Manuel d’utilisation Mitsubishi ETH-1000

36 pages 7.02 mb
Télécharger

Aller à la page of 36

Summary
  • Mitsubishi ETH-1000 - page 1

    eth1000_large.jpg Using ICC E TH-1000 EtherNet/IP Interface w ith Mitsubishi i Q PLC ...

  • Mitsubishi ETH-1000 - page 2

    i Contents Contents ..................................................................................................... .............................................................. i FURT HER READING REF ERENCE LI ST ......................................................................................... ...................... ii Chapter 1 Int ...

  • Mitsubishi ETH-1000 - page 3

    ii FURTHER RE A DING REFE RENCE LIST ( Mitsub ishi Q Correspond ing MELSE C Comm unication Protocol R eference Manua l SH(NA)-08000 8-K QnUCPU Us er’s Manual C ommunic ation via Built-in Ether net Port SH(N A)-080811ENG-B Q Correspond ing Ethernet I nterface Modul e User’s Ma nual (Basic) SH ( NA)-0800 09-N ICC Instruction Ma nual: ETH -1000 Mu ...

  • Mitsubishi ETH-1000 - page 4

    iii This Page is intentionall y left blank! ...

  • Mitsubishi ETH-1000 - page 5

    1-1 Chapter 1 Introduction This document provides instruc tions and ex amples on how t o configure a s y stem c onsists of Rockwell ControlLogix PLC, an ICC ET H-1000 Gat eway, and Mitsubish i iQ PLC s y stem . An Example of the system configurat ion is shown in Fi gure 1 below. EtherNet/ I P M C Prot ocol G at eway Et h er net N etwork Switch R oc ...

  • Mitsubishi ETH-1000 - page 6

    2-1 Chapter 2 System Overview A Verification Sy stem is used as a test bed for verif ying the steps docum ented in this Quick Start guide. The Verification System is s hown in Figure 2 be low with the IP address ass ignments of al l the devices. Netgear Switch Monitoring Laptop 2 192.168.1.5 ControlLogix 192.168.1.30 ICC 192.168.1.102 iQ (Built-in ...

  • Mitsubishi ETH-1000 - page 7

    3-1 Chapter 3 Connecting Devices to the Network The steps of configuring th e IP addresses of the ControlLo gix PLC system , the ICC ETH -1000 module, an d the PLC are doc umented in th is chapter. 3.1 Changing th e IP Address of the ControlL ogix System The minimum configuration of a ControlLogix syst em consists of a ControlLogix c hassis (e.g. 1 ...

  • Mitsubishi ETH-1000 - page 8

    3-2 4. Right-Click on the ENBT M odule and se lect “Module C onfiguration” from the drop down list: 5. Under the “P ort Configur ation” tab, se lect the Net work Configurati on Type to be “Static”, and o ne can m odify the IP ad dress and the Ne twork Mask to the desired values. C lick “OK” and sa ve the new IP ad dress configuratio ...

  • Mitsubishi ETH-1000 - page 9

    3-3 6. Once the n ew I P addres s is set, it is ver y likely ( depending on wha t IP address and Net work m ask were as signed to the E NBT m odule) that the C onfiguration PC wi ll no longer be abl e to comm unicate with the ENBT module. The IP a ddress of the Conf iguration P C will need to be changed to be in the sam e subnet of the ENBT m odule ...

  • Mitsubishi ETH-1000 - page 10

    3-4 2. Click the “Auto Conn ect” b utton, a nd the ETH- 1000 module w ill b e con nected, and the screen will be populat ed with the cur rent information: The proper devic e type is sho wn with a green LED lit showing the co nnection has been established. The f irmware type, version, and Database t ype are als o shown on the sc reen. 3. The use ...

  • Mitsubishi ETH-1000 - page 11

    3-5 5. After the do wnload, the s ystem wi ll need to be reset fo r the changes to take ef fect. Click “Y es” to the pop-up m essage and the ETH-1000 will go through the r eset sequence 6. After the ET H-1000 system reboot, the screen sho uld show the ne w IP address . In th is example, the IP addres s was change d to 192.168.5.1 90. 1 Introduc ...

  • Mitsubishi ETH-1000 - page 12

    3-6 3.3 Changing th e IP Address es of the iQ PLC Built-in Ethern et Port The f ollowing are steps to c hange the IP a ddress of the iQ PLC Built-in Ethernet Port: 1. Open the GX W orks2 on the C onfiguration PC a nd create a ne w pr oject for the appropriate CPU Module (e.g. Q 13UDEH in t his example). 2. Select the PLC Param eter on th e Pr oject ...

