    6104BAFG R05 Page 1 RESIDENTIAL BURNERS Potential for Fire, Smoke and Asphyxiation Hazards T o the Homeowner or Equipment Owner: Please read and carefully follow all instructions provided in this manual regarding your responsibilities in caring for your heating equipment. Contact a professional, quali fi ed service agency for installation, start-u ...

  • Weil-McLain UO-5 CV - page 3

    Page 2 6104BAFG R0 6 T able of Contents Hazard Def nitions and Owner ’ s Information ........................................................................................ 3 Information T o Be Used Only By Qualif ed Service T echnicians General Information ......................................................................................... ...

  • Weil-McLain UO-5 CV - page 4

    6104BAFG R0 6 Page 3 NO TICE This manual contains information that applies to both AF and AFG burners. These burners may appear to be basically identical, but there are differences in design and performance. Please review the comparison chart below: Feature AF AFG Static Pressure Capability Conventional - Low range Enhanced - Medium range Blower Wh ...

  • Weil-McLain UO-5 CV - page 5

    Page 4 6104BAFG R0 6 Do NOT Alter the Original Burner Design Maintain the design to its original con fi guration. Only use parts speci fi ed for AF or AFG Burners Do NOT remove the air guide from the AFG chassis. Do NOT use ‘M’ Series air tube combinations on AF Burn- ers. Never try to convert an AF to an AFG or vice versa Any design alterati ...

  • Weil-McLain UO-5 CV - page 6

    6104BAFG R0 6 Page 5 General Speci fi cations Please read and understand the manual supplied with this equipment. This equipment must be installed, ad- justed and put into operation only by a quali fi ed individu- al or service agency that is: Licensed or certi fi ed to install and provide tech- nical service to oil heating systems. Experienced ...

  • Weil-McLain UO-5 CV - page 7

    Page 6 6104BAFG R0 6 Carefully inspect the chimney or exhaust vent system. Make sure it is properly sized and in good work- ing condition. Follow the instructions supplied by the appliance manufacturer . The installation must strictly comply with all ap- plicable codes, authorities having jurisdiction and the latest revision of the National Fire Pr ...

  • Weil-McLain UO-5 CV - page 8

    6104BAFG R0 6 Page 7 Inspect/Prepar e Installation Site Combustion air supply The burner cannot properly burn the fuel if it is not supplied with a reliable combustion air source. Follow the guidelines in the latest editions of the NFP A 31 and CSA-B139 regarding providing ad- equate air for combustion and ventilation. y y Failure to provide adequa ...

  • Weil-McLain UO-5 CV - page 9

    Page 8 6104BAFG R0 6 T able 4. AFG Reduced Firing Rates (with LFRB) Burner head type Low Firing Rate Baf fl e installed F0 up to 0.65 gph F3 or L1 up to 0.85 gph F4 or F6 up to 0.90 gph V1 up to 1.00 gph Prepar e the Bur ner Low Firing Rate Baff e The AFG Low Firing Rate Baf fl e (LFRB) reduces the air fl ow and pressure. The LFRB is sometimes u ...

  • Weil-McLain UO-5 CV - page 10

    6104BAFG R0 6 Page 9 If the nozzle is already installed, remove the noz- zle line assembly to verify that the nozzle size and spray pattern are correct for the application (per ap- pliance manufacturer ’s information). V erify that the electrode tip settings comply with Figure 3. If the nozzle is not installed, obtain a nozzle from the manufactur ...

  • Weil-McLain UO-5 CV - page 11

    Page 10 6104BAFG R0 6 1-3/8” 1-1/8” Check/Adjust ‘Z’ Dimension - ‘F’ heads 1. The important ‘Z’ dimension is the distance from the face of the nozzle to the fl at face of the head (or heat shield, if applicable). This dis- tance for F heads is 1- ⅛ ” (1- ⅜ ” if the air tube has a heat shield). The “Z” dimension is facto ...

  • Weil-McLain UO-5 CV - page 12

    6104BAFG R0 6 Page 1 1 Figure 5. Check/Adjust ‘Z’ Dimension - L1 & L2 Heads Figure 6. Check/Adjust ‘Z’ Dimension - V1 Heads V1 Adjusting Plate Setting AFG with V1 Head Burner Firing Rates 0 0.75-1.00 1 1.00-1.50 2 1.50-1.75 3 1.75-2.00 4 2.00-2.25 5 2.25-2.50 6 2.50-2.75 T able for initial adjusting plate settings for V1 Head L1/L2 head ...

