Summary
  • Trane GSSD - page 1

    Installation Operation & Maintenance WSHPC-IOM-2 72-9041-02 Library Service Literature Product Section Unitary Product W ater Source Heat Pump Model GSSD Literatur e T ype Installation, Operation and Maintenance Sequence 2 Date June 1999 File No. SL-UN-WSHP-GSSD-I OM-2-6-99 Supersedes WSHPC-IOM-2 / 72- 9041-01 (Jan 98) Water Source Heat Pump Re ...

  • Trane GSSD - page 2

    2 Model Number Descriptions.............. ....... 3 Installation (W ater Loop).. 15 General Information............ .......... 4 Refrigeration Charge........ 16 Receiving and Handling.............. ............ 6 Refrigeration System....... 17 Installatio n Drawings............. ............ 7 Accessories....... ........... . 18 Installatio n (W at ...

  • Trane GSSD - page 3

    3 DIGITS 1 & 2 - PRODUCT TYPE GS = Ground Source Heat Pump DIGIT 3 - PRODUCT CONFIGU- RATION S = Split System DIGIT 4 - DEVELOPMENT SE- QUENCE D DIGITS 5,6 & 7 - UNIT NOMINAL CAPACITY (MBH) 024 = 24.1 030 = 29.6 036 = 36.4 042 = 41.1 048 = 48.7 060 = 59.2 072 = 65.6 DIGIT 8 - VOLTAGE/HERTZ/ PHASE 1 = 208/230-60-1 DIGIT 9 - UNIT ARRANGEM ENT ...

  • Trane GSSD - page 4

    4 The GSSD split unit has been ARI rat- ed with the Trane TWE air handlers with ICM 2 variab le speed motors to create a complete split system for res- idential applications. The GSSD equipment is completel y assembled, piped, inte rnally wire d and test operat- ed in the factory. The GSSD equip- ment is ETL and CSA listed. A prewired terminal stri ...

  • Trane GSSD - page 5

    5 Wa r r a n t y The unit is warranted by the manufac- turer against any defects in material and factory workmanship for one year after installation (labor and parts) . The refrigerant circuit, including the compressor, expansion device, revers- ing valve (less solenoid coil) , and all heat exchangers in contact with refrig- erants are warranted fo ...

  • Trane GSSD - page 6

    6 The GSSD is packaged in clear stretch wrap to allow immediate visual in- spection. A careful inspecti on should be made for shipping damage. All o r- ders are free on board (FOB) facto- ry, therefore claims must be made with the delivering carrier. Carefully remove the stretch wrap and the top cardboard corner pieces. Also remove the (4) four shi ...

  • Trane GSSD - page 7

    7 Installation-Location Considerations 23-5/16” 23” TOP VIEW 24-5/16” 24-13/16” 8 -7/16” 13-1/4” 2-1/16” 13-15/16” 7-3/16” 14-3/4” WATER IN-1” NPTI WATER OUT 1” NPTI LIQUID LINE 1/2” O.D . HI VOLTAGE 1-1/8” DIA. 6-7/16” 5-1/2” 3-15/16” 1-7/16” LOW VOLTAGE 1-1/8” DIA . PUMP CONTROL 1-1/8” DIA . SUCTION/DISCH 3 ...

  • Trane GSSD - page 8

    8 Installation-Location Considerations 23-5/16” 23” TOP VIEW 24-5/16” 24-13/16” 8 -7/16” 11-1/2” 2-1/16” 13” 7-3/16” 14-3/4” WATER IN-1” NPTI WATER OUT 1” NPTI LIQUID LINE 1/2” O.D . HI VOLTAGE 1-1/8” DIA. 6-7/16” 5-1/2” 3-15/16” 1-7/16” LOW VOLTAGE 1-1/8” DIA . PUMP CONTROL 1-1/8” DIA . SUCTION/DISCH 3/4” ...

  • Trane GSSD - page 9

    9 23-5/16” 23” TOP VIEW 24-5/16” 24-13/16” 8 -7/16” 11-1/2” 2-1/16” 7-3/16” 14-3/4” WATER IN-1” NPTI WATER OUT 1” NPTI LIQUID LINE 1/2” O.D . HI VOLTAGE 1-1/8” DIA. 6-7/16” 5-1/2” 3-15/16” 1-7/16” LOW VOLTAGE 1-1/8” DIA . PUMP CONTROL 1-1/8” DIA . SUCTION/DISCH 3/4” O.D. WATER REG (SCHRADER PORT) DESUPER OUT ...

  • Trane GSSD - page 10

    10 Installation-Water Connections Location Consideration ! Unit should be placed on a level surface in a indoor protected area. Units should not be installed or stored in an exterior environment. ! There should be approximately 2 to 3 feet of clearance available for accessing the unit for service. Accessiblity into unit is made by re- moving (2) tw ...

  • Trane GSSD - page 11

    11 RF Y 2 OC RG Y O B W 1 W 2 34 5 6 1 T-Stat (X13510588 020) Manual changeover: -two-stage heat -one-stage co ol TWE (Sizes 031-065) GSSD (Sizes 024-072) GSSD 24V Field Wiring W 1 W 2 Compressor Reversing valve (energized 5 6 in cooling) Field Wiring Connections Power wiring to the unit should be in- stalled per local electric codes by a professio ...

