    Affix this manual and Users Information Manual adjacent to the unit. INST ALLA TION & OPERA TING INSTRUCTIONS for A/GPG13 M SERIES W/R410A SINGLE P ACKAGE GAS-ELECTRIC HEA TING & COOLING UNIT C US ® Goodman Manufacturing Company , L.P . IO-357A 5151 San Felipe, Suite 500, Houston, TX 77056 3/10 www .goodmanmfg.com © 2009 - 2010 Goodman Ma ...

  • Goodman Mfg A/GPG13 M - page 2

    2 Index Replacement Parts ...................................................................................................................................................................... 3 O RDERING P ARTS .......................................................................................................................................... ...

  • Goodman Mfg A/GPG13 M - page 3

    3 REPLACEMENT PAR TS O RDERING P ARTS When reporting shortages or damages, or ordering repair parts, give the complete unit model and serial numbers as stamped on the unit’s nameplate. Replacement part s for this appliance are available through your contractor or local distributor . For the location of your nearest distributor , consult the white ...

  • Goodman Mfg A/GPG13 M - page 4

    4 WARNIN G T O PREVE N T THE RISK O F PROPERTY DAMAGE, P ERSONAL INJUR Y , O R DE ATH, DO NOT STORE COMB USTIBLE MATERIALS OR USE GASOLI NE OR OTHER FLAM MABLE LIQ U I DS OR VAPO RS I N TH E VICIN ITY OF TH IS A PPLI ANC E. CA RBON M ONOXIDE POISON ING HA ZA RD B10259-216 Carbo n monox ide produc ing devi ces (s uch as an aut omobil e, spac e heate ...

  • Goodman Mfg A/GPG13 M - page 5

    5 Outside Slab Installation R OOFTOP I NSTALLATIONS O NLY : NOTE: To ensure proper condensate drainage, unit must be installed in a level position. • T o avoid possible property damage or personal injury , the roof must have sufficient structural strength to carry the weight of the unit(s) and snow or water loads as required by local codes. Consu ...

  • Goodman Mfg A/GPG13 M - page 6

    6 The heating and cooling capacities of the unit should be greater than or equal to the design heating and cooling loads of the area to be conditioned. The loads should be calculated by an approved method or in accordance with A.S.H.R.A.E. Guide or Manual J - Load Calculations published by the Air Conditioning Contractors of America. Obtain from: A ...

  • Goodman Mfg A/GPG13 M - page 7

    7 P IPING IMPORT ANT NOTE: T o avoid possible unsatisfactory operation or equipment damage due to under firing of equipment, do not un- dersize the natural/propane gas piping from the meter/tank to the unit. When sizing a trunk line, include all appliances on that line that could be operated simultaneously . The rating plate is stamped with the mod ...

  • Goodman Mfg A/GPG13 M - page 8

    8 Sizing Between Fi rst and Second S tage Regulator Maximum Prop ane Capacities listed a re based on 1 P SIG Pressure Drop at 10 PSIG Settin g. Capacities in 1,000 BT U/HR 3/8" 1/2" 5/ 8" 3/4" 7/8" 1/2" 3/4" 30 309 700 1,303 2, 205 3,394 1,843 3,854 40 265 599 1,115 1, 887 2,904 1,577 3,298 50 235 531 988 1,672 2, ...

  • Goodman Mfg A/GPG13 M - page 9

    9 CAUTION T O PREVENT IMPROPE R A ND DANGEROUS OPERAT I ON DUE TO WIRING ERRORS, LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICI NG CONTROLS. V ERI FY PROPER OPERATION AFTER SERVICI NG. For unit protection, use a time delay fuse or HACR circuit breaker that is in excess of the circuit ampacity , but less than or equal to the maximum overcurrent ...

  • Goodman Mfg A/GPG13 M - page 10

    10 G Y W R R W Y G Fr o m Unit Typical Thermostat and Unit 24 V Wiring Hookup CIRCULA TING AIR AND FIL TERS A IRFLOW C ONVERSION Units can easily be converted from horizontal to down- discharge airflow delivery . In down-discharge or high static installations, the installer should measure the total external static and review the blower performance ...

  • Goodman Mfg A/GPG13 M - page 11

    11 VENTING NOTE: V enting is self-contained. Do not modify or block. F LUE H OOD I NSTALLATION Install the exhaust flue hood and combustion air intake hood prior to operation of the unit. T o install the flue hood cover , please refer to IO-653*, included in the flue hood assembly box located in the blower compartment. Flue Hood and Bug Screen Inst ...

