  • Energy Tech Laboratories DSH - page 1

    Model DSH Ceiling Mounted Ducted R-410A Air Conditioning Units New Release Form 145.32-IOM1 (908) CEILING MOUNTED DUCTED R-410A AIR CONDITIONING UNITS INST ALLA TION INSTRUCTIONS ...

  • Energy Tech Laboratories DSH - page 2

    JOHNSON CONTROLS 2 FORM 145.32-IOM1 (908) This equipment is a relatively complicated apparatus. During installation, operation, maintenance or service, individuals may be exposed to certain components or conditions including, but not limited to: refrigerants, oils, materials under pressure, rotating components, and both high and low voltage. Each o ...

  • Energy Tech Laboratories DSH - page 3

    FORM 145.32-IOM1 (908) 3 JOHNSON CONTROLS CHANGEABILITY OF THIS DOCUMENT T ABLE OF CONTENTS In complying with Joh nson C ontro ls policy for continu- ous product improvement, the information contained in this document is subject to change without notice. While Jo hnson Con trols makes no commitment to up- date or provide current information automat ...

  • Energy Tech Laboratories DSH - page 4

    JOHNSON CONTROLS 4 FORM 145.32-IOM1 (908) GENERAL INFORMA TION Our units are designed to meet the ever-changing (un ique) instal latio n requi remen ts of today ’s mark et. The horizontal conguration is unitized for single package or split installation. Low prole design allows the unit to be installed on the oor or suspended from the cei ...

  • Energy Tech Laboratories DSH - page 5

    FORM 145.32-IOM1 (908) 5 JOHNSON CONTROLS TYPICAL INST ALLA TION DRA WING ...

  • Energy Tech Laboratories DSH - page 6

    JOHNSON CONTROLS 6 FORM 145.32-IOM1 (908) PRE-INST ALLA TION INSPECTION OF EQUIPMENT All units are factory tested to ensure safe operation and quality assembly . Units are packaged and sealed on shipping skids and shipped in rst class condition. T orn and broken packaging, scratched or dented panels should be reported to carrier immediately . An ...

  • Energy Tech Laboratories DSH - page 7

    FORM 145.32-IOM1 (908) 7 JOHNSON CONTROLS UNIT MOUNTING The 2 through 5 ton unit consist of an evaporator and condenser module. These two modules are rigidly at- tac hed by a join ing str ip acro ss the top of the two cab inet , an d two long sid e cro ss- memb er angl es whi ch brid ge the mou nting chann els on the botto m of the unit. These unit ...

  • Energy Tech Laboratories DSH - page 8

    JOHNSON CONTROLS 8 FORM 145.32-IOM1 (908) SEP ARA TION OF UNITS The 2 through 5 ton units are provided with refrigerant shut-off valves to allow the evaporator and condenser sections to be eld split - without the necessity of re - claiming the entire unit refrigerant charge. The evaporator and condenser sections may be sepa- rated by performing ...

  • Energy Tech Laboratories DSH - page 9

    FORM 145.32-IOM1 (908) 9 JOHNSON CONTROLS DIMENSIONAL DA T A ...

  • Energy Tech Laboratories DSH - page 10

    JOHNSON CONTROLS 10 FORM 145.32-IOM1 (908) DIMENSIONAL DA T A (Cont.) ...

  • Energy Tech Laboratories DSH - page 11

    FORM 145.32-IOM1 (908) 11 JOHNSON CONTROLS DUCTWORK When installing ductwork, adhere to local Codes and sensible practice. Minimize duct runs and avoid abrupt cha nge s in dire ctio n whe re poss ible . Allow amp le acces s space for servicing of the coils and changing of lters. Perform regular maintenance on ducts to increase unit life, maintai ...

  • Energy Tech Laboratories DSH - page 12

    JOHNSON CONTROLS 12 FORM 145.32-IOM1 (908) ELECTRICAL WIRING Follow local electrical codes when making electrical co nn ect ion s. Uni ts are co mpl ete ly fac to ry wi red fo r no rma l supply voltages (ie.208-230, 460, 575/3phase/60Hz) Conrm unit specications by checking unit data plate. The factory wiring terminates in two boxes, one in ea ...