  • Mitsubishi ETH-1000 - page 13

    3-7 c. Click the Open Setting box and enter the first channel as MC Protocol with a proper Host Station Por t number (In th is example, the Port Number is set at Hex 5001) 3. Download th e param eter settings to the PLC . 1 Introduction 2 System Overview 3 Devices to the Network 4 ControlLogix PLC Project Configuration 5 ETH-1000 Configuration 6 Us ...

  • Mitsubishi ETH-1000 - page 14

    3-8 3.4 Configuring the External Eth ernet Mod ule in the iQ System W hen app lication requires, an externa l E thernet modul e c an be added to the syst em and comm unicating to the iQ CPU. This sect ion describes the co nfiguration of a QJ7 1E71-100 modu le to be used in the comm unication with a CLX through the ICC ETH-1000 gateway. 1. Select th ...

  • Mitsubishi ETH-1000 - page 15

    3-9 2. At the “Ethern et Operatio n Setting windo w”, one can config ure the IP addre ss of the Ethernet module. a. Set the Com munication Dat a Code to Binar y b. Check the “Enable Online Change” check box c. Select the “ Initial Tim ing” to be A lways wait f or OPEN (Com munication pos sible at ST OP time). T his is a crit ical s tep ...

  • Mitsubishi ETH-1000 - page 16

    3-10 3. At the Net work Parameter Setting window, click “Open Setting” a nd op en the wind ow be low a nd enter the par ameters as shown: a. Configure the Host Station Port Num ber to matc h the C onnection Object port number configured in the ICC ET H-1000. ...

  • Mitsubishi ETH-1000 - page 17

    4-1 Chapter 4 ControlLogix PLC P roj ect Configuration The configuratio n s teps of a ControlL ogix pr oject are described this Chapter. T hese steps are us ed to comm unicate with an ICC ETH -1000 module. It is assum ed that the user has basic k nowledge in using RSLogix5000 software to perform the basic configurati on steps. 4.1 A dding the 1756 ...

  • Mitsubishi ETH-1000 - page 18

    4-2 3. In the “Select Module” pop- up window, cho ose the “Com munications” 4. Then select th e proper m odule 1756 ENBT ...

  • Mitsubishi ETH-1000 - page 19

    4-3 5. Then s elect the Major Revision level of the ENBT firm ware. In the Verification System, the m ajor revision le vel of the ENBT module is 2. 6. Enter th e proper Name, Slot Location, Revision Level and IP Addres s of the ENBT module. In the Verification System, the module nam e is set at CSC_EIP, the revision firm ware level is 2.3, the modu ...

  • Mitsubishi ETH-1000 - page 20

    4-4 7. Click “O K” to accept t he configurat ion and m ake no add itional conf iguration changes to the “Connection” t ab. Sim ply click “OK” again to accept the configuration. 4.2 A dding the ICC M odule The following st eps ar e us ed to add the I CC m odule f or c o mm unication us ing I/O Messag ing ( or Im plicit Messaging m ethod) ...

  • Mitsubishi ETH-1000 - page 21

    4-5 2. Select the “C ommunicatio ns” and expa nd the tree for additional sel ection. 3. Choose the Ethernet-Mod ule Generic Ether net Module 1 Introduction 2 System Overview 3 Devices to the Network 4 ControlLogix PLC Project Configuration 5 ETH-1000 Configuration 6 Using EtherNet/IP Explicit Messaging 7 Terminology ...

  • Mitsubishi ETH-1000 - page 22

    4-6 4. Double C lick on the se lection an d c onfigure the I CC module according ly. T his is a critica l configurat ion step to e nsure the ETH-1000 will w ork properly in the s ystem as the application requires. Please a lso cons ult the ICC ET H-1000 Us er’s Manua l carefull y about t he configur ation of these item s. a. Configure the “C om ...

  • Mitsubishi ETH-1000 - page 23

    4-7 5. Configure the RPI to 10.0 ms. 6. Select “OK” to accept the c onfiguration an d complete the ICC Module C onfiguration. 7. Double c lick on the “Co ntroller T ags” selec tion, and the foll owing tags are a utomatica lly created for the ICC ET H-1000 m odule: 1 Introduction 2 System Overview 3 Devices to the Network 4 ControlLogix PLC ...

