    eth1000_large.jpg Using ICC E TH-1000 EtherNet/IP Interface w ith Mitsubishi i Q PLC ...

  • Mitsubishi ETH-1000 - page 2

    i Contents Contents ..................................................................................................... .............................................................. i FURT HER READING REF ERENCE LI ST ......................................................................................... ...................... ii Chapter 1 Int ...

  • Mitsubishi ETH-1000 - page 3

    ii FURTHER RE A DING REFE RENCE LIST ( Mitsub ishi Q Correspond ing MELSE C Comm unication Protocol R eference Manua l SH(NA)-08000 8-K QnUCPU Us er’s Manual C ommunic ation via Built-in Ether net Port SH(N A)-080811ENG-B Q Correspond ing Ethernet I nterface Modul e User’s Ma nual (Basic) SH ( NA)-0800 09-N ICC Instruction Ma nual: ETH -1000 Mu ...

  • Mitsubishi ETH-1000 - page 4

    iii This Page is intentionall y left blank! ...

  • Mitsubishi ETH-1000 - page 5

    1-1 Chapter 1 Introduction This document provides instruc tions and ex amples on how t o configure a s y stem c onsists of Rockwell ControlLogix PLC, an ICC ET H-1000 Gat eway, and Mitsubish i iQ PLC s y stem . An Example of the system configurat ion is shown in Fi gure 1 below. EtherNet/ I P M C Prot ocol G at eway Et h er net N etwork Switch R oc ...

  • Mitsubishi ETH-1000 - page 6

    2-1 Chapter 2 System Overview A Verification Sy stem is used as a test bed for verif ying the steps docum ented in this Quick Start guide. The Verification System is s hown in Figure 2 be low with the IP address ass ignments of al l the devices. Netgear Switch Monitoring Laptop 2 192.168.1.5 ControlLogix 192.168.1.30 ICC 192.168.1.102 iQ (Built-in ...

  • Mitsubishi ETH-1000 - page 7

    3-1 Chapter 3 Connecting Devices to the Network The steps of configuring th e IP addresses of the ControlLo gix PLC system , the ICC ETH -1000 module, an d the PLC are doc umented in th is chapter. 3.1 Changing th e IP Address of the ControlL ogix System The minimum configuration of a ControlLogix syst em consists of a ControlLogix c hassis (e.g. 1 ...

  • Mitsubishi ETH-1000 - page 8

    3-2 4. Right-Click on the ENBT M odule and se lect “Module C onfiguration” from the drop down list: 5. Under the “P ort Configur ation” tab, se lect the Net work Configurati on Type to be “Static”, and o ne can m odify the IP ad dress and the Ne twork Mask to the desired values. C lick “OK” and sa ve the new IP ad dress configuratio ...

  • Mitsubishi ETH-1000 - page 9

    3-3 6. Once the n ew I P addres s is set, it is ver y likely ( depending on wha t IP address and Net work m ask were as signed to the E NBT m odule) that the C onfiguration PC wi ll no longer be abl e to comm unicate with the ENBT module. The IP a ddress of the Conf iguration P C will need to be changed to be in the sam e subnet of the ENBT m odule ...

  • Mitsubishi ETH-1000 - page 10

    3-4 2. Click the “Auto Conn ect” b utton, a nd the ETH- 1000 module w ill b e con nected, and the screen will be populat ed with the cur rent information: The proper devic e type is sho wn with a green LED lit showing the co nnection has been established. The f irmware type, version, and Database t ype are als o shown on the sc reen. 3. The use ...

  • Mitsubishi ETH-1000 - page 11

    3-5 5. After the do wnload, the s ystem wi ll need to be reset fo r the changes to take ef fect. Click “Y es” to the pop-up m essage and the ETH-1000 will go through the r eset sequence 6. After the ET H-1000 system reboot, the screen sho uld show the ne w IP address . In th is example, the IP addres s was change d to 192.168.5.1 90. 1 Introduc ...

  • Mitsubishi ETH-1000 - page 12

    3-6 3.3 Changing th e IP Address es of the iQ PLC Built-in Ethern et Port The f ollowing are steps to c hange the IP a ddress of the iQ PLC Built-in Ethernet Port: 1. Open the GX W orks2 on the C onfiguration PC a nd create a ne w pr oject for the appropriate CPU Module (e.g. Q 13UDEH in t his example). 2. Select the PLC Param eter on th e Pr oject ...

