    Johnson Controls Unitary Produ cts 1031452-UIM-B-0513 R-22 OUTDOOR SPLIT -SYSTEM AIR CONDITIONING SHIPPED WITH NITROGEN CHARGE ONL Y MODELS: 13 SEER - GC GD 1.5 TO 5 T ONS INSTALLATION MANUAL ® LIST OF SECTIONS GENERAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 SAFETY . . . . . . . . . . . . . . . ...

  • Johnson Controls 13 SEER - GCGD - page 2

    1031452-UIM-B-0513 2 Johnson Controls Unitary Products LIMIT A TIONS The unit should be installed in accordance with all National, S tate and Local Safety Codes and the limitations listed below: 1. Limitations for the indoor unit, coil, and appropriate accessories must also be observed. 2. The outdoor unit must not be installed with any duct work i ...

  • Johnson Controls 13 SEER - GCGD - page 3

    1031452-UIM-B-0513 Johnson Controls Unitary Produ cts 3 LIQUID LINE FIL TER-DRIER The air conditioning unit’s copper spun filter/dryer is located on the liq - uid line. PIPING CONNECTIONS The outdoor condensing unit must be connected to the indoor evapora - tor coil using field supplied r efrigerant grade (ACR) co pper tubing that is internally c ...

  • Johnson Controls 13 SEER - GCGD - page 4

    1031452-UIM-B-0513 4 Johnson Controls Unitary Products Connect the refrigerant lines u sing the following proced ure: 1. Remove the cap and Schrader core from both the liquid and vapor service valve service ports at the outdoor unit. Connect low pres- sure nitrogen to the liquid line service port. 2. Braze the liquid line to the liqui d valve at th ...

  • Johnson Controls 13 SEER - GCGD - page 5

    1031452-UIM-B-0513 Johnson Controls Unitary Produ cts 5 SECTION V : TXV INST ALLA TIONS The following are the basic steps fo r inst allation. For detailed instruc- tions, refer to the Installation Instructions accompanying the TXV kit. Install TXV kit as follows: 1. Relieve the holding charge by pulling off the rubber cap plug on the suction manifo ...

  • Johnson Controls 13 SEER - GCGD - page 6

    1031452-UIM-B-0513 6 Johnson Controls Unitary Products SUPERHEA T CHARGING METHOD - PIST ON INDOOR 1. Operate system until temperatures and pressures stabilize (mini- mum of 10 minutes). 2. Measure and record indoor wet bulb (WB) temperature using a sling psychrometer and the outdoor dry bulb (DB) temperature using a thermometer . 3. Measure and re ...

  • Johnson Controls 13 SEER - GCGD - page 7

    1031452-UIM-B-0513 Johnson Controls Unitary Produ cts 7 FIELD CONNECTIONS CONTR OL WIRING 1. Route low voltage wiring into bottom of control box as shown in Figure 6. Make low voltage wiring conne ctions inside the low volt- age box per Figures 7 - 1 1. 2. The complete connection diagram and schematic wiring label is located on the inside surface o ...

  • Johnson Controls 13 SEER - GCGD - page 8

    1031452-UIM-B-0513 8 Johnson Controls Unitary Products For additional connection diagrams for a ll UPG equipment refer to “Low V oltage System Wiring” document available online at www . upgnet.com in the Product Catalog Section. FIGURE 8: Thermostat Chart - Single S tage AC with PSC Air Handler AC 1A Single Stage Air Conditioner – PSC Air Han ...

  • Johnson Controls 13 SEER - GCGD - page 9

    1031452-UIM-B-0513 Johnson Controls Unitary Produ cts 9 FIGURE 9: Thermostat Chart - Single S tage AC with PSC Air Handler AC 1B Single Stage Air Conditioner – PSC Air Handler C 24 – Volt Comm on Y Compressor Contactor SINGLE STAGE AIR CONDIT IONER MA SHP AHP ID MODELS SINGLE STAGE AIR CONDIT I O N ER Other Part Nu mbers: SAP = Legacy 265902 = ...

  • Johnson Controls 13 SEER - GCGD - page 10

    1031452-UIM-B-0513 10 Johnson Controls Unitary Products FIGURE 10: Thermostat Chart - Single S tage AC with PSC Furnace AC 5A Single Stage Air Conditioner – Single Stage PSC Furnace G*9F G*(8/9)S F*(8/9) S PS(8/9) GF(8/9) G8C L*8S C 24 – Volt Comm on R 24 – Volt Hot W Full Stage Heat Y / Y2 Second or Full Stage Compressor SINGLE STAGE PSC FUR ...

  • Johnson Controls 13 SEER - GCGD - page 11

    1031452-UIM-B-0513 Johnson Controls Unitary Produ cts 11 FIGURE 1 1: Thermostat Chart - Single S tage AC with PSC Furnace AC 5B Single Stage Air Conditioner – Single Stage PSC Furnace C 24 – Volt Comm on Y Compressor Contactor SINGLE STAGE AIR CONDIT IONER SINGLE STAGE AIR CONDIT I O N ER Y Full Stage Compressor G Fan *BP11C50124 *BN11C01124 *D ...

