    PRODUCT D A T A Copyright © 1996 Honeywell Inc. • All Rights Reserved X-XX UL 60-2337-3 R4140G Flame Safeguard Programming Controls APPLICA TION The R4140G Flame Safeguard Programmers provide flameout protection plus automatic sequencing of the burner motor (blower), firing rate motor , ignition, pilot valve, and main fuel valve(s) for commercia ...

  • Honeywell R4140G - page 2

    R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 2 ORDERING INFORMA TION When purchasing replacement and modernization products from your TRADELINE ® wholesaler or distributor , refer to the TRADELINE ® Catalog or price sheets for complete ordering number or specify order number . Order separately: 1. Flame detection system (amplifier a ...

  • Honeywell R4140G - page 3

    R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 3 NOTE: Allowable inrush can be up to ten times the pilot duty rating. EXAMPLE: Pilot duty rating = 50 V A. At 120V , running current is: 50 120 = 0.42A . Maximum allowable inrush is ten times 0.42A = 4.2A. Interlock Ratings: See T able 3. T able 3. Interlock Ratings. Ambient Operating T em ...

  • Honeywell R4140G - page 4

    R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 4 Fig. 1. Mounting dimensions of the Q520A wiring subbase in in. (mm). 13/64 (5) DIAMETER (4) (FOR MOUNTING ON 4 X 4 [102 X 102] JUNCTION BOX) 1-27/32 (47) 5/8 (16) (4) 7/8 (22) DIAMETER KNOCKOUT (2) 3-3/8 (86) 7 -1/16 (179) 7-3/16 (183) 15/16 (24) (2) 1-3/4 (45) 6-5/32 (156) 31/32 (25) (2) ...

  • Honeywell R4140G - page 5

    R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 5 Accessories: W136A T est Meter (includes 1 17053 Meter Connector Plug); has SPL position with damping for testing self- checking flame detection systems. 1 17053 Meter Connector Plug (for older W136A models). 123514A Flame Simulator (for use with R7247A Rectification Amplifiers). 123514B ...

  • Honeywell R4140G - page 6

    R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 6 OPERA TION Models with Preignition Interlocks Fig. 3 shows all contacts in the standby position (zero seconds). The opening and closing times are shown adjacent Fig. 3. Simplified schematic dia gram of R4140G1015 Programmer . 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 ...

  • Honeywell R4140G - page 7

    R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 7 Fig. 4. Timer sequence for R4140G1015 Programmer . Step-By-Step Operation (R4140G1015) Start And Prepurge 0 seconds — On a call for heat, the burner controller contacts close. If the limits and preignition interlocks are closed and flame relay 2K is not holding in, relay 1K pulls in thr ...

  • Honeywell R4140G - page 8

    R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 8 Ignition T rials 60 seconds — M4A closes; power is applied to terminals 5 and 6, energizing the ignition transformer and pilot valve (or main fuel valve(s) on terminal 7 if using direct spark ignition). — When a flame is detected, relay 2K pulls in, 2K2 opens, and the LS HTR stops hea ...

  • Honeywell R4140G - page 9

    R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 9 Fig. 5. Simplified schematic dia gram of R4140G1106 Programmer . 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 B R W B R W 14 12 11 10 9 L1 (HOT) L2 1 2 120V , 60 HZ POWER SUPPL Y UNDERLINED O OR C DENOTES SNAP A CTION OF CONT ACT . A TIMER CONT ACTS SNAP CLOSED . B CONT ...

  • Honeywell R4140G - page 10

    R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 10 Fig. 6. Timer sequence for R4140G1106 Programmer . Step-By-Step Operation (R4140G1106) Start and Prepurge 0 seconds — On a call for heat, the burner controller contacts close. If the limits and preignition interlocks are closed and flame relay 2K is not holding in, relay 1K pulls in th ...

  • Honeywell R4140G - page 11

    R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 11 Ignition T rials 60 seconds — M4A closes; power is applied to terminals 5 and 6, energizing the ignition transformer and pilot valve (or main fuel valve(s) on terminal 7 If using direct spark ignition). — When a flame is detected, relay 2K pulls in, 2K2 opens, and the LS HTR stops he ...

  • Honeywell R4140G - page 12

    R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 12 Fig. 7. Simplified schematic dia gram of R4140G1049 Programmer . 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 B R W B R W 14 12 11 10 9 L1 (HOT) L2 1 2 120V , 60 HZ POWER SUPPL Y UNDERLINED O OR C DENOTES SNAP A CTION OF CONT ACT . A TIMER CONT ACTS SNAP CLOSED ...

  • Honeywell R4140G - page 13

    R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 13 Fig. 8. Timer sequence for R4140G1049 Programmer . M10055 TIMER SECONDS TIMER DIAL TIMER MOTOR BURNER MOTOR (BLOWER) INTERRUPTED PILOT/IGNITION 5 SECOND IGNITION MAIN FUEL VALVE(S) (GAS OR OIL) FIRING RATE MOTOR SWITCHING ACTUAL DAMPER OPERATION 0 10 20 30 40 50 60 70 80 90 100 110 120 S ...