  • Mitsubishi ETH-1000 - page 13

    3-7 c. Click the Open Setting box and enter the first channel as MC Protocol with a proper Host Station Por t number (In th is example, the Port Number is set at Hex 5001) 3. Download th e param eter settings to the PLC . 1 Introduction 2 System Overview 3 Devices to the Network 4 ControlLogix PLC Project Configuration 5 ETH-1000 Configuration 6 Us ...

  • Mitsubishi ETH-1000 - page 14

    3-8 3.4 Configuring the External Eth ernet Mod ule in the iQ System W hen app lication requires, an externa l E thernet modul e c an be added to the syst em and comm unicating to the iQ CPU. This sect ion describes the co nfiguration of a QJ7 1E71-100 modu le to be used in the comm unication with a CLX through the ICC ETH-1000 gateway. 1. Select th ...

  • Mitsubishi ETH-1000 - page 15

    3-9 2. At the “Ethern et Operatio n Setting windo w”, one can config ure the IP addre ss of the Ethernet module. a. Set the Com munication Dat a Code to Binar y b. Check the “Enable Online Change” check box c. Select the “ Initial Tim ing” to be A lways wait f or OPEN (Com munication pos sible at ST OP time). T his is a crit ical s tep ...

  • Mitsubishi ETH-1000 - page 16

    3-10 3. At the Net work Parameter Setting window, click “Open Setting” a nd op en the wind ow be low a nd enter the par ameters as shown: a. Configure the Host Station Port Num ber to matc h the C onnection Object port number configured in the ICC ET H-1000. ...

  • Mitsubishi ETH-1000 - page 17

    4-1 Chapter 4 ControlLogix PLC P roj ect Configuration The configuratio n s teps of a ControlL ogix pr oject are described this Chapter. T hese steps are us ed to comm unicate with an ICC ETH -1000 module. It is assum ed that the user has basic k nowledge in using RSLogix5000 software to perform the basic configurati on steps. 4.1 A dding the 1756 ...

  • Mitsubishi ETH-1000 - page 18

    4-2 3. In the “Select Module” pop- up window, cho ose the “Com munications” 4. Then select th e proper m odule 1756 ENBT ...

  • Mitsubishi ETH-1000 - page 19

    4-3 5. Then s elect the Major Revision level of the ENBT firm ware. In the Verification System, the m ajor revision le vel of the ENBT module is 2. 6. Enter th e proper Name, Slot Location, Revision Level and IP Addres s of the ENBT module. In the Verification System, the module nam e is set at CSC_EIP, the revision firm ware level is 2.3, the modu ...

  • Mitsubishi ETH-1000 - page 20

    4-4 7. Click “O K” to accept t he configurat ion and m ake no add itional conf iguration changes to the “Connection” t ab. Sim ply click “OK” again to accept the configuration. 4.2 A dding the ICC M odule The following st eps ar e us ed to add the I CC m odule f or c o mm unication us ing I/O Messag ing ( or Im plicit Messaging m ethod) ...

  • Mitsubishi ETH-1000 - page 21

    4-5 2. Select the “C ommunicatio ns” and expa nd the tree for additional sel ection. 3. Choose the Ethernet-Mod ule Generic Ether net Module 1 Introduction 2 System Overview 3 Devices to the Network 4 ControlLogix PLC Project Configuration 5 ETH-1000 Configuration 6 Using EtherNet/IP Explicit Messaging 7 Terminology ...

  • Mitsubishi ETH-1000 - page 22

    4-6 4. Double C lick on the se lection an d c onfigure the I CC module according ly. T his is a critica l configurat ion step to e nsure the ETH-1000 will w ork properly in the s ystem as the application requires. Please a lso cons ult the ICC ET H-1000 Us er’s Manua l carefull y about t he configur ation of these item s. a. Configure the “C om ...

  • Mitsubishi ETH-1000 - page 23

    4-7 5. Configure the RPI to 10.0 ms. 6. Select “OK” to accept the c onfiguration an d complete the ICC Module C onfiguration. 7. Double c lick on the “Co ntroller T ags” selec tion, and the foll owing tags are a utomatica lly created for the ICC ET H-1000 m odule: 1 Introduction 2 System Overview 3 Devices to the Network 4 ControlLogix PLC ...

