    PRODUCT D A T A Copyright © 1996 Honeywell Inc. • All Rights Reserved X-XX UL 60-2337-3 R4140G Flame Safeguard Programming Controls APPLICA TION The R4140G Flame Safeguard Programmers provide flameout protection plus automatic sequencing of the burner motor (blower), firing rate motor , ignition, pilot valve, and main fuel valve(s) for commercia ...

  • Honeywell R4140G - page 2

    R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 2 ORDERING INFORMA TION When purchasing replacement and modernization products from your TRADELINE ® wholesaler or distributor , refer to the TRADELINE ® Catalog or price sheets for complete ordering number or specify order number . Order separately: 1. Flame detection system (amplifier a ...

  • Honeywell R4140G - page 3

    R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 3 NOTE: Allowable inrush can be up to ten times the pilot duty rating. EXAMPLE: Pilot duty rating = 50 V A. At 120V , running current is: 50 120 = 0.42A . Maximum allowable inrush is ten times 0.42A = 4.2A. Interlock Ratings: See T able 3. T able 3. Interlock Ratings. Ambient Operating T em ...

  • Honeywell R4140G - page 4

    R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 4 Fig. 1. Mounting dimensions of the Q520A wiring subbase in in. (mm). 13/64 (5) DIAMETER (4) (FOR MOUNTING ON 4 X 4 [102 X 102] JUNCTION BOX) 1-27/32 (47) 5/8 (16) (4) 7/8 (22) DIAMETER KNOCKOUT (2) 3-3/8 (86) 7 -1/16 (179) 7-3/16 (183) 15/16 (24) (2) 1-3/4 (45) 6-5/32 (156) 31/32 (25) (2) ...

  • Honeywell R4140G - page 5

    R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 5 Accessories: W136A T est Meter (includes 1 17053 Meter Connector Plug); has SPL position with damping for testing self- checking flame detection systems. 1 17053 Meter Connector Plug (for older W136A models). 123514A Flame Simulator (for use with R7247A Rectification Amplifiers). 123514B ...

  • Honeywell R4140G - page 6

    R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 6 OPERA TION Models with Preignition Interlocks Fig. 3 shows all contacts in the standby position (zero seconds). The opening and closing times are shown adjacent Fig. 3. Simplified schematic dia gram of R4140G1015 Programmer . 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 ...

  • Honeywell R4140G - page 7

    R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 7 Fig. 4. Timer sequence for R4140G1015 Programmer . Step-By-Step Operation (R4140G1015) Start And Prepurge 0 seconds — On a call for heat, the burner controller contacts close. If the limits and preignition interlocks are closed and flame relay 2K is not holding in, relay 1K pulls in thr ...

  • Honeywell R4140G - page 8

    R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 8 Ignition T rials 60 seconds — M4A closes; power is applied to terminals 5 and 6, energizing the ignition transformer and pilot valve (or main fuel valve(s) on terminal 7 if using direct spark ignition). — When a flame is detected, relay 2K pulls in, 2K2 opens, and the LS HTR stops hea ...

  • Honeywell R4140G - page 9

    R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 9 Fig. 5. Simplified schematic dia gram of R4140G1106 Programmer . 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 B R W B R W 14 12 11 10 9 L1 (HOT) L2 1 2 120V , 60 HZ POWER SUPPL Y UNDERLINED O OR C DENOTES SNAP A CTION OF CONT ACT . A TIMER CONT ACTS SNAP CLOSED . B CONT ...

  • Honeywell R4140G - page 10

    R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 10 Fig. 6. Timer sequence for R4140G1106 Programmer . Step-By-Step Operation (R4140G1106) Start and Prepurge 0 seconds — On a call for heat, the burner controller contacts close. If the limits and preignition interlocks are closed and flame relay 2K is not holding in, relay 1K pulls in th ...

  • Honeywell R4140G - page 11

    R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 11 Ignition T rials 60 seconds — M4A closes; power is applied to terminals 5 and 6, energizing the ignition transformer and pilot valve (or main fuel valve(s) on terminal 7 If using direct spark ignition). — When a flame is detected, relay 2K pulls in, 2K2 opens, and the LS HTR stops he ...

  • Honeywell R4140G - page 12

    R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 12 Fig. 7. Simplified schematic dia gram of R4140G1049 Programmer . 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 B R W B R W 14 12 11 10 9 L1 (HOT) L2 1 2 120V , 60 HZ POWER SUPPL Y UNDERLINED O OR C DENOTES SNAP A CTION OF CONT ACT . A TIMER CONT ACTS SNAP CLOSED ...

  • Honeywell R4140G - page 13

    R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 13 Fig. 8. Timer sequence for R4140G1049 Programmer . M10055 TIMER SECONDS TIMER DIAL TIMER MOTOR BURNER MOTOR (BLOWER) INTERRUPTED PILOT/IGNITION 5 SECOND IGNITION MAIN FUEL VALVE(S) (GAS OR OIL) FIRING RATE MOTOR SWITCHING ACTUAL DAMPER OPERATION 0 10 20 30 40 50 60 70 80 90 100 110 120 S ...