  • Energy Tech Laboratories DSH - page 13

    FORM 145.32-IOM1 (908) 13 JOHNSON CONTROLS STANDA RD MOT ORS MO DEL VOLTA GE COMPRESSOR E VAP OR ATOR FAN CONDENSER F A N MIN. CCT. "MOP" # QTY RLA LRA HP FLA HP FLA AMP ACIT Y Max Overcurrent Prot. AC024H12 208-230/1/60 1 @ 13.5 58.3 0.25 2.6 0.50 4.5 23.98 35 AC024H32 208-230/3/60 1 @ 8.6 55.0 0.25 1.4 0.50 2.2 14.35 20 AC036H12 208-230 ...

  • Energy Tech Laboratories DSH - page 14

    JOHNSON CONTROLS 14 FORM 145.32-IOM1 (908) MOTOR AND PULLEY DA T A EVAPORA TOR - STANDARD BLOW ER M OTOR AND DRIVE DATA Belts HP Frame Eff.(%) Pitch Dia.(in) Browning # Pitch Dia.(in) Br owning# Ratin g / Size Qty 2 TON 845-1170 1/4 56 66.0 2.6-3.6 1VP40 X 5/8 5.4 AK56H 4L370 1 3 TON 675-1010 1/3 56 75.0 2.0-3.0 1VP34 X 5/8 5.2 AK54H 4L370 1 4 TON ...

  • Energy Tech Laboratories DSH - page 15

    FORM 145.32-IOM1 (908) 15 JOHNSON CONTROLS ST ART -UP AND OPERA TION Prior to starting unit for the rst time, tur n t he th erm os tat sy st em swi tc h t o OFF - or raise the cooling setpoint to the highest temperature, to prevent the unit from starting. Close the electrical dis connec t switc h. This will energ ize the compressor crankcase hea ...

  • Energy Tech Laboratories DSH - page 16

    JOHNSON CONTROLS 16 FORM 145.32-IOM1 (908) TYPICAL SCHEMA TIC ...

  • Energy Tech Laboratories DSH - page 17

    FORM 145.32-IOM1 (908) 17 JOHNSON CONTROLS MAINTENANCE / SERVICE Disconnect And Lock Out Power When Servicing Unit. Failure T o Do So May Result In Personal Injury Or Death Due T o Electrical Shock. Exercise care when working around the sharp metal edges of door panels or door frames, etc. These edges can cause injury . FIL TERS Inspect lters mo ...

  • Energy Tech Laboratories DSH - page 18

    JOHNSON CONTROLS 18 FORM 145.32-IOM1 (908) COMFORT ALERT™ DIAGNOSTICS The Comfort Alert diagnostics module is a brea kthrough innovation for troubleshooting and protecting three phase Copeland Scroll® compressors. The module installs easily in the electrical box of the condensing unit near the compressor contactor . By monitoring and analyzing d ...

  • Energy Tech Laboratories DSH - page 19

    FORM 145.32-IOM1 (908) 19 JOHNSON CONTROLS Status LED Status LED Description Status LED Troubleshooting Information Green “POW ER” Module has power Supply vo ltage is present at module terminal s 1. Compressor protector is open 2. Condensing unit pow er disconnect is open 3. Compressor circuit breaker or fuse(s) is open 4. Broken suppl y wire s ...

  • Energy Tech Laboratories DSH - page 20

    JOHNSON CONTROLS 20 FORM 145.32-IOM1 (908) Fla sh cod e numb er corr espon ds to a num ber of LED flashes, followed by a pause and then repeated. TRIP and ALERT LED’ s flashing at the same time means control circuit voltage is too low for opera- tion. Resetting Alert Codes Alert codes can be reset manually and automatically . The manual method ...

  • Energy Tech Laboratories DSH - page 21

    FORM 145.32-IOM1 (908) 21 JOHNSON CONTROLS Miswiring the Comfort Alert module will cause false LED codes. T able 1 describes LED opera - tion when the module is miswired and what troubleshooting action is required to correct the problem. Installation V erication T o verify the installation of Comfort Alert is correct, a functional test can be pe ...

