    SS-CPH90-150 ww w .goodmanmfg.c om 6/11 Supersedes 3/11 Standard Featur es • R-410Achlorine -freerefrigerant • High- eciencyscrollcompressor • Coppertube/aluminumncoils • Contactorwithlugs • High- capacity,st eel- casedlterdryer • Single -pointentry • 24-volt? ...

  • Goodman Mfg SS-CPH90-150 - page 2

    P roduCt S PeCifiCa tionS P roduCt S PeCifiCa tionS 2 ww w .goodmanmfg.c om SS-CPH90-150 n omenCla ture  C P H 090 045 3 B X X X           Brand F actoryInstalledOp<ons      ? ...

  • Goodman Mfg SS-CPH90-150 - page 3

    P roduCt S PeCifiCa tionS P roduCt S PeCifiCa tionS SS-CPH90-150 ww w .goodmanmfg.c om 3 P roduCt S PeCifiCa tionS — 7½ t onS CPH090 ***3B*** CPH090 ***4B*** CPH090 ***7B*** Cooling Cap a city T otal BTU/h 90,000 90,000 90,000 Sensible BTU/h 65,700 65,700 65,700 EER / IEER 11.5 / 11.2 11.5 / 11.2 11.5 / 11.2 IPL V 12.30 12.30 12.30 Decibels 83 8 ...

  • Goodman Mfg SS-CPH90-150 - page 4

    P roduCt S PeCifiCa tionS P roduCt S PeCifiCationS 4 ww w .goodmanmfg.c om SS-CPH90-150 P roduCt S PeCifiCa tionS — 8½ t onS CPH102 ***3B*** CPH102 ***4B*** CPH102 ***7B*** Cooling Cap acity T otal, BTU/h 102,000 102,000 102,000 Sensible BTU/h 73,440 73,440 73,440 EER / IEER 11.1 / 11.2 11.1 / 11.2 11.1 / 11.2 Decibels 83 83 83 ARI Ref erence #s ...

  • Goodman Mfg SS-CPH90-150 - page 5

    P roduCt S PeCifiCa tionS P roduCt S PeCifiCationS SS-CPH90-150 ww w .goodmanmfg.c om 5 P roduCt S PeCifiCa tionS — 1 0 t onS CPH120 ***3B*** CPH120 ***4B*** CPH120 ***7B*** Cooling Cap acity T otal BTU/h 118,000 118,000 118,000 Sensible BTU/h 87,300 87,300 87,300 EER / IEER 11.5 / 11.5 11.5 / 11.5 11.5 / 11.5 Decibels 83 83 83 Hea ting Cap acity ...

  • Goodman Mfg SS-CPH90-150 - page 6

    P roduCt S PeCifiCa tionS P roduCt S PeCifiCationS 6 ww w .goodmanmfg.c om SS-CPH90-150 P roduCt S PeCifiCa tionS — 12½ t onS CPH150XXX 3BXXX CPH150XXX 4BXXX CPH150XXX 7BXXX Cooling Cap acity T otal, BTU/h 146,000 146,000 146,000 Sensible BTU/h 102,200 102,200 102,200 EER / IPL V 10.8 / 11.2 10.8 / 11.2 10.8 / 11.2 Decibels 83 83 83 ARI Ref eren ...

  • Goodman Mfg SS-CPH90-150 - page 7

    P roduCt S PeCifiCa tionS P roduCt S PeCifiCationS SS-CPH90-150 ww w .goodmanmfg.c om 7 e xP anded H eating d a ta CPH090 Outdoor Ambient Temper a ture 65 60 55 50 47 45 40 35 30 25 20 17 15 10 5 0 -5 -10 MBh 114.4 108.3 101.9 95.3 91.0 88.2 81.9 75.5 70.5 65.0 59.9 56.6 54.5 48.9 43.3 37.8 32.2 26.4 T/ R 35.3 33.4 31.5 29.4 28.1 27.2 25.3 23.3 21. ...

  • Goodman Mfg SS-CPH90-150 - page 8

    P roduCt S PeCifiCa tionS P roduCt S PeCifiCationS 8 ww w .goodmanmfg.c om SS-CPH90-150 e xP anded C ooling d at a — 7½ t onS Outdoor Ambient Temper a ture 65 75 85 95 105 115 Entering Indoor Wet Bulb Temper a ture IDB Airflow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 70 3375 MBh 88.2 91.4 100.2 - 86.1 89.3 97.8 - 8 ...