  • Honeywell R4140G - page 14

    R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 14 Ignition T rials 60 seconds — M4A closes; power is applied to terminals 18, 5, and 6, energizing the ignition transformer and pilot valve (or main fuel valve(s) on terminal 7 if using direct spark ignition). — When a flame is detected, relay 2K pulls in, 2K2 opens, and the LS HTR sto ...

  • Honeywell R4140G - page 15

    R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 15 Fig. 9. Simplified schematic dia gram of the R4140G1056 and R4140G1064 Programmer s. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 B R W B R W 14 12 11 10 9 L1 (HOT) L2 1 2 120V , 60 HZ POWER SUPPL Y UNDERLINED O OR C DENOTES SNAP A CTION OF CONT ACT . A TIMER C ...

  • Honeywell R4140G - page 16

    R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 16 Fig. 10. Timer sequence for R4140G1056 and R4140G1064 Programmer s. M10056 TIMER SECONDS TIMER DIAL TIMER MOTOR BURNER MOTOR (BLOWER) INTERMITTENT PILOT OR 1ST STAGE FUEL VALVE 10 SECOND INTERRUPTED PILOT/IGNITION 5 SECOND IGNITION MAIN FUEL VALVE(S) (GAS OR OIL) FIRING RATE MOTOR SWITCH ...

  • Honeywell R4140G - page 17

    R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 17 Ignition T rials 60 seconds — M4A closes; power is applied to terminals 18, 5, and 6, energizing the ignition transformer and pilot valve (or first stage fuel valve when using direct spark ignition). — When a flame is detected, relay 2K pulls in, 2K2 opens, and the LS HTR stops heati ...

  • Honeywell R4140G - page 18

    R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 18 Fig. 11. Simplified schematic dia gram of R4140G1171, R4140G122 and R4140G1114 Programmer s. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 B R W B R W 14 12 11 10 9 L1 (HOT) L2 1 2 120V , 60 HZ POWER SUPPL Y UNDERLINED O OR C DENOTES SNAP A CTION OF CONT ACT . A ...

  • Honeywell R4140G - page 19

    R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 19 Fig. 12. Timer sequence for R4140G1171, R4140G1122 and R4140G1114 Programmer s. M10057 1 2 3 4 5 6 TERMINAL NUMBERS (CIRCLED). SLOPE DEPENDS ON MOTOR TIMING. TIMER STOPS AT 60 SECONDS UNTIL LOW FIRE PROVING SWITCH CLOSES. FIRING RATE MOTOR MODULATES UNDER CONTROL OF SERIES 90 CONTROLLER ...

  • Honeywell R4140G - page 20

    R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 20 Ignition T rials 70 seconds — M4A closes; power is applied to terminals 18, 5 and 6, energizing the ignition transformer and pilot valve (and terminal 7, main oil valve solenoid, if using direct spark ignition of oil). — When flame is detected, relay 2K pulls in, 2K2 opens, and the L ...

  • Honeywell R4140G - page 21

    R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 21 Fig. 13. Simplified schematic dia gram of R4140G1148 Programmer . 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 B R W B R W 14 12 11 10 9 L1 (HOT) L2 1 2 120V , 60 HZ POWER SUPPL Y UNDERLINED O OR C DENOTES SNAP A CTION OF CONT ACT . A TIMER CONT ACTS SNAP CLOSE ...

  • Honeywell R4140G - page 22

    R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 22 Fig. 14. Timer sequence for R4140G1148 Programmer . Step-By-Step Operation (R4140G1148) Start and Prepurge 0 seconds — On a call for heat, the burner controller contacts close. If the limits and start interlock(s) are closed and flame relay 2K is not holding in, relay 1K pulls in throu ...

  • Honeywell R4140G - page 23

    R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 23 Ignition T rials 60 seconds — M4A closes; power is applied to terminals 18, 5 and 6, energizing the ignition transformer and pilot valve (or main fuel valve(s) on terminal 7 if using direct spark ignition). — When a flame is detected, relay 2K pulls in, 2K2 opens, and the LS HTR stop ...

  • Honeywell R4140G - page 24

    R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 24 Fig. 15. Sample bloc k diagram of field wiring f or R4140G1007, R4140G1015 and R4140G1106 Programmer s. RECTIFYING FLAME ROD , RECTIFYING PHOT OCELL, OR INFRARED (LEAD SULFIDE) FLAME DETECTOR C7027A, C7035A, OR C7044A UL TRA VIOLET FLAME DETECTOR C7012A,C,E,F OR C7076A UL TRA VIOLET FLAM ...