  • Weil-McLain UO-5 CV - page 13

    Page 12 6104BAFG R0 6 Installing the Oil T ank and Supply System Fuel supply level with or above burner – SK8745 Figure 7. – Mounting Burner in Appliance T ilt down 2 o If space between burner air tube and opening exceeds 1/2 inch, pack burner opening with ce- ramic fiber refractory . Figure 8. – Inside T ank Gravity Feed System Figure 9. – ...

  • Weil-McLain UO-5 CV - page 14

    6104BAFG R0 6 Page 13 Disconnect electrical power before installing or servicing the burner . Provide ground wiring to the burner , metal con- trol enclosures and accessories. (This may also be required to aid proper control system opera- tion.) Perform all wiring in compliance with the Na- tional Electrical Code ANSI/NFP A 70 (Canada CSA C22.1) y ...

  • Weil-McLain UO-5 CV - page 15

    Page 14 6104BAFG R0 6 GeniSys Model 7505 Control W iring Display Module: For programming and diagnostics Alarm Module: For adding isolated low voltage alarm contacts to the base control. See Alarm Module Instructions for speci fi cations. Figure 10. The control can malfunction if it gets wet, leading to accumulation of oil or explosive oil vapors. ...

  • Weil-McLain UO-5 CV - page 16

    6104BAFG R0 6 Page 15 6. Run : The fl ame is sustained until the call for heat is satis fi ed. The burner is then sent to Motor-Off Delay , if applicable, or it is shut down and sent to Standby . 7. Recycle : If the fl ame is lost while the burner is fi ring, the control shuts down the burner , enters a 60 second recycle delay , and repeats the ...

  • Weil-McLain UO-5 CV - page 17

    Page 16 6104BAFG R05 Figure 1 1a. – Interrupted ignition, valve-on delay only (no motor-off delay) Figure 1 1b. – Interrupted ignition, valve-on delay and motor-off delay SAFETY AND OPERA TING LIMITS LIMIT L1 L2 (VL V) VA LV E L2 MOTOR L2 (MTR) L2 (IGN) IGNITER CAD CELL MOTOR IGNITER W R 80 70 60 50 50 70 80 60 OIL V AL VE CAD CELL THERMOST A T ...

  • Weil-McLain UO-5 CV - page 18

    6104BAFG R0  Page 17 61351 7. RECYCLE. If the fl ame is lost while the burner is fi ring, the control shuts down the burner , enters a 60 second recycle delay , and then repeats the above ignition sequence. If fl ame is lost three times in a row , the control locks out to prevent cycling with repetitious fl ame loss due to poor combustion. 8 ...

  • Weil-McLain UO-5 CV - page 19

    Page 18 6104BAFG R0  Make connections to the control’s terminals as shown in Figures 1 1a and 11 b . Refer to the label on the un- derside of the control for wiring details. Note: Motor-off delay on a 7505P will be disabled if the safety and operating limits as shown in Figures 1 1a and 1 1b interrupt power to the control terminal L1. Connect ...

  • Weil-McLain UO-5 CV - page 20

    6104BAFG R0  Page 19 Startup / Checkout If the burner or control fails any of the following tests, recheck control wiring. If the burner or control still fails any tests, replace the control. Check Safety Features Safe Start Check Place a jumper across the cad cell terminals. Refer to the steps for “Start up burner/set combustion” and have t ...

  • Weil-McLain UO-5 CV - page 21

    Page 20 6104BAFG R0  Step 4: Recheck smoke level. It should be Zero. This procedure provides a margin of reserve air to accommodate variable conditions. If the draft level has changed, recheck the smoke and CO 2 levels and readjust the burner if necessary Once combustion is set, tighten all fasteners on air band, air shutter and head adjusting p ...

  • Weil-McLain UO-5 CV - page 22

    6104BAFG R0  Page 21 Figure 12. Blower wheel assembly SK9190 Use a Feeler Gauge to set the gap to; AF = 0.125 +1/64 inch AFG = 0.030 +1/64 inch Replace the blower wheel: T urn off all power to the burner before servic- ing. Disconnect the burner motor wires. Remove the bolts securing the motor to the burner housing. Remove the motor and blower w ...