  • Goodman Mfg A/GPG13 M - page 12

    12 WARNING T O AVOI D P ROPERTY DAMAGE, PERSONAL INJURY OR DEATH DUE TO FIRE OR EXPLOSION, A QUALIFIED SERVICER MUST INVESTIG ATE THE RE ASON FOR THE R OLLOUT PROTECTION DEVICE TO OP E N BEFORE MANUALLY RE S E TTING THE R OLLOUT PROTECTION DEVICE . Rol lou t Pro t ect ion Rollout Protection on Burner Bracket Secondary Limit Control The secondary li ...

  • Goodman Mfg A/GPG13 M - page 13

    13 8. Measure the gas supply pressure with burners firing. Adjust supply pressure using the Inlet Gas Supply Pressure table shown below . If supply pressure reading differs from the table, make necessary adjustments to pressure regulator , gas piping size, etc., and/or consult with local gas utility . Propane Gas Natural Gas Inlet Gas Supply Pressu ...

  • Goodman Mfg A/GPG13 M - page 14

    14 6. Turn ON power and close thermostat “R” and “W” contacts to provide a call for heat. 7. Using a leak detection solution or soap suds, check for leaks at outlet pressure boss plug (Honeywell valve) or screw (White-Rodgers valve). Bubbles forming indicate a leak. SHUT OFF GAS AND REP AIR ALL LEAKS IMMEDIA TEL Y! 8. Measure the gas manifo ...

  • Goodman Mfg A/GPG13 M - page 15

    15 Adjust the thermostat setting below room temperature. 1. Main burners must go OFF . 2. Circulating Air Blower will continue to run for 120, 135 or 150 seconds, depending on the setting. 1 2 3 10 11 12 9 6 23 6 5 8 9 11 12 L2 L2 L2 L2 D1 L1 L1 UNUSED HEAT COOL FS K2 K1 R8 R10 R3 K4 K3 R31 LE D 1 0 6 8 - 8 3 - 4 0 0 A C27 D3 R38 D9 D10 R34 R3 5 R4 ...

  • Goodman Mfg A/GPG13 M - page 16

    16 The diagnostic fault code is 1 flash for a lockout due to failed ignition attempts or flame dropouts. The integrated control will automatically reset after one hour , or it can be reset by removing the thermostat signal or disconnecting the electrical power supply for over five seconds. If the diagnostic LED indicates an external lockout, perfor ...

  • Goodman Mfg A/GPG13 M - page 17

    17 C ABINET F INISH M AINTENANCE Use a fine grade automotive wax on the cabinet finish to maintain the finish’ s original high luster . This is especially important in installations with extended periods of direct sunlight. C LEAN O UTSIDE C OIL ( Q UALIFIED S ERVICER O NLY ) The coil with the outside air flowing over it should be inspected annua ...

  • Goodman Mfg A/GPG13 M - page 18

    18 5 . Replace burners and manifold, inspect the burner assembly for proper seating of burners in retention slots. 6. Reconnect electrical power and gas supply . CAUTION L ABEL ALL W IRES PRIO R TO DISC ONNECTION WHEN SERVICING CONTROLS. W IRING ERRORS CAN CAUSE I MPROPER AND DANGEROUS OPERA TION. CAUTION A LWAYS V ERIFY PROP ER OPERATIO N AFTER S ...

  • Goodman Mfg A/GPG13 M - page 19

    19 Un it Stati c CFM W ATT S AM PS RISE C F M W AT TS AMPS RI SE C F M W ATT S AMPS R ISE 0. 1 1 , 056 350 1 . 5 1 33 1, 26 1 4 52 1.95 NR 1 ,3 70 509 2 . 2 3 NR 0. 2 1 , 010 339 1 . 4 3 34 1, 22 1 4 42 1.90 NR 1 ,3 10 492 2 . 1 3 NR 0. 3 971 343 1 . 4 5 36 1, 17 4 4 28 1. 84 NR 1 ,2 62 489 2 . 0 9 NR 0. 4 937 329 1 .4 1 37 1, 12 5 4 14 1. 80 31 1, ...

  • Goodman Mfg A/GPG13 M - page 20

    20 BLOWER PERFORMANCE DA T A - SINGLE PHASE NR = Heating T emperature Rise Not Recommended. NOTE: The shaded area indicates ranges in excess of maximum external static pressure allowable when heating. For satisfactory operation, external static pressure should not exceed 0.5" w .c. Un it St ati c CFM W ATTS AMPS RISE CFM W ATTS AMPS R I SE CFM ...

  • Goodman Mfg A/GPG13 M - page 21

    21 Un it St ati c CFM W ATTS AMPS R I SE C F M W AT T S AMPS R I SE CF M W ATT S AMPS RISE 0 . 1 ------ -- -------- ------ -- -------- -------- -------- - ------- --- ----- --- --- -- -------- -------- ----- --- 0. 2 914 125 1 . 0 7 56 1, 10 5 1 86 1. 56 46 1 ,3 97 323 2 . 5 7 NR 0. 3 822 134 1 . 1 4 62 1, 02 4 1 93 1. 60 50 1 ,3 46 331 2 . 6 7 NR ...