  • Mitsubishi ETH-1000 - page 24

    4-8 a. 248 integer tags were created for CSC_ICC_ ETH1000_INT :I. These are the t ag locations where I CC will transf er the data to the ControlLog ix us ing Implicit Messag e prot ocol ev ery RPI. b. 248 integer t ags were created f or CSC _ICC_ETH 1000_INT:O. T hese are the t ag l ocations where data will be sent to I CC ETH-1000 through Im plici ...

  • Mitsubishi ETH-1000 - page 25

    5-1 Chapter 5 ETH-1000 Configuration The s teps to configur e th e ETH-1000 m odule to work with the ControlLog ix PLC usin g Et herNet/IP Im plicit Messaging and Mitsubish i controllers usin g MC Proto col are docum ented. Configuring the Validation System as sh own in Figur e 2 is used as the exam ple. Some param eters will n eed different v alue ...

  • Mitsubishi ETH-1000 - page 26

    5-2 2. Select th e EtherNet/I P t ab of the ICC Conf iguration scr een an d d efine the ICC Database locations where dat a items w ill be exc hanged between the Co ntrolLogix PL C and th e ICC module throug h the Implicit Mess aging protoc ol. In this exam ple, the “Prod uce Data Start Addres s” of the ICC m odule is set at Databas e Location 0 ...

  • Mitsubishi ETH-1000 - page 27

    5-3 The database addr esses in the ICC ar e us ed t o address “by te” data locat ions. Thus, 248 wor ds will take up 49 6 database addr esses. 3. Select the “M onitor” tab and c heck the “Dis play Usage ” c heckbox to sho w the DB m emor y loc ations that are conf igured for use by both the Pro duced and Consumed data . 5.2 Configuring ...

  • Mitsubishi ETH-1000 - page 28

    5-4 2. Enter the IP address of the controller that will be co nnected. The IP is 192.16 8.1.40 for this exam ple 3. Enter the Port Number in d ecimal. T he Port is 20481 or 0x 5001 for this exam ple. 4. Hit “Create” af ter the inf ormation is entered a nd the Co nnection Object is shown as below. 5.2.2. Configu ring Service Obje cts In the Veri ...

  • Mitsubishi ETH-1000 - page 29

    5-5 5. Enter the Start ing Point of the Data Registers where the data item s will be written i nto. I n this exam ple, the Starting Poin t is “12268.” 6. Enter the n umber of words to b e transferr ed in the “Nu m W ords” dialog box. In this exam ple, the number of words is “20.” 7. Enter the Datab ase Address (Datab ase Addr.) of the I ...

  • Mitsubishi ETH-1000 - page 30

    5-6 9. Repeat th e steps 1-8 to de fine the other three s ervice obj ects to perf orm the tran sfers between ICC and iQ PLC. a. Define the Service Object t o read 20 Data Registers to ICC b. Define the Service Object t o write 10 W ords to Internal R elay ...

  • Mitsubishi ETH-1000 - page 31

    5-7 c. Define the Service Object t o read 10 words of Link Rel ay to ICC 1 Introduction 2 System Overview 3 Devices to the Network 4 ControlLogix PLC Project Configuration 5 ETH-1000 Configuration 6 Using EtherNet/IP Explicit Messaging 7 Terminology ...

  • Mitsubishi ETH-1000 - page 32

    5-8 5.2.3. Configu ring the Connecti on Object for Q J71E71 Ethernet Modu le Repeat steps docum ented in S ections 5.2.1and 5.2 .2 to configure t he Connec tion and Service objects to comm unicate to the ext ernal Ethernet m odule in the system . 1. Creat a Connecti on Obj ect first with name Connection2. Enter the IP addr ess of the Ethernet modul ...

  • Mitsubishi ETH-1000 - page 33

    5-9 5.2.4. Calculating the ICC ET H-1000 DB A ddres ses One of the most important steps in config uring a serv ice objec t is to de termine the D atabase Address that n eeds to be entered. Since the ICC ET H-1000 DB is a “shared databas e” bet ween Eth erNet/IP and MELSEC pr otocols, one has to def ine carefull y which wa y the d ata item s wil ...

