarten Goodman Mfg
- Informationsbroschüren
- oder Energieetiketten Goodman Mfg A/GPG13 M
Jede von ihnen ist wichtig, jedoch finden wir die wichtigsten Informationen für den Nutzer des Geräts in der Bedienungsanleitung Goodman Mfg A/GPG13 M.

Die Dokumentengruppe, die als Bedienungsanleitungen bezeichnet wird, wird ebenfalls in detaillierte Arten geteilt, solche wie: Montageanleitungen Goodman Mfg A/GPG13 M, Wartungsanleitungen, Kurzanleitungen oder Benutzeranleitungen Goodman Mfg A/GPG13 M. Abhängig vom Bedarf, sollten Sie das Dokument finden, das Sie brauchen. In unserem Service können Sie sich die populärste Bedienungsanleitung des Produkts Goodman Mfg A/GPG13 M ansehen.

Ähnliche Bedienungsanleitungen

Die komplette Bedienungsanleitung des Geräts Goodman Mfg A/GPG13 M, wie sollte sie aussehen?
Die Bedienungsanleitung, auch bezeichnet als Benutzerhandbuch, oder einfach nur „Anleitung”, ist ein technisches Dokument, das dem Benutzer bei der Nutzung von Goodman Mfg A/GPG13 M hilfreich sein soll. Die Bedienungsanleitungen werden in der Regel von technischen Schriftstellern geschrieben, aber in einer Sprache, die für alle Nutzer von Goodman Mfg A/GPG13 M verständlich ist.

Eine gänzliche Bedienungsanleitung von Goodman Mfg sollte einige Grundelemente enthalten. Ein Teil von ihnen ist nicht so wichtig, wie z.B.: die Titelseite oder Autorenseiten. Die restlichen von ihnen jedoch, sollten Informationen liefern, die für den Nutzer von enormer Wichtigkeit sind.

1. Einführung und Hinweise, wie man sich in einer Bedienungsanleitung von Goodman Mfg A/GPG13 M bewegt - Am Anfang jeder Bedienungsanleitung sollten wir Hinweise bezüglich der Nutzungsart eines bestimmten Ratgebers finden. In ihr sollten sich Informationen über die Lokalisierung des Inhaltsverzeichnisses von Goodman Mfg A/GPG13 M befinden, FAQ oder über oft auftretende Probleme – also Stellen, die von den Benutzern in jeder Bedienungsanleitung am meisten gesucht werden
2. Inhaltsverzeichnis - Index aller Ratschläge bezüglich Goodman Mfg A/GPG13 M, die wir im aktuellen Dokument finden
3. Ratschläge zur Nutzung der Grundfunktionen des Geräts Goodman Mfg A/GPG13 M - die uns die ersten Schritte während der Nutzung von Goodman Mfg A/GPG13 M erleichtern sollten
4. Troubleshooting - geordneter Tätigkeitslauf, der uns bei der Diagnose und als nächstes bei der Lösung wichtiger Probleme mit Goodman Mfg A/GPG13 M hilft
5. FAQ - häufig gestellte Fragen
6. Kontaktdaten Informationen darüber, wo man Kontakt zum Produzenten / Service von Goodman Mfg A/GPG13 M im bestimmten Land suchen kann, wenn es nicht gelingt, das Problem selbst zu lösen.

Haben Sie eine Frage bezüglich Goodman Mfg A/GPG13 M?

Nutzen Sie das untere Formular

Wenn Sie mit Hilfe der gefundenen Bedienungsanleitung Ihr Problem mit Goodman Mfg A/GPG13 M nicht gelöst haben, stellen Sie eine Frage, indem Sie das untere Formular nutzen. Wenn einer der Nutzer ein ähnliches Problem mit Goodman Mfg A/GPG13 M hatte, ist es möglich, dass er mit Ihnen die Lösung teilen möchte.

Text vom Bild übertragen

Kommentare (0)