  • Goodman Mfg SS-CPH90-150 - page 9

    P roduCt S PeCifiCa tionS P roduCt S PeCifiCationS SS-CPH90-150 ww w .goodmanmfg.c om 9 e xP anded C ooling d at a — 7½ t onS ( Cont .) Outdoor Ambient Temper a ture 65 75 85 95 105 115 Entering Indoor Wet Bulb Temper a ture IDB Airflow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 80 3375 MBh 91.3 93.3 99.7 106.5 89.2 ...

  • Goodman Mfg SS-CPH90-150 - page 10

    P roduCt S PeCifiCa tionS P roduCt S PeCifiCationS 10 ww w .goodmanmfg.c om SS-CPH90-150 e xP anded C ooling d at a — 8½ t onS Outdoor Ambient Temper a ture 65 75 85 95 105 115 Entering Indoor Wet Bulb Temper a ture IDB Airflow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 70 3820 MBh 100.0 103.6 113.5 - 97.6 101.2 110. ...

  • Goodman Mfg SS-CPH90-150 - page 11

    P roduCt S PeCifiCa tionS P roduCt S PeCifiCationS SS-CPH90-150 ww w .goodmanmfg.c om 11 e xP anded C ooling d at a — 8½ t onS ( Cont .) Outdoor Ambient Temper a ture 65 75 85 95 105 115 Entering Indoor Wet Bulb Temper a ture IDB Airflow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 80 3820 MBh 103.5 105.7 112.9 120.7 1 ...

  • Goodman Mfg SS-CPH90-150 - page 12

    P roduCt S PeCifiCa tionS P roduCt S PeCifiCationS 12 ww w .goodmanmfg.c om SS-CPH90-150 e xP anded C ooling d at a — 1 0 t onS Outdoor Ambient Temper a ture 65 75 85 95 105 115 Entering Indoor Wet Bulb Temper a ture IDB Airflow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 70 4500 MBh 115.6 119.8 131.3 - 112.9 117.1 128 ...

  • Goodman Mfg SS-CPH90-150 - page 13

    P roduCt S PeCifiCa tionS P roduCt S PeCifiCationS SS-CPH90-150 ww w .goodmanmfg.c om 13 e xP anded C ooling d at a — 1 0 t onS ( Cont .) Outdoor Ambient Temper a ture 65 75 85 95 105 115 Entering Indoor Wet Bulb Temper a ture IDB Airflow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 80 4500 MBh 119.7 122.3 130.7 139.7 1 ...

  • Goodman Mfg SS-CPH90-150 - page 14

    P roduCt S PeCifiCa tionS P roduCt S PeCifiCationS 14 ww w .goodmanmfg.c om SS-CPH90-150 e xP anded C ooling d at a — 12½ t onS Outdoor Ambient Temper a ture 65 75 85 95 105 115 Entering Indoor Wet Bulb Temper a ture IDB Airflow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 70 4725 MBh 143.1 148.3 162.5 - 139.7 144.8 15 ...

  • Goodman Mfg SS-CPH90-150 - page 15

    P roduCt S PeCifiCa tionS P roduCt S PeCifiCationS SS-CPH90-150 ww w .goodmanmfg.c om 15 e xP anded C ooling d at a — 12½ t onS ( Cont .) Outdoor Ambient Temper a ture 65 75 85 95 105 115 Entering Indoor Wet Bulb Temper a ture IDB Airflow 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 59 63 67 71 80 4725 MBh 148.1 151.3 161.7 172.8 ...

  • Goodman Mfg SS-CPH90-150 - page 16

    P roduCt S PeCifiCa tionS P roduCt S PeCifiCationS 16 ww w .goodmanmfg.c om SS-CPH90-150 a irfl ow d a ta — 7½ t onS St andard Bel t Drive — Down Sho t ESP , In H 2 O T urns Open 012345 CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP 0.1 3617 704 1.07 3293 653 0.84 0.3 3541 749 1.15 3179 704 0.88 2757 656 0.66 0.5 3447 ...

  • Goodman Mfg SS-CPH90-150 - page 17

    P roduCt S PeCifiCa tionS P roduCt S PeCifiCationS SS-CPH90-150 ww w .goodmanmfg.c om 17 a irfl ow d a ta — 8½ t onS St andard Bel t Drive — Down Sho t ESP , In H 2 O T urns Open 012345 CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP 0.1 3467 701 1.04 3143 650 0.81 0.3 3391 746 1.12 3029 701 0.85 2607 653 0.63 0.5 3297 ...

  • Goodman Mfg SS-CPH90-150 - page 18

    P roduCt S PeCifiCa tionS P roduCt S PeCifiCationS 18 ww w .goodmanmfg.c om SS-CPH90-150 a irfl ow d a ta — 1 0 t onS St andard Bel t Drive — Down sho t ESP , In H 2 O T urns Open 012345 CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP CFM RPM BHP 0.2 4629 774 1.76 4269 733 1.42 0.4 4539 824 1.86 4198 781 1.53 3797 735 1.21 0.6 4511 ...

