    Model DSH Ceiling Mounted Ducted R-410A Air Conditioning Units New Release Form 145.32-IOM1 (908) CEILING MOUNTED DUCTED R-410A AIR CONDITIONING UNITS INST ALLA TION INSTRUCTIONS ...

  • Energy Tech Laboratories DSH - page 2

    JOHNSON CONTROLS 2 FORM 145.32-IOM1 (908) This equipment is a relatively complicated apparatus. During installation, operation, maintenance or service, individuals may be exposed to certain components or conditions including, but not limited to: refrigerants, oils, materials under pressure, rotating components, and both high and low voltage. Each o ...

  • Energy Tech Laboratories DSH - page 3

    FORM 145.32-IOM1 (908) 3 JOHNSON CONTROLS CHANGEABILITY OF THIS DOCUMENT T ABLE OF CONTENTS In complying with Joh nson C ontro ls policy for continu- ous product improvement, the information contained in this document is subject to change without notice. While Jo hnson Con trols makes no commitment to up- date or provide current information automat ...

  • Energy Tech Laboratories DSH - page 4

    JOHNSON CONTROLS 4 FORM 145.32-IOM1 (908) GENERAL INFORMA TION Our units are designed to meet the ever-changing (un ique) instal latio n requi remen ts of today ’s mark et. The horizontal conguration is unitized for single package or split installation. Low prole design allows the unit to be installed on the oor or suspended from the cei ...

  • Energy Tech Laboratories DSH - page 5

    FORM 145.32-IOM1 (908) 5 JOHNSON CONTROLS TYPICAL INST ALLA TION DRA WING ...

  • Energy Tech Laboratories DSH - page 6

    JOHNSON CONTROLS 6 FORM 145.32-IOM1 (908) PRE-INST ALLA TION INSPECTION OF EQUIPMENT All units are factory tested to ensure safe operation and quality assembly . Units are packaged and sealed on shipping skids and shipped in rst class condition. T orn and broken packaging, scratched or dented panels should be reported to carrier immediately . An ...

  • Energy Tech Laboratories DSH - page 7

    FORM 145.32-IOM1 (908) 7 JOHNSON CONTROLS UNIT MOUNTING The 2 through 5 ton unit consist of an evaporator and condenser module. These two modules are rigidly at- tac hed by a join ing str ip acro ss the top of the two cab inet , an d two long sid e cro ss- memb er angl es whi ch brid ge the mou nting chann els on the botto m of the unit. These unit ...

  • Energy Tech Laboratories DSH - page 8

    JOHNSON CONTROLS 8 FORM 145.32-IOM1 (908) SEP ARA TION OF UNITS The 2 through 5 ton units are provided with refrigerant shut-off valves to allow the evaporator and condenser sections to be eld split - without the necessity of re - claiming the entire unit refrigerant charge. The evaporator and condenser sections may be sepa- rated by performing ...

  • Energy Tech Laboratories DSH - page 9

    FORM 145.32-IOM1 (908) 9 JOHNSON CONTROLS DIMENSIONAL DA T A ...

  • Energy Tech Laboratories DSH - page 10

    JOHNSON CONTROLS 10 FORM 145.32-IOM1 (908) DIMENSIONAL DA T A (Cont.) ...

  • Energy Tech Laboratories DSH - page 11

    FORM 145.32-IOM1 (908) 11 JOHNSON CONTROLS DUCTWORK When installing ductwork, adhere to local Codes and sensible practice. Minimize duct runs and avoid abrupt cha nge s in dire ctio n whe re poss ible . Allow amp le acces s space for servicing of the coils and changing of lters. Perform regular maintenance on ducts to increase unit life, maintai ...

  • Energy Tech Laboratories DSH - page 12

    JOHNSON CONTROLS 12 FORM 145.32-IOM1 (908) ELECTRICAL WIRING Follow local electrical codes when making electrical co nn ect ion s. Uni ts are co mpl ete ly fac to ry wi red fo r no rma l supply voltages (ie.208-230, 460, 575/3phase/60Hz) Conrm unit specications by checking unit data plate. The factory wiring terminates in two boxes, one in ea ...