  • Honeywell R4140G - page 14

    R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 14 Ignition T rials 60 seconds — M4A closes; power is applied to terminals 18, 5, and 6, energizing the ignition transformer and pilot valve (or main fuel valve(s) on terminal 7 if using direct spark ignition). — When a flame is detected, relay 2K pulls in, 2K2 opens, and the LS HTR sto ...

  • Honeywell R4140G - page 15

    R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 15 Fig. 9. Simplified schematic dia gram of the R4140G1056 and R4140G1064 Programmer s. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 B R W B R W 14 12 11 10 9 L1 (HOT) L2 1 2 120V , 60 HZ POWER SUPPL Y UNDERLINED O OR C DENOTES SNAP A CTION OF CONT ACT . A TIMER C ...

  • Honeywell R4140G - page 16

    R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 16 Fig. 10. Timer sequence for R4140G1056 and R4140G1064 Programmer s. M10056 TIMER SECONDS TIMER DIAL TIMER MOTOR BURNER MOTOR (BLOWER) INTERMITTENT PILOT OR 1ST STAGE FUEL VALVE 10 SECOND INTERRUPTED PILOT/IGNITION 5 SECOND IGNITION MAIN FUEL VALVE(S) (GAS OR OIL) FIRING RATE MOTOR SWITCH ...

  • Honeywell R4140G - page 17

    R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 17 Ignition T rials 60 seconds — M4A closes; power is applied to terminals 18, 5, and 6, energizing the ignition transformer and pilot valve (or first stage fuel valve when using direct spark ignition). — When a flame is detected, relay 2K pulls in, 2K2 opens, and the LS HTR stops heati ...

  • Honeywell R4140G - page 18

    R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 18 Fig. 11. Simplified schematic dia gram of R4140G1171, R4140G122 and R4140G1114 Programmer s. 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 B R W B R W 14 12 11 10 9 L1 (HOT) L2 1 2 120V , 60 HZ POWER SUPPL Y UNDERLINED O OR C DENOTES SNAP A CTION OF CONT ACT . A ...

  • Honeywell R4140G - page 19

    R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 19 Fig. 12. Timer sequence for R4140G1171, R4140G1122 and R4140G1114 Programmer s. M10057 1 2 3 4 5 6 TERMINAL NUMBERS (CIRCLED). SLOPE DEPENDS ON MOTOR TIMING. TIMER STOPS AT 60 SECONDS UNTIL LOW FIRE PROVING SWITCH CLOSES. FIRING RATE MOTOR MODULATES UNDER CONTROL OF SERIES 90 CONTROLLER ...

  • Honeywell R4140G - page 20

    R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 20 Ignition T rials 70 seconds — M4A closes; power is applied to terminals 18, 5 and 6, energizing the ignition transformer and pilot valve (and terminal 7, main oil valve solenoid, if using direct spark ignition of oil). — When flame is detected, relay 2K pulls in, 2K2 opens, and the L ...

  • Honeywell R4140G - page 21

    R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 21 Fig. 13. Simplified schematic dia gram of R4140G1148 Programmer . 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 B R W B R W 14 12 11 10 9 L1 (HOT) L2 1 2 120V , 60 HZ POWER SUPPL Y UNDERLINED O OR C DENOTES SNAP A CTION OF CONT ACT . A TIMER CONT ACTS SNAP CLOSE ...

  • Honeywell R4140G - page 22

    R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 22 Fig. 14. Timer sequence for R4140G1148 Programmer . Step-By-Step Operation (R4140G1148) Start and Prepurge 0 seconds — On a call for heat, the burner controller contacts close. If the limits and start interlock(s) are closed and flame relay 2K is not holding in, relay 1K pulls in throu ...

  • Honeywell R4140G - page 23

    R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 23 Ignition T rials 60 seconds — M4A closes; power is applied to terminals 18, 5 and 6, energizing the ignition transformer and pilot valve (or main fuel valve(s) on terminal 7 if using direct spark ignition). — When a flame is detected, relay 2K pulls in, 2K2 opens, and the LS HTR stop ...

  • Honeywell R4140G - page 24

    R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 24 Fig. 15. Sample bloc k diagram of field wiring f or R4140G1007, R4140G1015 and R4140G1106 Programmer s. RECTIFYING FLAME ROD , RECTIFYING PHOT OCELL, OR INFRARED (LEAD SULFIDE) FLAME DETECTOR C7027A, C7035A, OR C7044A UL TRA VIOLET FLAME DETECTOR C7012A,C,E,F OR C7076A UL TRA VIOLET FLAM ...