  • Johnson Controls 13 SEER - GCGD - page 12

    1031452-UIM-B-0513 12 Johnson Controls Unitary Products SECTION IX: INSTRUCTING THE O WNER Assist owner with processing warr anty cards and/or online registration. Review Owners Guide and provide a copy to the owner and guidance on proper operation and maintenance. I nstruct the owner or the opera- tor how to start, stop and adjust temperature sett ...

  • Johnson Controls 13 SEER - GCGD - page 13

    1031452-UIM-B-0513 Johnson Controls Unitary Produ cts 13 SECTION X: WIRING DIAGRAM FIGURE 12: Wiring Diagram ...

  • Johnson Controls 13 SEER - GCGD - page 14

    1031452-UIM-B-0513 14 Johnson Controls Unitary Products NOTES ...

  • Johnson Controls 13 SEER - GCGD - page 15

    1031452-UIM-B-0513 Johnson Controls Unitary Produ cts 15 SECTION XI: ST ART UP SHEET Air Conditioning and Heating Start-Up Sheet Proper start-up is critical to customer comfort and equipment longevity Name Address City State or Province Zip or Postal Code Indoor Unit Model # Indoor Unit Serial # Indoor Coil Model # Indoor Coil Serial # Upflow Downf ...

  • Johnson Controls 13 SEER - GCGD - page 16

    Subject to change without not ice. Published in U.S.A. 1031452-UIM-B-0513 Copyright © 2013 by Johnson Controls, Inc. All rights reserved. Supersedes: 1031452-UIM-A-0413 Y ork Internat ional Corp. 5005 Y ork Driv e Norman, OK 73069 Supply static after indoor coil (in w.c.") Return Static (in w.c.") before filter Total External Static Pres ...

Fabbricante Johnson Controls Categoria Air Conditioner

I documenti che otteniamo dal fabbricante del dispositivoJohnson Controls 13 SEER - GCGD possono essere suddivisi in diversi gruppi. Questi sono tra gli altri:
- disegni tecnici Johnson Controls
- manuali per l’uso 13 SEER - GCGD
- schede prodotto Johnson Controls
- opuscoli
- o etichette energetiche Johnson Controls 13 SEER - GCGD
Tutti sono importanti, ma le informazioni più importanti dal punto di vista di utilizzo del dispositivo possono essere trovate nel manuale per l’uso Johnson Controls 13 SEER - GCGD.

Un gruppo di documenti denominato manuali per l’uso, è anche suddiviso in tipi più specifici, come: Manuali di installazione Johnson Controls 13 SEER - GCGD, manuali di manutenzione, brevi manuali o manuali utente Johnson Controls 13 SEER - GCGD. A seconda delle esigenze, si dovrebbe cercare il documento necessario. Nel nostro sito web, puoi visualizzare il manuale più popolare per l'uso del prodotto Johnson Controls 13 SEER - GCGD.

Manuale completo del dispositivo Johnson Controls 13 SEER - GCGD, come deve essere?
Il manuale per l’uso, denominato anche istruzioni per l’uso, o semplicemente il manuale è un documento tecnico progettato per aiutare ad utilizzare Johnson Controls 13 SEER - GCGD dagli utenti. I manuali sono di solito scritti da uno scrittore tecnico, ma in un linguaggio accessibile a tutti gli utenti Johnson Controls 13 SEER - GCGD.

Il manuale per l’uso completo Johnson Controls, dovrebbe includere vari elementi di base. Alcuni di loro sono meno importanti, come ad esempio: copertina / pagina del titolo o pagina di autore. Tuttavia, la parte rimanente, dovrebbe fornire informazioni importanti dal punto di vista dell'utente.

1. Introduzione e la guida su come utilizzare il manuale Johnson Controls 13 SEER - GCGD - All'inizio di ogni manuale, dovremmo trovare indizi su come utilizzare il documento. Dovrebbe contenere informazioni sulla posizione dell’indice Johnson Controls 13 SEER - GCGD, FAQ o i problemi più comuni : i punti che sono più spesso cercati dagli utenti di ogni manuale
2. Indice - elenco di tutti i suggerimenti per Johnson Controls 13 SEER - GCGD che possono essere trovati nel documento corrente
3. Suggerimenti su come utilizzare le funzioni di base del dispositivo Johnson Controls 13 SEER - GCGD - che ci dovrebbe aiutare nei primi passi durante l'uso Johnson Controls 13 SEER - GCGD
4. Troubleshooting - sequenza sistematica delle attività che vi aiuterà a diagnosticare e, successivamente, risolvere i problemi più importanti del Johnson Controls 13 SEER - GCGD
5. FAQ - domande più frequenti
6. Dettagli di contatto Informazioni su dove cercare il contatto con il fabbricante / servizio Johnson Controls 13 SEER - GCGD in un dato paese, se il problema non può essere risolto da noi stessi.

Hai una domanda su Johnson Controls 13 SEER - GCGD?

Utilizza il modulo sottostante

Se non hai risolto il problema con Johnson Controls 13 SEER - GCGD con l'aiuto del manuale che hai trovato, fai una domanda utilizzando il modulo sottostante. Se un utente ha avuto un problema simile con Johnson Controls 13 SEER - GCGD è probabile che voglia condividere il modo di risolverlo.

Riscrivi il testo dall’immagine

Commenti (0)