  • Energy Tech Laboratories DSH - page 13

    FORM 145.32-IOM1 (908) 13 JOHNSON CONTROLS STANDA RD MOT ORS MO DEL VOLTA GE COMPRESSOR E VAP OR ATOR FAN CONDENSER F A N MIN. CCT. "MOP" # QTY RLA LRA HP FLA HP FLA AMP ACIT Y Max Overcurrent Prot. AC024H12 208-230/1/60 1 @ 13.5 58.3 0.25 2.6 0.50 4.5 23.98 35 AC024H32 208-230/3/60 1 @ 8.6 55.0 0.25 1.4 0.50 2.2 14.35 20 AC036H12 208-230 ...

  • Energy Tech Laboratories DSH - page 14

    JOHNSON CONTROLS 14 FORM 145.32-IOM1 (908) MOTOR AND PULLEY DA T A EVAPORA TOR - STANDARD BLOW ER M OTOR AND DRIVE DATA Belts HP Frame Eff.(%) Pitch Dia.(in) Browning # Pitch Dia.(in) Br owning# Ratin g / Size Qty 2 TON 845-1170 1/4 56 66.0 2.6-3.6 1VP40 X 5/8 5.4 AK56H 4L370 1 3 TON 675-1010 1/3 56 75.0 2.0-3.0 1VP34 X 5/8 5.2 AK54H 4L370 1 4 TON ...

  • Energy Tech Laboratories DSH - page 15

    FORM 145.32-IOM1 (908) 15 JOHNSON CONTROLS ST ART -UP AND OPERA TION Prior to starting unit for the rst time, tur n t he th erm os tat sy st em swi tc h t o OFF - or raise the cooling setpoint to the highest temperature, to prevent the unit from starting. Close the electrical dis connec t switc h. This will energ ize the compressor crankcase hea ...

  • Energy Tech Laboratories DSH - page 16

    JOHNSON CONTROLS 16 FORM 145.32-IOM1 (908) TYPICAL SCHEMA TIC ...

  • Energy Tech Laboratories DSH - page 17

    FORM 145.32-IOM1 (908) 17 JOHNSON CONTROLS MAINTENANCE / SERVICE Disconnect And Lock Out Power When Servicing Unit. Failure T o Do So May Result In Personal Injury Or Death Due T o Electrical Shock. Exercise care when working around the sharp metal edges of door panels or door frames, etc. These edges can cause injury . FIL TERS Inspect lters mo ...

  • Energy Tech Laboratories DSH - page 18

    JOHNSON CONTROLS 18 FORM 145.32-IOM1 (908) COMFORT ALERT™ DIAGNOSTICS The Comfort Alert diagnostics module is a brea kthrough innovation for troubleshooting and protecting three phase Copeland Scroll® compressors. The module installs easily in the electrical box of the condensing unit near the compressor contactor . By monitoring and analyzing d ...

  • Energy Tech Laboratories DSH - page 19

    FORM 145.32-IOM1 (908) 19 JOHNSON CONTROLS Status LED Status LED Description Status LED Troubleshooting Information Green “POW ER” Module has power Supply vo ltage is present at module terminal s 1. Compressor protector is open 2. Condensing unit pow er disconnect is open 3. Compressor circuit breaker or fuse(s) is open 4. Broken suppl y wire s ...

  • Energy Tech Laboratories DSH - page 20

    JOHNSON CONTROLS 20 FORM 145.32-IOM1 (908) Fla sh cod e numb er corr espon ds to a num ber of LED flashes, followed by a pause and then repeated. TRIP and ALERT LED’ s flashing at the same time means control circuit voltage is too low for opera- tion. Resetting Alert Codes Alert codes can be reset manually and automatically . The manual method ...

  • Energy Tech Laboratories DSH - page 21

    FORM 145.32-IOM1 (908) 21 JOHNSON CONTROLS Miswiring the Comfort Alert module will cause false LED codes. T able 1 describes LED opera - tion when the module is miswired and what troubleshooting action is required to correct the problem. Installation V erication T o verify the installation of Comfort Alert is correct, a functional test can be pe ...

  • Energy Tech Laboratories DSH - page 22

    JOHNSON CONTROLS 22 FORM 145.32-IOM1 (908) LIMITED W ARRANTY ONE YEAR LIMITED W ARRANTY Johnson Controls warrants this product to be free from defects in workmanship or material for a period of one year from date of original installation or 18 months from date of shipment, whichever comes rst. Johnson Controls obligation under this Warranty is L ...