  • Mitsubishi ETH-1000 - page 24

    4-8 a. 248 integer tags were created for CSC_ICC_ ETH1000_INT :I. These are the t ag locations where I CC will transf er the data to the ControlLog ix us ing Implicit Messag e prot ocol ev ery RPI. b. 248 integer t ags were created f or CSC _ICC_ETH 1000_INT:O. T hese are the t ag l ocations where data will be sent to I CC ETH-1000 through Im plici ...

  • Mitsubishi ETH-1000 - page 25

    5-1 Chapter 5 ETH-1000 Configuration The s teps to configur e th e ETH-1000 m odule to work with the ControlLog ix PLC usin g Et herNet/IP Im plicit Messaging and Mitsubish i controllers usin g MC Proto col are docum ented. Configuring the Validation System as sh own in Figur e 2 is used as the exam ple. Some param eters will n eed different v alue ...

  • Mitsubishi ETH-1000 - page 26

    5-2 2. Select th e EtherNet/I P t ab of the ICC Conf iguration scr een an d d efine the ICC Database locations where dat a items w ill be exc hanged between the Co ntrolLogix PL C and th e ICC module throug h the Implicit Mess aging protoc ol. In this exam ple, the “Prod uce Data Start Addres s” of the ICC m odule is set at Databas e Location 0 ...

  • Mitsubishi ETH-1000 - page 27

    5-3 The database addr esses in the ICC ar e us ed t o address “by te” data locat ions. Thus, 248 wor ds will take up 49 6 database addr esses. 3. Select the “M onitor” tab and c heck the “Dis play Usage ” c heckbox to sho w the DB m emor y loc ations that are conf igured for use by both the Pro duced and Consumed data . 5.2 Configuring ...

  • Mitsubishi ETH-1000 - page 28

    5-4 2. Enter the IP address of the controller that will be co nnected. The IP is 192.16 8.1.40 for this exam ple 3. Enter the Port Number in d ecimal. T he Port is 20481 or 0x 5001 for this exam ple. 4. Hit “Create” af ter the inf ormation is entered a nd the Co nnection Object is shown as below. 5.2.2. Configu ring Service Obje cts In the Veri ...

  • Mitsubishi ETH-1000 - page 29

    5-5 5. Enter the Start ing Point of the Data Registers where the data item s will be written i nto. I n this exam ple, the Starting Poin t is “12268.” 6. Enter the n umber of words to b e transferr ed in the “Nu m W ords” dialog box. In this exam ple, the number of words is “20.” 7. Enter the Datab ase Address (Datab ase Addr.) of the I ...

  • Mitsubishi ETH-1000 - page 30

    5-6 9. Repeat th e steps 1-8 to de fine the other three s ervice obj ects to perf orm the tran sfers between ICC and iQ PLC. a. Define the Service Object t o read 20 Data Registers to ICC b. Define the Service Object t o write 10 W ords to Internal R elay ...

  • Mitsubishi ETH-1000 - page 31

    5-7 c. Define the Service Object t o read 10 words of Link Rel ay to ICC 1 Introduction 2 System Overview 3 Devices to the Network 4 ControlLogix PLC Project Configuration 5 ETH-1000 Configuration 6 Using EtherNet/IP Explicit Messaging 7 Terminology ...

  • Mitsubishi ETH-1000 - page 32

    5-8 5.2.3. Configu ring the Connecti on Object for Q J71E71 Ethernet Modu le Repeat steps docum ented in S ections 5.2.1and 5.2 .2 to configure t he Connec tion and Service objects to comm unicate to the ext ernal Ethernet m odule in the system . 1. Creat a Connecti on Obj ect first with name Connection2. Enter the IP addr ess of the Ethernet modul ...

  • Mitsubishi ETH-1000 - page 33

    5-9 5.2.4. Calculating the ICC ET H-1000 DB A ddres ses One of the most important steps in config uring a serv ice objec t is to de termine the D atabase Address that n eeds to be entered. Since the ICC ET H-1000 DB is a “shared databas e” bet ween Eth erNet/IP and MELSEC pr otocols, one has to def ine carefull y which wa y the d ata item s wil ...