  • Goodman Mfg SS-CPH90-150 - page 19

    P roduCt S PeCifiCa tionS P roduCt S PeCifiCationS SS-CPH90-150 ww w .goodmanmfg.c om 19 a irfl ow d a ta — 12½ t onS St andard Bel t Drive --- Down Sho t ESP (in W .C.) T urns Open 0 1 2 3 4 5 CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP CFM BHP 0.2 5378 2.35 4967 1.92 4710 1.59 4512 1.33 0.4 5514 2.92 5349 2.56 4750 1.97 4583 1.71 4319 1.40 4030 1. ...

  • Goodman Mfg SS-CPH90-150 - page 20

    P roduCt S PeCifiCa tionS P roduCt S PeCifiCationS 20 ww w .goodmanmfg.c om SS-CPH90-150 H ea t k it e leCtriCal d a t a — 7½ t onS m inimum a irflow for e leCtriC H ea t Hea ter Size (kW) Minimum CFM 15 3,000 30 3,000 43 3,000 kW Correction F actor f or 3-Phase Units Suppl y Vol t age 240 230 220 210 208 Correction F actor 1 0.93 0.82 0.78 0.76 ...

  • Goodman Mfg SS-CPH90-150 - page 21

    P roduCt S PeCifiCa tionS P roduCt S PeCifiCationS SS-CPH90-150 ww w .goodmanmfg.c om 21 H ea t k it e leCtriCal d a t a — 8½ t onS Model and Hea t Kit Usage MCA¹ a t 240V MOP² (amps) a t 240V Actu al kW a t 240V Recommended Airflow Range (Downsho t) Recommended Airflow Range (Horizont al) CPH102***3B*** 43 50 EHK3-16 88 90 15 3400 - 3825 CFM ...

  • Goodman Mfg SS-CPH90-150 - page 22

    P roduCt S PeCifiCa tionS P roduCt S PeCifiCationS 22 ww w .goodmanmfg.c om SS-CPH90-150 H ea t k it e leCtriCal d a t a — 1 0 t onS k w C orreCtion f aCt or kW Corre ction Fa ctor (for 1- & 3-Pha se Units) Supply V oltage 240 230 220 210 208 Correcon F actor 1 0.93 0.82 0.78 0.76 kW Corre ction Fa ctor for 480V Unit s Actual V oltage 460 ...

  • Goodman Mfg SS-CPH90-150 - page 23

    P roduCt S PeCifiCa tionS P roduCt S PeCifiCationS SS-CPH90-150 ww w .goodmanmfg.c om 23 H ea t k it e leCtriCal d a t a — 12½ t onS kW Corre ction Fa ctor for 1- & 3-Pha se Units Suppl y V ol t age 240 230 220 210 208 Corre ction Fa ctor 1 0.93 0.82 0.78 0.76 kW Corre ction Fa ctor for 480V Unit s Suppl y V ol t age 460 440 430 Corre ction ...

  • Goodman Mfg SS-CPH90-150 - page 24

    P roduct S Pecifica tionS P roduct S PecificationS 24 ww w .goodmanmfg.c om SS-CPH90-150 d imenSionS 20 APPENDIX C UNIT DIMENSIONS Horizontal Discharge Vertical Discharge (Bottom of Unit) RETURN SUPPL Y 13 7/ 8” 28 3/ 8” 7 3/8” 12 5/ 8” 6 1/4 ” 36 3/ 8” 5 7/8 ” RETURN SUP PL Y 5 3/8” 7 1/2” 6 1/2” 99 1/ 8” 61 3/ 4” Y NOTE Fo ...

  • Goodman Mfg SS-CPH90-150 - page 25

    P roduct S Pecifica tionS P roduct S PecificationS SS-CPH90-150 ww w .goodmanmfg.c om 25 48” 36” Min. 48” 48” 75” u nit c learanceS e lectrical e ntrance l oca tionS 11⅝” 10 3 / 16 ” 3” Low -V oltage Entr ance High-V oltage En trance Dimples Mark Drill Locaons Maintain an adequate clearance around the unit for saf ety, service, ...

  • Goodman Mfg SS-CPH90-150 - page 26

    P roduct S Pecifica tionS P roduct S PecificationS 26 ww w .goodmanmfg.c om SS-CPH90-150 r oof c urb i nSt alla tion — r igging Pr ovisions for forks hav e been included in the unit base frame. No other fork locations are appr oved. • Unit must be lifted by the four lifting holes located at the base frame corners. • Lifting cables shoul ...