  • Honeywell R4140G - page 25

    R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 25 Fig. 16. Sample bloc k diagram of field wiring f or R4140G1049, R4140G1056, R4140G1064, R4140G1114, R4140G1122, R4140G1148 and R4140G1171 Programmer s. RECTIFYING FLAME ROD , RECTIFYING PHOT OCELL, OR INFRARED (LEAD SULFIDE) FLAME DETECTOR C7027A, C7035A, OR C7044A UL TRA VIOLET FLAME DE ...

  • Honeywell R4140G - page 26

    R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 26 Optional Hookups f or T wo-Sta ge Switching or Intermittent Pilot/Ignition (Nonmodulating Oil Burners) If modulation of the firing rate is not required, an R4140G can be used to provide two-stage switching for an oil burner; also, an R4140G with interrupted pilot/ignition on terminal 6 c ...

  • Honeywell R4140G - page 27

    R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 27 M10061 TIMER SECONDS INTERRUPTED PILOT/IGNITION OR 1ST STAGE OIL VALVE 20 SECOND INTERRUPTED PILOT/IGNITION MAIN FUEL VALVE OR 2ND STAGE OIL VALVE 0 10 20 30 40 50 60 70 80 90 100 110 120 3 1 1 2 3 2 12 5 6 TERMINAL NUMBERS (CIRCLED). TIMER STOPS AT 104 SECONDS FOR THE RUN PERIOD WITH TH ...

  • Honeywell R4140G - page 28

    R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 28 Honeywell Europe S.A. 3 Avenue du Bourget B-1140 Brussels Belgium Honeywell Asia Pacific Inc. Room 3213-3225 Sun Hung Kai Centre No. 30 Harbour Road Wanchai Hong Kong Home and Building Control Honeywell Limited-Honeywell Limitée 35 Dynamic Drive Scarborough, Ontario M1V 4Z9 Honeywell La ...

Fabricante Honeywell Categoría Car Amplifier

Los documentos del dispositivo Honeywell R4140G que obtenemos del fabricante se pueden dividir en varios grupos. Entre ellos están::
- dibujos técnicos Honeywell
- manuales de instrucciones R4140G
- hojas de producto Honeywell
- folletos informativos
- o etiquetas energéticas Honeywell R4140G
Todos son importantes, pero lo más importante desde el punto de vista del usuario de un dispositivo lo encontraremos en el manual de instrucciones Honeywell R4140G.

Un conjunto de documentos determinado como manual de instrucciones se divide también en tipos más detallados, tales como: instrucciones de montaje Honeywell R4140G, instrucciones de servicio, instrucciones cortas o instrucciones de usuario Honeywell R4140G. Dependiendo de la situación debes buscar el documento que necesitas. En nuestra página puedes consultar el manual de instrucciones más popular del producto Honeywell R4140G.

Manuales de instrucciones parecidos

El manual de instrucciones del dispositivo Honeywell R4140G, ¿cómo debería ser?
El manual de instrucciones, también determinado como el manual de usuario o simplemente instrucciones, es un documento técnico que tiene como objetivo ayudar a los usuarios a utilizar Honeywell R4140G. Las instrucciones normalmente las realiza un escritor técnico pero en un lenguaje comprensible para todos los usuarios de Honeywell R4140G.

El manual de instrucciones completo de Honeywell debe contener unos elementos básicos. Una parte de ellos es menos importante, como por ejemplo: la portada / la página principal o las páginas de autor. Sin embargo, lo demás debe facilitarnos la información más importante desde el punto de vista del usuario.

1. Introducción y pistas sobre cómo orientarse con el manual Honeywell R4140G - Al principio de cada manual se deben encontrar las indicaciones acerca de la manera de usar un manual de instrucciones. Debe contener información sobre dónde encontrar el índice Honeywell R4140G, preguntas frecuentes o problemas más comunes – son los apartados más buscados por los usuarios de cada manual de instrucciones.
2. Índice - listados de todos los consejos acerca de Honeywell R4140G que encontraremos en el documento
3. Consejos de uso de las funciones básicas del dispositivo Honeywell R4140G - que deben facilitarnos los primeros pasos durante el uso de Honeywell R4140G
4. Troubleshooting - una secuencia sistematizada de acciones que nos ayudará a diagnosticar los problemas más importantes con Honeywell R4140G
5. FAQ - las preguntas frecuentes
6. Datos de contacto Información acerca de cómo encontrar los datos de contacto del fabricante / servicio de Honeywell R4140G en cada país si no somos capaces de solucionar el problema por nuestra cuenta.

¿Tienes una pregunta acerca de Honeywell R4140G?

Utiliza el formulario que se encuentra abajo

Si con la ayuda del manual de instrucciones encontrado no has podido solucionar tu problema con Honeywell R4140G, haz una pregunta utilizando el formulario que se encuentra abajo. Si alguno de los usuarios ha tenido un problema parecido con Honeywell R4140G probablemente compartirá una forma de solucionarlo.

Copia el texto de la imagen

Comentarios (0)