  • Weil-McLain UO-5 CV - page 23

    21 23 24 6 ...

  • Weil-McLain UO-5 CV - page 24

    6104BAFG R0 6 Page 23 # Part No. Description 1 Burner Housing Assembly 2 Specify* Air Band - Specify # of slots 3 Specify* Air Shutter - Specify # of slots 4 21807U V alve Cordset Not Shown 21887U PD Timer Delay Cordset 5 2184404U CleanCut Pump 6 5394 Copper Oil Line - 8” 7 3666 Splined Nut 8 3493 Escutcheon (F & L1/L2 heads) 9 2139 Hole Plug ...

  • Weil-McLain UO-5 CV - page 25

    Page 24 6104BAFG R0 6 Limited WARRANTY For Residential, Commercial and Specialty Burners The R. W. BECKETT CORPORATION (“Beckett”) warrants to persons who purchase its Beckett burners from Beckett for resale or for incorporation into a product for resale (“Customers”) that its equipment is free from defects in material and workmanship under ...

メーカー Weil-McLain カテゴリー Burner

Weil-McLain UO-5 CVのメーカーから受け取ることができるドキュメントは、いくつかのグループに分けられます。その一部は次の通りです:
- #BRANDの図面#
- UO-5 CVの取扱説明書
- Weil-McLainの製品カード
- パンフレット
- またはWeil-McLain UO-5 CVの消費電力シール
それらは全部重要ですが、デバイス使用の観点から最も重要な情報は、Weil-McLain UO-5 CVの取扱説明書に含まれています。

取扱説明書と呼ばれる文書のグループは、Weil-McLain UO-5 CVの取り付け説明書、サービスマニュアル、簡易説明書、またはWeil-McLain UO-5 CVのユーザーマニュアル等、より具体的なカテゴリーに分類されます。ご必要に応じてドキュメントを検索しましょう。私たちのウェブサイトでは、Weil-McLain UO-5 CVの製品を使用するにあたって最も人気のある説明書を閲覧できます。

関連する取扱説明書

Weil-McLain UO-5 CVデバイスの取扱説明書はどのようなものですか?
取扱説明書は、ユーザーマニュアル又は単に「マニュアル」とも呼ばれ、ユーザーがWeil-McLain UO-5 CVを使用するのを助ける技術的文書のことです。説明書は通常、全てのWeil-McLain UO-5 CVユーザーが容易に理解できる文章にて書かれており、その作成者はその分野の専門家です。

Weil-McLainの取扱説明書には、基本的な要素が記載されているはずです。その一部は、カバー/タイトルページ、著作権ページ等、比較的重要度の低いものです。ですが、その他の部分には、ユーザーにとって重要な情報が記載されているはずです。

1. Weil-McLain UO-5 CVの説明書の概要と使用方法。説明書にはまず、その閲覧方法に関する手引きが書かれているはずです。そこにははWeil-McLain UO-5 CVの目次に関する情報やよくある質問、最も一般的な問題に関する情報を見つけられるはずです。つまり、それらはユーザーが取扱説明書に最も期待する情報なのです。
2. 目次。Weil-McLain UO-5 CVに関してこのドキュメントで見つけることができる全てのヒントの目次
3. Weil-McLain UO-5 CVデバイスの基本機能を使うにあたってのヒント。 Weil-McLain UO-5 CVのユーザーが使い始めるのを助けてくれるはずです。
4. トラブルシューティング。Weil-McLain UO-5 CVに関する最も重要な問題を診断し、解決するために役立つ体系化された手続き
5. FAQ。よくある質問
6. 連絡先。一人では問題を解決できない場合に、その国におけるWeil-McLain UO-5 CVのメーカー/サービスへの連絡先に関する情報。

Weil-McLain UO-5 CVについてご質問がありますか?

次のフォームを使用してください

見つけた説明書を読んでもWeil-McLain UO-5 CVの問題を解決できない場合、下記のフォームを使用して質問をしましょう。ユーザーのどなたかがWeil-McLain UO-5 CVで同様の問題を抱えていた場合、その解決方法を共有したいと考えるかもしれません。

画像のテキストを入力してください

コメント (0)