  • Energy Tech Laboratories DSH - page 23

    FORM 145.32-IOM1 (908) 23 JOHNSON CONTROLS R-410A QUICK REFERENCE GUIDE  RefertoInstallationInstructionsfor specicinstallationrequir ements . • R-410A Refrigerant operates at 50 - 70 percent higher pressures than R-22. Be sure that servicing equipment and replacement components are designed to operate with R-410A. • R ...

  • Energy Tech Laboratories DSH - page 24

    Subject to change without notice. Printed in U.S.A. Copyright © 2008 by Unitary Products Group. All rights reserved. Form 145.32-IOM1 (908) New Release Y ork PA 17405 P .O. Box 1592 Y ork, P A 17405 Engineered Systems Products Group ...

Fabricante Energy Tech Laboratories Categoría Air Conditioner

Los documentos del dispositivo Energy Tech Laboratories DSH que obtenemos del fabricante se pueden dividir en varios grupos. Entre ellos están::
- dibujos técnicos Energy Tech Laboratories
- manuales de instrucciones DSH
- hojas de producto Energy Tech Laboratories
- folletos informativos
- o etiquetas energéticas Energy Tech Laboratories DSH
Todos son importantes, pero lo más importante desde el punto de vista del usuario de un dispositivo lo encontraremos en el manual de instrucciones Energy Tech Laboratories DSH.

Un conjunto de documentos determinado como manual de instrucciones se divide también en tipos más detallados, tales como: instrucciones de montaje Energy Tech Laboratories DSH, instrucciones de servicio, instrucciones cortas o instrucciones de usuario Energy Tech Laboratories DSH. Dependiendo de la situación debes buscar el documento que necesitas. En nuestra página puedes consultar el manual de instrucciones más popular del producto Energy Tech Laboratories DSH.

Manuales de instrucciones parecidos

El manual de instrucciones del dispositivo Energy Tech Laboratories DSH, ¿cómo debería ser?
El manual de instrucciones, también determinado como el manual de usuario o simplemente instrucciones, es un documento técnico que tiene como objetivo ayudar a los usuarios a utilizar Energy Tech Laboratories DSH. Las instrucciones normalmente las realiza un escritor técnico pero en un lenguaje comprensible para todos los usuarios de Energy Tech Laboratories DSH.

El manual de instrucciones completo de Energy Tech Laboratories debe contener unos elementos básicos. Una parte de ellos es menos importante, como por ejemplo: la portada / la página principal o las páginas de autor. Sin embargo, lo demás debe facilitarnos la información más importante desde el punto de vista del usuario.

1. Introducción y pistas sobre cómo orientarse con el manual Energy Tech Laboratories DSH - Al principio de cada manual se deben encontrar las indicaciones acerca de la manera de usar un manual de instrucciones. Debe contener información sobre dónde encontrar el índice Energy Tech Laboratories DSH, preguntas frecuentes o problemas más comunes – son los apartados más buscados por los usuarios de cada manual de instrucciones.
2. Índice - listados de todos los consejos acerca de Energy Tech Laboratories DSH que encontraremos en el documento
3. Consejos de uso de las funciones básicas del dispositivo Energy Tech Laboratories DSH - que deben facilitarnos los primeros pasos durante el uso de Energy Tech Laboratories DSH
4. Troubleshooting - una secuencia sistematizada de acciones que nos ayudará a diagnosticar los problemas más importantes con Energy Tech Laboratories DSH
5. FAQ - las preguntas frecuentes
6. Datos de contacto Información acerca de cómo encontrar los datos de contacto del fabricante / servicio de Energy Tech Laboratories DSH en cada país si no somos capaces de solucionar el problema por nuestra cuenta.

¿Tienes una pregunta acerca de Energy Tech Laboratories DSH?

Utiliza el formulario que se encuentra abajo

Si con la ayuda del manual de instrucciones encontrado no has podido solucionar tu problema con Energy Tech Laboratories DSH, haz una pregunta utilizando el formulario que se encuentra abajo. Si alguno de los usuarios ha tenido un problema parecido con Energy Tech Laboratories DSH probablemente compartirá una forma de solucionarlo.

Copia el texto de la imagen

Comentarios (0)