  • Honeywell R4140G - page 25

    R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 25 Fig. 16. Sample bloc k diagram of field wiring f or R4140G1049, R4140G1056, R4140G1064, R4140G1114, R4140G1122, R4140G1148 and R4140G1171 Programmer s. RECTIFYING FLAME ROD , RECTIFYING PHOT OCELL, OR INFRARED (LEAD SULFIDE) FLAME DETECTOR C7027A, C7035A, OR C7044A UL TRA VIOLET FLAME DE ...

  • Honeywell R4140G - page 26

    R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 26 Optional Hookups f or T wo-Sta ge Switching or Intermittent Pilot/Ignition (Nonmodulating Oil Burners) If modulation of the firing rate is not required, an R4140G can be used to provide two-stage switching for an oil burner; also, an R4140G with interrupted pilot/ignition on terminal 6 c ...

  • Honeywell R4140G - page 27

    R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 27 M10061 TIMER SECONDS INTERRUPTED PILOT/IGNITION OR 1ST STAGE OIL VALVE 20 SECOND INTERRUPTED PILOT/IGNITION MAIN FUEL VALVE OR 2ND STAGE OIL VALVE 0 10 20 30 40 50 60 70 80 90 100 110 120 3 1 1 2 3 2 12 5 6 TERMINAL NUMBERS (CIRCLED). TIMER STOPS AT 104 SECONDS FOR THE RUN PERIOD WITH TH ...

  • Honeywell R4140G - page 28

    R4140G FLAME SAFEGU ARD PROGRAMMING CONTROLS 60-2337 — 3 28 Honeywell Europe S.A. 3 Avenue du Bourget B-1140 Brussels Belgium Honeywell Asia Pacific Inc. Room 3213-3225 Sun Hung Kai Centre No. 30 Harbour Road Wanchai Hong Kong Home and Building Control Honeywell Limited-Honeywell Limitée 35 Dynamic Drive Scarborough, Ontario M1V 4Z9 Honeywell La ...

メーカー Honeywell カテゴリー Car Amplifier

Honeywell R4140Gのメーカーから受け取ることができるドキュメントは、いくつかのグループに分けられます。その一部は次の通りです:
- #BRANDの図面#
- R4140Gの取扱説明書
- Honeywellの製品カード
- パンフレット
- またはHoneywell R4140Gの消費電力シール
それらは全部重要ですが、デバイス使用の観点から最も重要な情報は、Honeywell R4140Gの取扱説明書に含まれています。

取扱説明書と呼ばれる文書のグループは、Honeywell R4140Gの取り付け説明書、サービスマニュアル、簡易説明書、またはHoneywell R4140Gのユーザーマニュアル等、より具体的なカテゴリーに分類されます。ご必要に応じてドキュメントを検索しましょう。私たちのウェブサイトでは、Honeywell R4140Gの製品を使用するにあたって最も人気のある説明書を閲覧できます。

関連する取扱説明書

Honeywell R4140Gデバイスの取扱説明書はどのようなものですか?
取扱説明書は、ユーザーマニュアル又は単に「マニュアル」とも呼ばれ、ユーザーがHoneywell R4140Gを使用するのを助ける技術的文書のことです。説明書は通常、全てのHoneywell R4140Gユーザーが容易に理解できる文章にて書かれており、その作成者はその分野の専門家です。

Honeywellの取扱説明書には、基本的な要素が記載されているはずです。その一部は、カバー/タイトルページ、著作権ページ等、比較的重要度の低いものです。ですが、その他の部分には、ユーザーにとって重要な情報が記載されているはずです。

1. Honeywell R4140Gの説明書の概要と使用方法。説明書にはまず、その閲覧方法に関する手引きが書かれているはずです。そこにははHoneywell R4140Gの目次に関する情報やよくある質問、最も一般的な問題に関する情報を見つけられるはずです。つまり、それらはユーザーが取扱説明書に最も期待する情報なのです。
2. 目次。Honeywell R4140Gに関してこのドキュメントで見つけることができる全てのヒントの目次
3. Honeywell R4140Gデバイスの基本機能を使うにあたってのヒント。 Honeywell R4140Gのユーザーが使い始めるのを助けてくれるはずです。
4. トラブルシューティング。Honeywell R4140Gに関する最も重要な問題を診断し、解決するために役立つ体系化された手続き
5. FAQ。よくある質問
6. 連絡先。一人では問題を解決できない場合に、その国におけるHoneywell R4140Gのメーカー/サービスへの連絡先に関する情報。

Honeywell R4140Gについてご質問がありますか?

次のフォームを使用してください

見つけた説明書を読んでもHoneywell R4140Gの問題を解決できない場合、下記のフォームを使用して質問をしましょう。ユーザーのどなたかがHoneywell R4140Gで同様の問題を抱えていた場合、その解決方法を共有したいと考えるかもしれません。

画像のテキストを入力してください

コメント (0)