  • Goodman Mfg A/GPG13 M - page 22

    22 NR = Heating T emperature Rise Not Recommended. NOTE: The shaded area indicates ranges in excess of maximum external static pressure allowable when heating. For satisfactory operation, external static pressure should not exceed 0.5" w .c. BLOWER PERFORMANCE DA T A - SINGLE PHASE Un i t Stati c C F M W ATT S AMPS RISE CFM W AT TS AMPS R I SE ...

  • Goodman Mfg A/GPG13 M - page 23

    23 BLOWER PERFORMANCE DA T A - HEA TING SPEEDS THREE PHASE NR = Heating T emperature Rise Not Recommended. NOTE: The shaded area indicates ranges in excess of maximum external static pressure allowable when heating. For satisfactory operation, external static pressure should not exceed 0.5" w .c. Un it St a ti c C FM W AT T S AMPS R I SE C F M ...

  • Goodman Mfg A/GPG13 M - page 24

    24 NR = Heating T emperature Rise Not Recommended. NOTE: The shaded area indicates ranges in excess of maximum external static pressure allowable when heating. For satisfactory operation, external static pressure should not exceed 0.5" w .c. BLOWER PERFORMANCE DA T A - COOLING SPEEDS THREE PHASE Un it S t at i c CF M W a t t s RP M Amp s C F M ...

  • Goodman Mfg A/GPG13 M - page 25

    25 Light Signal Refer to Abnormal Heating or Cooling Operation Sections of this Manual Off Internal Control Failure 1 Flash External Lockout 2 Flashes Pressure Switch S tuck Open 3 Flashes Pressure Switch S tuck Closed 4 Flashes Thermal Protection Device Open 5 Flashes Flame Detected with Gas V alve Closed 6 Flashes Short Cycle Compressor Delay (Co ...

  • Goodman Mfg A/GPG13 M - page 26

    26 APPENDIX UNIT DIMENSIONS EXHAUST FLUE HO OD CO NTROL W I R E EN TRANC E POWER W IRE ENTRA NC E HEA T EXCHAN GE ACCESS P A N EL B B A FLUE EXHAU ST BLOWER ACCESS PAN EL FLUE EXHAU ST HO OD ...

  • Goodman Mfg A/GPG13 M - page 27

    27 Y NO TE 3 CONNECTED A T L1, L 2 CH OPTI ONAL BL /P K BL / PK HPS 01 40G 01 23 3 RE V . A NOTE 4 PU R VM IGN FS GA S V A LV E BL PU PU NO TE 5 ( A L T . ) HONEYW ELL GV BL W. R. PU GV MV GAS V A L VE MV RS PL PU Y 1 4 G 3 2 5 6 BL Y Y1 Y/Y2 CR PU Y BL R WG G W PU PS Y Y ALS MOT OR 4S P E E D PU B BL CAP BR Y F C H R 10 O R 7 4 1 FS 11 12 89 2 56 ...

  • Goodman Mfg A/GPG13 M - page 28

    28 6. U SE C OPP ER W IR E HP S BL/ PK BLU E/ PIN K HPS HIGH PRESS U RE SW I T CH 1. R EPLA C EMEN T W I RE MU ST BE THE SAM E SIZ E A ND TYPE OF 3B L I N K S 6B L I N K S 2B L I N K S ST A T U S LIG H T 4B L I N K S 5B L I N K S IN SU L A TIO N AS OR IGI N AL.(U SE COP PER CONDUC TOR ON L Y). 3. C R A N KC ASE H EA T ER ( O PT IONA L ). 2. FOR 208 ...

  • Goodman Mfg A/GPG13 M - page 29

    29 *PG13(48,60)1** WIRING DIAGRAM Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring. HIGH VOL T A GE! DISCONNECT ALL POWER BEFORE SERVICING OR INS T A LLING THIS UNIT . MUL T IPLE POW ER SOURCES M A Y BE P RESENT . F A ILURE T O DO SO MA Y CAUS E PROPERTY DAMA GE, PERSONAL INJURY OR DEA TH . ...

  • Goodman Mfg A/GPG13 M - page 30

    30 *PG13(48,60)1** WIRING DIAGRAM Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring. HI GH VO L T AGE! DISC ONNECT AL L POWER BEFORE SERVICING OR INST A LLING THIS UNIT . MUL T IPLE POW ER S OURCES MA Y BE PRESENT . F AI LURE TO DO SO MA Y CAUS E PROPERTY DAMAG E, PERSONAL INJURY OR DEA TH . ...