  • Trane GSSD - page 12

    12 . T able 1: Electrical Data Unit Model: GSSD 024 030 036 042 048 060 072 Electrical V olts-60HZ/1Phase 208-230 208-230 208-230 208-230 208-230 208-230 208-2 30 Compr essor RLA 1 1.4 13.6 15 18.4 20.4 28 32.1 Compr essor LRA 56 67 73 95 109 169 169 Blower Motor RLA 3 5 5.6 5.6 5.6 7.4 7.4 Min. Cir cuit Amp. 14.7 17.4 19.2 23.4 25.9 35.4 40.5 Max ...

  • Trane GSSD - page 13

    13 Press ure Switch A high pressure switch is provided to protect the compress or against exces- sive refrigeration pressure. The low pressure switch should b e wired in ac- cordance with the type of freezestat that is used. Trane factory supplies two low pressure switches in the re- frigerant circuit. The electrical con- nection is dependant upon ...

  • Trane GSSD - page 14

    14 L1 L2 1K1 L3 T3 1K1 L1 T1 5F3 5F2 230V 6A MAX TO WATERSOURCE PUMP A,C 6A,C,D,E C 7C 1C1 6E 4 5F1 2A 6F 5C A 7A A R S C 2B1 4S5 6G 4S6 6H DESUPE R- HEATER PUMP 6B1 5C 1TB3-1 16 F,G 1TB3-5 18 1TB3-6 25 1K3 C2 C1 A 1K3 5 19A 4S3 20A 4S4 4S1 21A A 4S4 23 1TB3-7 C A F 1TB3-8 23 A 16 1TB3-2 1K1 D,F D 1K3-24 G 1K1-12,14 NOTES: 1. UNLESS OTHERWISE NOTED ...

  • Trane GSSD - page 15

    15 Loop W ater Applications It should be noted that there is no me- chanical differen ce between geother- mal (closed loop) and ground water (open loop) GSSD units. General ly in a closed loop application, there is a percentage of antifreeze in the water. In these applications, the 20 degree F freezestat, along with the 7 psig safety pressure switc ...

  • Trane GSSD - page 16

    16 GSSD Units Coupled with TWE Air Handlers The GSSD IS coupled with the TWE- E series. Table 4 may be used to det er- mine the amount of charge necessary for the split unit system withou t any refrigerant line connecting the two. Table 5 can be used to determine the amount of refrigerant needed for lines. By adding the two weights toget her, the a ...

  • Trane GSSD - page 17

    17 Refrigeration System ! Compr essor: The unit includes a high efficiency scroll compressor with and internal v ibration isolator that absorbs start ing and stopping energy . It also contains an internal overload protection. External vibration isolatio n is provided by rubber mounting devices located underneath the mounting base of the compressor ...

  • Trane GSSD - page 18

    18 Accessory Items Note: The following eq ui pment may be pur- chased thr ough the near est T rane dis- tributor . ! W ater Regulating V alve Assembly : The water regulating valve assembly consists of a direct acting valve and a reverse acting valve. The direct acting valve opens in response to an increase in discharge pressure during the cooling c ...

メーカー Trane カテゴリー Heat Pump

Trane GSSDのメーカーから受け取ることができるドキュメントは、いくつかのグループに分けられます。その一部は次の通りです:
- #BRANDの図面#
- GSSDの取扱説明書
- Traneの製品カード
- パンフレット
- またはTrane GSSDの消費電力シール
それらは全部重要ですが、デバイス使用の観点から最も重要な情報は、Trane GSSDの取扱説明書に含まれています。

取扱説明書と呼ばれる文書のグループは、Trane GSSDの取り付け説明書、サービスマニュアル、簡易説明書、またはTrane GSSDのユーザーマニュアル等、より具体的なカテゴリーに分類されます。ご必要に応じてドキュメントを検索しましょう。私たちのウェブサイトでは、Trane GSSDの製品を使用するにあたって最も人気のある説明書を閲覧できます。

関連する取扱説明書

Trane GSSDデバイスの取扱説明書はどのようなものですか?
取扱説明書は、ユーザーマニュアル又は単に「マニュアル」とも呼ばれ、ユーザーがTrane GSSDを使用するのを助ける技術的文書のことです。説明書は通常、全てのTrane GSSDユーザーが容易に理解できる文章にて書かれており、その作成者はその分野の専門家です。

Traneの取扱説明書には、基本的な要素が記載されているはずです。その一部は、カバー/タイトルページ、著作権ページ等、比較的重要度の低いものです。ですが、その他の部分には、ユーザーにとって重要な情報が記載されているはずです。

1. Trane GSSDの説明書の概要と使用方法。説明書にはまず、その閲覧方法に関する手引きが書かれているはずです。そこにははTrane GSSDの目次に関する情報やよくある質問、最も一般的な問題に関する情報を見つけられるはずです。つまり、それらはユーザーが取扱説明書に最も期待する情報なのです。
2. 目次。Trane GSSDに関してこのドキュメントで見つけることができる全てのヒントの目次
3. Trane GSSDデバイスの基本機能を使うにあたってのヒント。 Trane GSSDのユーザーが使い始めるのを助けてくれるはずです。
4. トラブルシューティング。Trane GSSDに関する最も重要な問題を診断し、解決するために役立つ体系化された手続き
5. FAQ。よくある質問
6. 連絡先。一人では問題を解決できない場合に、その国におけるTrane GSSDのメーカー/サービスへの連絡先に関する情報。

Trane GSSDについてご質問がありますか?

次のフォームを使用してください

見つけた説明書を読んでもTrane GSSDの問題を解決できない場合、下記のフォームを使用して質問をしましょう。ユーザーのどなたかがTrane GSSDで同様の問題を抱えていた場合、その解決方法を共有したいと考えるかもしれません。

画像のテキストを入力してください

コメント (0)