    TECHNICAL GUIDE SPLIT -SYSTEM AIR CONDITIONERS 13 SEER – R- 410A – 1 PHASE MODELS: YCJD18 THRU 60 (1.5 THRU 5 NOMINAL TONS) Due to continuous pro duct improvement, spec ifications are subject to cha nge with ou t notice. Visit us on the web at www . yor k.com Additional rating informa tion can be foun d at www . ahridirectory .org W ARRANTY S t ...

  • York YCJD18 THRU 60 - page 2

    561908-YTG-A-0410 2 Johnson Controls Unitary Products All dimensions are in inche s. They are subject to ch ange with- out notice. Certified dimensions will be provi ded upon request. Physical and Electr ical Dat a MODEL YCJD18S41 S3(H) YCJD24S41 S3(H) YCJD30S41 S3(H) YCJD36S41 S3(H) YCJD42S41 S3(H) YCJD48S4 1 S3(H) YCJD60S 41 S3 Unit Supply V olta ...

  • York YCJD18 THRU 60 - page 3

    561908-YTG-A-0410 Johnson Controls Unitary Pro ducts 3 PROCEDURES: 1. Unit factory charge listed on the u nit nameplate includes r e frigerant for the condenser, the smallest evaporator and 15 feet of interconnecting line tub ing. 2. V erify the TXV and additional charge required for specific evaporator coil in the system using the abo ve table. 3. ...

  • York YCJD18 THRU 60 - page 4

    561908-YTG-A-0410 4 Johnson Controls Unitary Products COOLING CAP ACITY - With Air Handler Coils UNIT MODEL AIR HANDLER COIL MODEL 1 COOLING MODEL W RA TED CFM NET MBH SEER EER TOT AL SENS. 13 SEER AC WITH MA YCJD18S41S3(H) MA08B 17 FC/MC18B 600 17.5 12.9 13.00 1 1.00 YCJD24S41S3(H) MA08B 17 FC/MC36B 800 24.0 16.7 13.00 1 1.00 MA08B 17 FC/MC35B 800 ...

  • York YCJD18 THRU 60 - page 5

    561908-YTG-A-0410 Johnson Controls Unitary Pro ducts 5 — = Not applicable. 13 SEER AC WITH AHP / SHP / AHX / F*FP YCJD18S41S3(H) AHP18 17 – 650 17.5 12.9 13.00 1 1.00 AHX18 17 - 630 18.0 13.8 14.50 12.00 F4FP024 18 – 600 17.5 12.9 13.00 1 1.00 F6FP018 17 - 600 17.8 13.3 14.50 12.00 YCJD24S41S3(H) AHP30 17 – 795 24.0 16.8 13.00 1 1.00 AHX30 ...

  • York YCJD18 THRU 60 - page 6

    561908-YTG-A-0410 6 Johnson Controls Unitary Products COOLING CAP ACITY - Upflow , Downflow & Horizontal Furnace s and Coils UNIT MODEL FURNACE** COIL MODEL COOLING CFM RANGE (Min.-max.) W RA TED CFM NET MBH SEER 1 EER TOT AL SENS. YCJD18S41S3(H) 450 - 750 14,17 FC/MC/PC18 600 17 .5 12 .9 13.00 1 1.00 450 - 750 14 HC18 600 17.5 12.9 13.00 1 1.0 ...

  • York YCJD18 THRU 60 - page 7

    561908-YTG-A-0410 Johnson Controls Unitary Pro ducts 7 COOLING CAP ACITY - With High Efficiency Motor Furnaces MODELS FURNACE MODEL COIL MODEL 1 W COOLING RA TED CFM Net MBH SEER EER TOT AL SE N S. 13 SEER HP WITH V ARIABLE SPEED FURNACES 2 YCJD18S41S3(H) T*(8,L)X*A12 FC/MC/PC18A 14 540 17.7 12.9 14.50 12.50 T*(8,L)X*B12 FC/MC/PC18B 17 580 18.0 13. ...