  • Goodman Mfg A/GPG13 M - page 31

    31 GPG13(36)3** WIRING DIAGRAM HIGH VOL T A GE! DISCONNECT ALL POWER BEFORE SERVICING OR INS T A LLING THIS UNIT . MUL T IPLE POW ER SOURCES M A Y BE PR ESENT . F AI LURE T O DO SO MA Y CAUS E PROP ERTY DAMAGE, PERSO NAL INJUR Y OR DEA TH . Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring. Y ...

  • Goodman Mfg A/GPG13 M - page 32

    32 GPG13(36)3** WIRING DIAGRAM Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring. HIGH VOL T A GE! DISCONNECT ALL POWER BEFORE SERVICING OR INS T A LLING THIS UNIT . MUL T IPLE POW ER SOURCES M A Y BE PR ESENT . F AI LURE T O DO SO MA Y CAUS E PROP ERTY DAMAGE, PERSONAL INJUR Y OR DEA TH . 2 ...

  • Goodman Mfg A/GPG13 M - page 33

    33 GPG13(48,60)3** WIRING DIAGRAM Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring. HIGH VOL T A GE! DISCONNECT ALL POWER BEFORE SERVICING OR INS T A LLING THIS UNIT . MUL T IPLE POW ER SOURCES M A Y BE PR ESENT . F AI LURE T O DO SO MA Y CAUS E PROP ERTY DAMAGE, PERSONAL INJUR Y OR DEA TH . ...

  • Goodman Mfg A/GPG13 M - page 34

    34 GPG13(48,60)3** WIRING DIAGRAM Wiring is subject to change. Always refer to the wiring diagram on the unit for the most up-to-date wiring. HIGH VOL T A GE! DISCONNECT ALL POWER BEFORE SERVICING OR INS T A LLING THIS UNIT . MUL T IPLE POW ER SOURCES M A Y BE PR ESENT . F AI LURE T O DO SO MA Y CAUS E PROP ERTY DAMAGE, PERSONAL INJUR Y OR DEA TH . ...

  • Goodman Mfg A/GPG13 M - page 35

    35 RECOMMENDED FIL TER SIZES UNIT 2 Ton 2 1/2 Ton 3 Ton 3 1/2 / 4 Ton 5 Ton Min. Filter Size (1)20 x 20 x 1 (1)20 x 25 x 1 (1)25 x 25 x1 (2)20 x 20 x 1 (2)20 x 25 x 1 MINIMUM CLEARANCES - NOTE: Roof overhang should be no more than 36". 3" MI N 12" MIN 12" MIN 36" MI N (FOR SERVICE ) . 48" MI N ...

  • Goodman Mfg A/GPG13 M - page 36

    36 NOTE: SPECIFICA TIONS AND PERFORMANCE DA T A LISTED HEREIN ARE SUBJECT T O CHANGE WITHOUT NOTICE Quality Makes the Difference! All of our systems are designed and manufactured with the same high quality standards regardless of size or efficiency . We have designed these units to significantly reduce the most frequent causes of product failure. T ...

Manufacturer Goodman Mfg Category Air Conditioner

Documents that we receive from a manufacturer of a Goodman Mfg A/GPG13 M can be divided into several groups. They are, among others:
- Goodman Mfg technical drawings
- A/GPG13 M manuals
- Goodman Mfg product data sheets
- information booklets
- or energy labels Goodman Mfg A/GPG13 M
All of them are important, but the most important information from the point of view of use of the device are in the user manual Goodman Mfg A/GPG13 M.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals Goodman Mfg A/GPG13 M, service manual, brief instructions and user manuals Goodman Mfg A/GPG13 M. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product Goodman Mfg A/GPG13 M.

A complete manual for the device Goodman Mfg A/GPG13 M, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use Goodman Mfg A/GPG13 M by users. Manuals are usually written by a technical writer, but in a language understandable to all users of Goodman Mfg A/GPG13 M.

A complete Goodman Mfg manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual Goodman Mfg A/GPG13 M - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the Goodman Mfg A/GPG13 M, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the Goodman Mfg A/GPG13 M, that we can find in the current document
3. Tips how to use the basic functions of the device Goodman Mfg A/GPG13 M - which should help us in our first steps of using Goodman Mfg A/GPG13 M
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with Goodman Mfg A/GPG13 M
5. FAQ - Frequently Asked Questions
6. Contact detailsInformation about where to look for contact to the manufacturer/service of Goodman Mfg A/GPG13 M in a specific country, if it was not possible to solve the problem on our own.

Do you have a question concerning Goodman Mfg A/GPG13 M?

Use the form below

If you did not solve your problem by using a manual Goodman Mfg A/GPG13 M, ask a question using the form below. If a user had a similar problem with Goodman Mfg A/GPG13 M it is likely that he will want to share the way to solve it.

Copy the text from the picture

Comments (0)