  • Mitsubishi ETH-1000 - page 34

    6-1 Chapter 6 Using EtherNe t/IP Explicit Messaging The ControlLogix PLC can com municate with the Mitsub ishi i Q PLC using E IP Explicit Messaging format through the ICC ETH-1000 gateway. The communication is accom plished throu gh the use of MSG instructions in RSLogix5 000. Ref er to Sections 11.1.4.5, 11.1.4. 6, 8.7.5.1 of the “ Instruction ...

  • Mitsubishi ETH-1000 - page 35

    7-1 Chapter 7 Terminolog y Implicit (I/O Data) Messaging Connecti ons are established to mo ve appli cation-specifi c I/O data at regular intervals. Th ese conne ctions often are s et u p a s one-t o-many rel ationship s in order to tak e fu ll ad v antage of t he p roducer- consume r m ulticast mod el. Impli cit messagi ng uses UDP/ IP r esources ...

  • Mitsubishi ETH-1000 - page 36

    Rev-1 Revisions July 2009 – Document c reated and Rel eased, Vers ion 1.0 October 20 09 – Minor revis ion to wording t hroughout t he docum ent, Version 1.1 ...

Fabricant Mitsubishi Catégorie Switch

Les documents que nous recevons du fabricant de l'appareilMitsubishi ETH-1000 peuvent être divisés en plusieurs groupes. Ceux-ci sont, entre autres:
- dessins techniques Mitsubishi
- manuels d’utilisations ETH-1000
- fiches produit Mitsubishi
- dépliants
- ou étiquettes-énergie Mitsubishi ETH-1000
Tous sont importants, mais les informations les plus importantes du point de vue de l'utilisation de l'appareil se trouvent dans le manuel d’utilisation Mitsubishi ETH-1000.

Un groupe de documents appelé manuels d’utilisation est également divisé en types plus spécifiques, tels que: Manuels d’installation Mitsubishi ETH-1000, manuels d’entretien, brefs manuels ou manuels de l’utilisateur Mitsubishi ETH-1000. Selon vos besoins, vous devriez chercher le document dont vous avez besoin. Sur notre site, vous pouvez voir le manuel le plus populaire d’utilisation du produit Mitsubishi ETH-1000.

Manuels d’utilsiation similaires

Manuel d’utilisation complet de l’appareil Mitsubishi ETH-1000, quelle devrait-elle être?
Le manuel d’utilisation, également appelé le mode d’emploi, ou tout simplement le manuel, est un document technique destiné à aider à utiliser Mitsubishi ETH-1000 par les utilisateurs. Des manuels sont généralement écrits par un rédacteur technique, mais dans un langage accessible à tous les utilisateurs Mitsubishi ETH-1000.

Le manuel d’utilisation complet Mitsubishi, devrait inclure plusieurs éléments de base. Certains d'entre eux sont moins importants, tels que: la couverture / page de titre ou pages d'auteur. Cependant, la partie restante, devrait nous fournir des informations importantes du point de vue de l'utilisateur.

1. Introduction et des conseils sur la façon d'utiliser le manuel Mitsubishi ETH-1000 - Au début de chaque manuel, nous devrions trouver des indices sur la façon d'utiliser le document. Il doit contenir des informations sur l'emplacement de la table des matières Mitsubishi ETH-1000, FAQ ou des problèmes les plus fréquents - les points qui sont les plus souvent recherchés par les utilisateurs de chaque manuel
2. Table des matières - index de tous les conseils pour lMitsubishi ETH-1000 qui peuvent être trouvés dans le document courant
3. Conseils sur la façon d'utiliser les fonctions de base de l’appareil Mitsubishi ETH-1000 - qui devraient nous aider dans les premières étapes lors de l'utilisation Mitsubishi ETH-1000
4. Troubleshooting - séquence systématique des activités qui nous aideront à diagnostiquer et ensuite résoudre les principaux problèmes de Mitsubishi ETH-1000
5. FAQ - questions fréquemment posées
6. Détails du contact Informations sur l'endroit où chercher le contact avec le fabricant / service Mitsubishi ETH-1000 dans un pays donné, si le problème ne peut être résolu par nous-mêmes.

Avez-vous une question à propos de Mitsubishi ETH-1000?

Utiliser le formulaire ci-dessous

Si vous n’avez pas résolu votre problème avec Mitsubishi ETH-1000, avec l'aide du manuel que vous avez trouvé, posez une question en utilisant le formulaire ci-dessous. Si un utilisateur a eu un problème similaire avec Mitsubishi ETH-1000 il est probable qu’il a envie de partager la façon de le résoudre.