  • Mitsubishi ETH-1000 - page 34

    6-1 Chapter 6 Using EtherNe t/IP Explicit Messaging The ControlLogix PLC can com municate with the Mitsub ishi i Q PLC using E IP Explicit Messaging format through the ICC ETH-1000 gateway. The communication is accom plished throu gh the use of MSG instructions in RSLogix5 000. Ref er to Sections 11.1.4.5, 11.1.4. 6, 8.7.5.1 of the “ Instruction ...

  • Mitsubishi ETH-1000 - page 35

    7-1 Chapter 7 Terminolog y Implicit (I/O Data) Messaging Connecti ons are established to mo ve appli cation-specifi c I/O data at regular intervals. Th ese conne ctions often are s et u p a s one-t o-many rel ationship s in order to tak e fu ll ad v antage of t he p roducer- consume r m ulticast mod el. Impli cit messagi ng uses UDP/ IP r esources ...

  • Mitsubishi ETH-1000 - page 36

    Rev-1 Revisions July 2009 – Document c reated and Rel eased, Vers ion 1.0 October 20 09 – Minor revis ion to wording t hroughout t he docum ent, Version 1.1 ...

Fabbricante Mitsubishi Categoria Switch

I documenti che otteniamo dal fabbricante del dispositivoMitsubishi ETH-1000 possono essere suddivisi in diversi gruppi. Questi sono tra gli altri:
- disegni tecnici Mitsubishi
- manuali per l’uso ETH-1000
- schede prodotto Mitsubishi
- opuscoli
- o etichette energetiche Mitsubishi ETH-1000
Tutti sono importanti, ma le informazioni più importanti dal punto di vista di utilizzo del dispositivo possono essere trovate nel manuale per l’uso Mitsubishi ETH-1000.

Un gruppo di documenti denominato manuali per l’uso, è anche suddiviso in tipi più specifici, come: Manuali di installazione Mitsubishi ETH-1000, manuali di manutenzione, brevi manuali o manuali utente Mitsubishi ETH-1000. A seconda delle esigenze, si dovrebbe cercare il documento necessario. Nel nostro sito web, puoi visualizzare il manuale più popolare per l'uso del prodotto Mitsubishi ETH-1000.

Manuali per l’uso simili

Manuale completo del dispositivo Mitsubishi ETH-1000, come deve essere?
Il manuale per l’uso, denominato anche istruzioni per l’uso, o semplicemente il manuale è un documento tecnico progettato per aiutare ad utilizzare Mitsubishi ETH-1000 dagli utenti. I manuali sono di solito scritti da uno scrittore tecnico, ma in un linguaggio accessibile a tutti gli utenti Mitsubishi ETH-1000.

Il manuale per l’uso completo Mitsubishi, dovrebbe includere vari elementi di base. Alcuni di loro sono meno importanti, come ad esempio: copertina / pagina del titolo o pagina di autore. Tuttavia, la parte rimanente, dovrebbe fornire informazioni importanti dal punto di vista dell'utente.

1. Introduzione e la guida su come utilizzare il manuale Mitsubishi ETH-1000 - All'inizio di ogni manuale, dovremmo trovare indizi su come utilizzare il documento. Dovrebbe contenere informazioni sulla posizione dell’indice Mitsubishi ETH-1000, FAQ o i problemi più comuni : i punti che sono più spesso cercati dagli utenti di ogni manuale
2. Indice - elenco di tutti i suggerimenti per Mitsubishi ETH-1000 che possono essere trovati nel documento corrente
3. Suggerimenti su come utilizzare le funzioni di base del dispositivo Mitsubishi ETH-1000 - che ci dovrebbe aiutare nei primi passi durante l'uso Mitsubishi ETH-1000
4. Troubleshooting - sequenza sistematica delle attività che vi aiuterà a diagnosticare e, successivamente, risolvere i problemi più importanti del Mitsubishi ETH-1000
5. FAQ - domande più frequenti
6. Dettagli di contatto Informazioni su dove cercare il contatto con il fabbricante / servizio Mitsubishi ETH-1000 in un dato paese, se il problema non può essere risolto da noi stessi.

Hai una domanda su Mitsubishi ETH-1000?

Utilizza il modulo sottostante

Se non hai risolto il problema con Mitsubishi ETH-1000 con l'aiuto del manuale che hai trovato, fai una domanda utilizzando il modulo sottostante. Se un utente ha avuto un problema simile con Mitsubishi ETH-1000 è probabile che voglia condividere il modo di risolverlo.

Riscrivi il testo dall’immagine

Commenti (0)