  • York YCJD18 THRU 60 - page 8

    561908-YTG-A-0410 8 Johnson Controls Unitary Products YCJD30S41S3(H) T*9X*C20 FC/MC/PC43C 21 720 28.2 19 .3 14 .00 12 .00 (Y*(8,L)C/T*8V)*A12 FC/MC/PC32A 14 1045 29.2 21.8 13.20 1 1.00 (Y*(8,L)C/T*8V)*B12 FC/MC/PC35B 17 995 29.6 21.4 14.00 1 1.50 (Y*9C/T*9V)*B12 FC/MC/PC35B 17 1045 29 .4 22.0 13.50 1 1.50 (Y*(8,L)C/T*8V)*C16 FC/MC/PC35C 21 1025 29. ...

  • York YCJD18 THRU 60 - page 9

    561908-YTG-A-0410 Johnson Controls Unitary Pro ducts 9 YCJD36S41S3(H) (Y*(8,L)C/T*8V)*C20 HC4 2 21 1 190 35.6 25.6 14.00 12.00 (Y*9C/T*9V)*C16 HC42 21 1240 35.4 25.2 13.50 1 1.50 (Y*9C/T*9V)*C20 HC42 21 1200 35.6 25.4 14.00 1 1.50 (Y*(8,L)C/T*8V)*C16 UC48C 21 1210 34.6 24.8 13.50 1 1.50 (Y*(8,L)C/T*8V)*C20 UC48C 21 1 155 34.8 24.8 14.00 1 1.50 (Y*9 ...

  • York YCJD18 THRU 60 - page 10

    561908-YTG-A-0410 10 Johnson Controls Unitary Products YCJD48S41S3(H) T*9X*C20 FC/PC60C 21 1625 47.0 34.6 13.40 1 1.00 T*9X*D20 FC/MC/PC60D 24 1490 47.5 33.8 13.20 1 1.00 T*9X*C16 FC/PC60C 21 1575 47.0 33.8 13.10 1 1.00 T*9X*C20 FC/PC60C 21 1625 47.0 33.8 13.10 1 1.00 (Y*(8,L)C/T*8V)*C16 FC/MC/PC48C 21 1565 49.0 35.0 13.10 1 1.00 (Y*(8,L)C/T*8V)*C2 ...

  • York YCJD18 THRU 60 - page 11

    561908-YTG-A-0410 Johnson Controls Unitary Pro ducts 11 ACCESSORIES Refer to Price Manua l for specific model numbers. Off Cycle Timer Delay - Provides a 5-minu te off cycle to pre- vent rapid recycling of the compressor . Hard St art Kit - Required when using TXV indoor coil. Also , provides increased starting torque for areas with low voltage. Th ...

  • York YCJD18 THRU 60 - page 12

    561908-YTG-A-0410 12 Johnson Controls Unitary Products Multipliers for determining the p erfo rman ce with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (bet ween 73-87 F), sensible capacity incr eases by 1060 BTUH per 1000 CFM per degree above the list ed temperature and decr eases by 1060 BTUH per 1000 CFM pe ...

  • York YCJD18 THRU 60 - page 13

    561908-YTG-A-0410 Johnson Controls Unitary Pro ducts 13 Multipliers for determining the perform ance with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (between 73-87 F), sensible capacity increase s by 1060 BTUH per 1000 CFM per degree above the li sted temperature and decrease s by 1060 BTUH per 1000 CFM per ...

  • York YCJD18 THRU 60 - page 14

    561908-YTG-A-0410 14 Johnson Controls Unitary Products Multipliers for determining the p erfo rman ce with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (bet ween 73-87 F), sensible capacity incr eases by 1060 BTUH per 1000 CFM per degree above the list ed temperature and decr eases by 1060 BTUH per 1000 CFM pe ...

  • York YCJD18 THRU 60 - page 15

    561908-YTG-A-0410 Johnson Controls Unitary Pro ducts 15 Multipliers for determining the perform ance with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (between 73-87 F), sensible capacity increase s by 1060 BTUH per 1000 CFM per degree above the li sted temperature and decrease s by 1060 BTUH per 1000 CFM per ...

  • York YCJD18 THRU 60 - page 16

    561908-YTG-A-0410 16 Johnson Controls Unitary Products Multipliers for determining the p erfo rman ce with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (bet ween 73-87 F), sensible capacity incr eases by 1060 BTUH per 1000 CFM per degree above the list ed temperature and decr eases by 1060 BTUH per 1000 CFM pe ...