  • Energy Tech Laboratories DSH - page 22

    JOHNSON CONTROLS 22 FORM 145.32-IOM1 (908) LIMITED W ARRANTY ONE YEAR LIMITED W ARRANTY Johnson Controls warrants this product to be free from defects in workmanship or material for a period of one year from date of original installation or 18 months from date of shipment, whichever comes rst. Johnson Controls obligation under this Warranty is L ...

  • Energy Tech Laboratories DSH - page 23

    FORM 145.32-IOM1 (908) 23 JOHNSON CONTROLS R-410A QUICK REFERENCE GUIDE  RefertoInstallationInstructionsfor specicinstallationrequir ements . • R-410A Refrigerant operates at 50 - 70 percent higher pressures than R-22. Be sure that servicing equipment and replacement components are designed to operate with R-410A. • R ...

  • Energy Tech Laboratories DSH - page 24

    Subject to change without notice. Printed in U.S.A. Copyright © 2008 by Unitary Products Group. All rights reserved. Form 145.32-IOM1 (908) New Release Y ork PA 17405 P .O. Box 1592 Y ork, P A 17405 Engineered Systems Products Group ...

メーカー Energy Tech Laboratories カテゴリー Air Conditioner

Energy Tech Laboratories DSHのメーカーから受け取ることができるドキュメントは、いくつかのグループに分けられます。その一部は次の通りです:
- #BRANDの図面#
- DSHの取扱説明書
- Energy Tech Laboratoriesの製品カード
- パンフレット
- またはEnergy Tech Laboratories DSHの消費電力シール
それらは全部重要ですが、デバイス使用の観点から最も重要な情報は、Energy Tech Laboratories DSHの取扱説明書に含まれています。

取扱説明書と呼ばれる文書のグループは、Energy Tech Laboratories DSHの取り付け説明書、サービスマニュアル、簡易説明書、またはEnergy Tech Laboratories DSHのユーザーマニュアル等、より具体的なカテゴリーに分類されます。ご必要に応じてドキュメントを検索しましょう。私たちのウェブサイトでは、Energy Tech Laboratories DSHの製品を使用するにあたって最も人気のある説明書を閲覧できます。

関連する取扱説明書

Energy Tech Laboratories DSHデバイスの取扱説明書はどのようなものですか?
取扱説明書は、ユーザーマニュアル又は単に「マニュアル」とも呼ばれ、ユーザーがEnergy Tech Laboratories DSHを使用するのを助ける技術的文書のことです。説明書は通常、全てのEnergy Tech Laboratories DSHユーザーが容易に理解できる文章にて書かれており、その作成者はその分野の専門家です。

Energy Tech Laboratoriesの取扱説明書には、基本的な要素が記載されているはずです。その一部は、カバー/タイトルページ、著作権ページ等、比較的重要度の低いものです。ですが、その他の部分には、ユーザーにとって重要な情報が記載されているはずです。

1. Energy Tech Laboratories DSHの説明書の概要と使用方法。説明書にはまず、その閲覧方法に関する手引きが書かれているはずです。そこにははEnergy Tech Laboratories DSHの目次に関する情報やよくある質問、最も一般的な問題に関する情報を見つけられるはずです。つまり、それらはユーザーが取扱説明書に最も期待する情報なのです。
2. 目次。Energy Tech Laboratories DSHに関してこのドキュメントで見つけることができる全てのヒントの目次
3. Energy Tech Laboratories DSHデバイスの基本機能を使うにあたってのヒント。 Energy Tech Laboratories DSHのユーザーが使い始めるのを助けてくれるはずです。
4. トラブルシューティング。Energy Tech Laboratories DSHに関する最も重要な問題を診断し、解決するために役立つ体系化された手続き
5. FAQ。よくある質問
6. 連絡先。一人では問題を解決できない場合に、その国におけるEnergy Tech Laboratories DSHのメーカー/サービスへの連絡先に関する情報。

Energy Tech Laboratories DSHについてご質問がありますか?

次のフォームを使用してください

見つけた説明書を読んでもEnergy Tech Laboratories DSHの問題を解決できない場合、下記のフォームを使用して質問をしましょう。ユーザーのどなたかがEnergy Tech Laboratories DSHで同様の問題を抱えていた場合、その解決方法を共有したいと考えるかもしれません。

画像のテキストを入力してください

コメント (0)