  • Goodman Mfg SS-CPH90-150 - page 27

    P roduCt S PeCifiCa tionS P roduCt S PeCifiCationS SS-CPH90-150 ww w .goodmanmfg.c om 27 r oof C urB i nSt alla tion ( Cont .) Curb installations must comply with local codes and should follow the establishedguidelinesoftheNationalRoongContractorsAssociation. Pr operunit installation ...

  • Goodman Mfg SS-CPH90-150 - page 28

    P roduCt S PeCifiCa tionS P roduCt S PeCifiCationS 28 ww w .goodmanmfg.c om SS-CPH90-150 w iring d ia gram — CPH090- 120***3B/ 4B ( for modelS witH Serial numBerS 090 7 and Below ) Wiring is subject to change. Alwa ys ref er to the wiring diagram or the unit for the most up-t o-date wiring. ⚠ W arning High Volt age:   ...

  • Goodman Mfg SS-CPH90-150 - page 29

    P roduCt S PeCifiCa tionS P roduCt S PeCifiCationS SS-CPH90-150 ww w .goodmanmfg.c om 29 w iring d ia gram — CPH090- 120***3B/ 4B ( Cont .) ( for modelS witH Serial numBerS 090 7 and Below ) Wiring is subject to change. Alwa ys ref er to the wiring diagram or the unit for the most up-t o-date wiring. ⚠ W arning High Volt age:  ? ...

  • Goodman Mfg SS-CPH90-150 - page 30

    P roduCt S PeCifiCa tionS P roduCt S PeCifiCationS 30 ww w .goodmanmfg.c om SS-CPH90-150 w iring d ia gram — CPH090- 120***3B/ 4B/ 7B*** TB1 OR BR REPLACE JUMP ER WI TH SMOKE/FIRE DETECTOR RD C 3 BL 1 PK 240 460 BL OR RD GR BK OR RD OR RD RD RD 6 GND COM HVDR R DFT1 L3 BK T3 YL NOTE 3 PLF NC NO BK UP RD GR BK 2 C WH C 8 L2 K1 BK BR DF2 C YL SPEED ...

  • Goodman Mfg SS-CPH90-150 - page 31

    P roduCt S PeCifiCa tionS P roduCt S PeCifiCationS SS-CPH90-150 ww w .goodmanmfg.c om 31 w iring d ia gram — CPH090- 120***3B/ 4B/ 7B*** ( Cont .) R EBTDR BC R HVDR Y RVC1 SEE UNIT RATING PLATE FOR TYPE AND SIZE 5 OF OVER CU RRENT PROTECTION 4 BLOW ER CONTACTOR COMPRESSOR CONTACTOR CONDENSER MOT OR CONDENSER M OTOR CONTACTOR COMPRESSOR DEFROST CO ...

  • Goodman Mfg SS-CPH90-150 - page 32

    P roduCt S PeCifiCa tionS P roduCt S PeCifiCationS 32 ww w .goodmanmfg.c om SS-CPH90-150 TB1 OR BR REPLACE JUMP ER WITH SMOKE/FIRE DE TECTOR RD C 3 BL 1 PK 240 460 BL OR RD GR BK OR RD OR RD RD RD 6 GND COM HVDR R DFT1 L3 BK T3 YL NOTE 3 PLF NC NO BK UP RD GR BK 2 C WH C 8 L2 K1 BK BR DF2 C YL SPEED R RVC1 DC BK RD YL L1 O 5 7 BL K1 BK M1 LPS2 XFMR ...

  • Goodman Mfg SS-CPH90-150 - page 33

    P roduCt S PeCifiCa tionS P roduCt S PeCifiCationS SS-CPH90-150 ww w .goodmanmfg.c om 33 w iring d ia gram — CPH1 50***3B/ 4B/ 7B*** ( Cont .) R EBTDR BC R HVDR Y RVC1 SEE UNIT RATING PLATE FOR TYPE AN D SIZE 5 OF OVER CUR RENT PROTECTION 4 BLOW ER CONTACTOR COMPRESSOR CO NTACTOR CONDENSER MOTOR CONDENSER MO T OR CONTACTOR COMPRESSOR DEFROST CONT ...

  • Goodman Mfg SS-CPH90-150 - page 34

    P roduCt S PeCifiCa tionS P roduCt S PeCifiCationS 34 ww w .goodmanmfg.c om SS-CPH90-150 a CCeSSorieS Item # Description Fits Model Sizes 14CURB90150 Roof Curb 14" T all 7½-12½ tons 25FD90150 25% Manual Fresh Air Damper 7½-12½ tons 25MFD90150 25% Motoriz ed Fresh Air Damper 7½-12½ tons BRD3672 Horizontal Bar ometric Relief Damper (two r ...