  • York YCJD18 THRU 60 - page 17

    561908-YTG-A-0410 Johnson Controls Unitary Pro ducts 17 Multipliers for determining the perform ance with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (between 73-87 F), sensible capacity increase s by 1060 BTUH per 1000 CFM per degree above the li sted temperature and decrease s by 1060 BTUH per 1000 CFM per ...

  • York YCJD18 THRU 60 - page 18

    Subject to change without notice. Published in U .S.A. 561908-YTG-A-0410 Copyright © 2010 by Johnson Controls, Inc. All rights reserved. Supersedes: 364834-YTG-H-0509 Johnson Controls Unitary Products 5005 Y ork Drive Norman, OK 73069 Multipliers for determining the p erfo rman ce with other indoor sections. NOTE: For dry bulb temperatures dif fer ...

Fabbricante York Categoria Air Conditioner

I documenti che otteniamo dal fabbricante del dispositivoYork YCJD18 THRU 60 possono essere suddivisi in diversi gruppi. Questi sono tra gli altri:
- disegni tecnici York
- manuali per l’uso YCJD18 THRU 60
- schede prodotto York
- opuscoli
- o etichette energetiche York YCJD18 THRU 60
Tutti sono importanti, ma le informazioni più importanti dal punto di vista di utilizzo del dispositivo possono essere trovate nel manuale per l’uso York YCJD18 THRU 60.

Un gruppo di documenti denominato manuali per l’uso, è anche suddiviso in tipi più specifici, come: Manuali di installazione York YCJD18 THRU 60, manuali di manutenzione, brevi manuali o manuali utente York YCJD18 THRU 60. A seconda delle esigenze, si dovrebbe cercare il documento necessario. Nel nostro sito web, puoi visualizzare il manuale più popolare per l'uso del prodotto York YCJD18 THRU 60.

Manuali per l’uso simili

Manuale completo del dispositivo York YCJD18 THRU 60, come deve essere?
Il manuale per l’uso, denominato anche istruzioni per l’uso, o semplicemente il manuale è un documento tecnico progettato per aiutare ad utilizzare York YCJD18 THRU 60 dagli utenti. I manuali sono di solito scritti da uno scrittore tecnico, ma in un linguaggio accessibile a tutti gli utenti York YCJD18 THRU 60.

Il manuale per l’uso completo York, dovrebbe includere vari elementi di base. Alcuni di loro sono meno importanti, come ad esempio: copertina / pagina del titolo o pagina di autore. Tuttavia, la parte rimanente, dovrebbe fornire informazioni importanti dal punto di vista dell'utente.

1. Introduzione e la guida su come utilizzare il manuale York YCJD18 THRU 60 - All'inizio di ogni manuale, dovremmo trovare indizi su come utilizzare il documento. Dovrebbe contenere informazioni sulla posizione dell’indice York YCJD18 THRU 60, FAQ o i problemi più comuni : i punti che sono più spesso cercati dagli utenti di ogni manuale
2. Indice - elenco di tutti i suggerimenti per York YCJD18 THRU 60 che possono essere trovati nel documento corrente
3. Suggerimenti su come utilizzare le funzioni di base del dispositivo York YCJD18 THRU 60 - che ci dovrebbe aiutare nei primi passi durante l'uso York YCJD18 THRU 60
4. Troubleshooting - sequenza sistematica delle attività che vi aiuterà a diagnosticare e, successivamente, risolvere i problemi più importanti del York YCJD18 THRU 60
5. FAQ - domande più frequenti
6. Dettagli di contatto Informazioni su dove cercare il contatto con il fabbricante / servizio York YCJD18 THRU 60 in un dato paese, se il problema non può essere risolto da noi stessi.

Hai una domanda su York YCJD18 THRU 60?

Utilizza il modulo sottostante

Se non hai risolto il problema con York YCJD18 THRU 60 con l'aiuto del manuale che hai trovato, fai una domanda utilizzando il modulo sottostante. Se un utente ha avuto un problema simile con York YCJD18 THRU 60 è probabile che voglia condividere il modo di risolverlo.

Riscrivi il testo dall’immagine

Commenti (0)