  • Goodman Mfg SS-CPH90-150 - page 35

    P roduCt S PeCifiCa tionS P roduCt S PeCifiCationS SS-CPH90-150 ww w .goodmanmfg.c om 35 n o teS ...

  • Goodman Mfg SS-CPH90-150 - page 36

    P roduct S Pecifica tionS P roduct S PecificationS 36 ww w .goodmanmfg.c om SS-CPH90-150 Goodman Manufacturing Company, L.P ., reser ves the right to discontinue, or change at an y time, specications or designs without noticeorwithoutincurringobligations.©2010•GoodmanManufacturingCompany,L.P .•? ...

Fabricant Goodman Mfg Catégorie Air Conditioner

Les documents que nous recevons du fabricant de l'appareilGoodman Mfg SS-CPH90-150 peuvent être divisés en plusieurs groupes. Ceux-ci sont, entre autres:
- dessins techniques Goodman Mfg
- manuels d’utilisations SS-CPH90-150
- fiches produit Goodman Mfg
- dépliants
- ou étiquettes-énergie Goodman Mfg SS-CPH90-150
Tous sont importants, mais les informations les plus importantes du point de vue de l'utilisation de l'appareil se trouvent dans le manuel d’utilisation Goodman Mfg SS-CPH90-150.

Un groupe de documents appelé manuels d’utilisation est également divisé en types plus spécifiques, tels que: Manuels d’installation Goodman Mfg SS-CPH90-150, manuels d’entretien, brefs manuels ou manuels de l’utilisateur Goodman Mfg SS-CPH90-150. Selon vos besoins, vous devriez chercher le document dont vous avez besoin. Sur notre site, vous pouvez voir le manuel le plus populaire d’utilisation du produit Goodman Mfg SS-CPH90-150.

Manuels d’utilsiation similaires

Manuel d’utilisation complet de l’appareil Goodman Mfg SS-CPH90-150, quelle devrait-elle être?
Le manuel d’utilisation, également appelé le mode d’emploi, ou tout simplement le manuel, est un document technique destiné à aider à utiliser Goodman Mfg SS-CPH90-150 par les utilisateurs. Des manuels sont généralement écrits par un rédacteur technique, mais dans un langage accessible à tous les utilisateurs Goodman Mfg SS-CPH90-150.

Le manuel d’utilisation complet Goodman Mfg, devrait inclure plusieurs éléments de base. Certains d'entre eux sont moins importants, tels que: la couverture / page de titre ou pages d'auteur. Cependant, la partie restante, devrait nous fournir des informations importantes du point de vue de l'utilisateur.

1. Introduction et des conseils sur la façon d'utiliser le manuel Goodman Mfg SS-CPH90-150 - Au début de chaque manuel, nous devrions trouver des indices sur la façon d'utiliser le document. Il doit contenir des informations sur l'emplacement de la table des matières Goodman Mfg SS-CPH90-150, FAQ ou des problèmes les plus fréquents - les points qui sont les plus souvent recherchés par les utilisateurs de chaque manuel
2. Table des matières - index de tous les conseils pour lGoodman Mfg SS-CPH90-150 qui peuvent être trouvés dans le document courant
3. Conseils sur la façon d'utiliser les fonctions de base de l’appareil Goodman Mfg SS-CPH90-150 - qui devraient nous aider dans les premières étapes lors de l'utilisation Goodman Mfg SS-CPH90-150
4. Troubleshooting - séquence systématique des activités qui nous aideront à diagnostiquer et ensuite résoudre les principaux problèmes de Goodman Mfg SS-CPH90-150
5. FAQ - questions fréquemment posées
6. Détails du contact Informations sur l'endroit où chercher le contact avec le fabricant / service Goodman Mfg SS-CPH90-150 dans un pays donné, si le problème ne peut être résolu par nous-mêmes.

Avez-vous une question à propos de Goodman Mfg SS-CPH90-150?

Utiliser le formulaire ci-dessous

Si vous n’avez pas résolu votre problème avec Goodman Mfg SS-CPH90-150, avec l'aide du manuel que vous avez trouvé, posez une question en utilisant le formulaire ci-dessous. Si un utilisateur a eu un problème similaire avec Goodman Mfg SS-CPH90-150 il est probable qu’il a envie de partager la façon de le résoudre.

Réécrire le texte de l'image

Commentaires (0)