Summary
  • Friedrich HazardGard 60 Hz - page 1

    SH15L30-B SH20L30-B HG-SVC-PRTS-07 (3-07) R oom Air Conditioners 60 Hz Mode ls 20 0 7 Ser vi ce & P ar ts Manu al ...

  • Friedrich HazardGard 60 Hz - page 2

    2 T ABLE OF CONT EN TS Speci fi cations ...................................................................................................................... ................................... 3 Per formance Data ............................................................................................................. ........................ ...

  • Friedrich HazardGard 60 Hz - page 3

    3 EV APORA T OR AIR TEMP . DEG. F EV APORA TOR TEMP . DEG. F CONDENSER TEMP . DEG. F Discharge T emp Suction T emp Liquid T emp Super Heat Sub- Cooling OPERA TING PRESSURES ELECTRICAL RA TINGS R-22 REF . Evap CFM Motor RPM BREAKER FUSE Discharge Air T emp. Drop F . E(in) E(out) Suction Discharge Amps Cool Amps Heat Locked Rotor Amps Charge in OZ. 6 ...

  • Friedrich HazardGard 60 Hz - page 4

    4 COMPRESSOR WINDING TEST (Figure 2.) Remov e the c ompress or terminal box c over and disconnect the wires from t he terminals. Using an ohmmeter , c heck c ontinuit y across the follow ing: COMPONENT OPERA TION AND TESTING COM PRE SSO RS Compress ors are single phase, 208 /23 0 volt. All c ompres sor motors are per manent split capaci tor t ype, ...

  • Friedrich HazardGard 60 Hz - page 5

    5 F AN MOTOR (Figure 4) A 230 volt single phase per manent split capacitor m otor is used to drive the evaporator blower and condenser fan. A running c apacitor is wired acros s the star t and r un terminals of the motor . The motor is totally enc losed and is protected with a line volt- age overload located inter nally of the motor . The motor sha ...

  • Friedrich HazardGard 60 Hz - page 6

    6 THERMOST A T A cross ambient ther most at is used to maintain the desire d comfor t level . The ther most at reacts only to a change in temperature at the bulb location. Impor t ant to the succ essful operation of the unit is the posit ion of the sensing bulb in relation to the evaporator ( see Figure 8 ) . TEST Remove the wires from the ther mos ...

  • Friedrich HazardGard 60 Hz - page 7

    7 NOTE: This procedure can be sped up by the use of heat lamps, or by breaking the v acuum with refr igerant o r d r y n i t r o g e n a t 5 , 0 0 0 m i c r o n s . P r e s s u r e s y s t e m t o 5 PSIG and leave in the s ystem a minimum of 10 minutes. Recover refrigerant, and proceed wit h evacuation to a pressure of 20 0 micr ons or a minimum of ...

  • Friedrich HazardGard 60 Hz - page 8

    8 TROUBLE SHOOTING PROBLEM POSSIBLE CAUSE TO CORRECT UNIT DO ES NOT RUN. Power disconnected. Check power source. System switch in “ O f f ” posit ion. Set switc h co rrec tly . Branch circuit f use blown or circuit breaker tripped. Replace fuse, reset breaker . If repeats, check f use or breaker size. Check for shor ts in unit wir ing and co mp ...

  • Friedrich HazardGard 60 Hz - page 9

    9 TROUBL ESHOOTING ( Continu ed) PROBLEM POSSIBLE CAUSE TO CORRECT COM PRES SOR AT T E M P T S T O ST ART , OR RUNS FO R S H O R T PERIOD S ON L Y . CYCL ES O N OV ER LOA D. Compress or attempts to st ar t before syst em pressures are equal ized. Allow a minimum of t wo (2 ) minutes to allow pres sures to equalize before attempting to star t. Low o ...

  • Friedrich HazardGard 60 Hz - page 10

    10 TROUBL ESHOOTING ( Continu ed) PROBLEM POSSIBLE CAUSE TO CORRECT F AN M OTOR DOES NOT R U N. Defective switch (On- Of f ). Check co ntinuit y across ter minals 2 and 3. F an capacitor open. Check by substituting a known go od c apacitor of the s ame rating . Inoperative fan motor . Direct test fan m otor . Incor rec t wiring of fan c ircuit. Con ...

  • Friedrich HazardGard 60 Hz - page 11

    11 WIRING DIA GR AM MODELS SH 1 5L30 - B and SH20L30 - B ...

  • Friedrich HazardGard 60 Hz - page 12

    12 HAZARDGARD CABINET P ARTS ...

  • Friedrich HazardGard 60 Hz - page 13

    13 HAZARDGARD CHASSIS P ARTS ...

  • Friedrich HazardGard 60 Hz - page 14

    14 HAZARDGARD P ARTS LIST REF DESCRIPTION P ART NO# MODELS CODE ELECTRICAL P ARTS SH15L30-B SH20L30-B 1 COMPRESSOR 61 193549 1 600 1 COMPRESSOR 61 193550 1 600 2 MOTOR, F AN 61871426 11 1 0 2 MOTOR, F AN 61871427 11 1 0 5 SWITCH, ON-OFF DPST 60935300 1 1 130 * INSULA TOR, ELECTRICAL 61829700 1 1 399 * RELA Y , SOLID ST A TE 61 108800 2 2 399 6 THER ...

  • Friedrich HazardGard 60 Hz - page 15

    15 HAZARDGARD P ARTS LIST REF DESCRIPTION P ART NO# MODELS CODE CHASSIS P ARTS SH15L30-B SH20L30-B 8 HOLDER, THERMOST A T 61829800 1 1 999 1 1 KNOB, CONTROL 61493915 1 1 761 17 DECORA TIVE P ANEL 61822662 1 1 760 22 F AN BLADE, COND. 60542003 1 710 22 F AN BLADE, COND. 60542004 1 710 23 BLOWER WHEEL, EV AP . 60610616 1 700 23 BLOWER WHEEL, EV AP . ...

  • Friedrich HazardGard 60 Hz - page 16

    HG-SVC-PRTS-07 (3-07) FRIEDRICH AIR CONDITIONING CO. Post Of fi ce Box 1540 · San Antonio, T exas 78295-1540 4200 N. Pan Am Expressway · San Antonio, T exas 78218-5212 (210) 357-4400 · F AX (210) 357-4480 www .friedrich.com Printed in the U.S.A. Friedrich Air Conditioning Company P.O. Box 1540 San Antonio, TX 78295 210.357.4400 www.fri edri ch. ...

メーカー Friedrich カテゴリー Air Conditioner

Friedrich HazardGard 60 Hzのメーカーから受け取ることができるドキュメントは、いくつかのグループに分けられます。その一部は次の通りです:
- #BRANDの図面#
- HazardGard 60 Hzの取扱説明書
- Friedrichの製品カード
- パンフレット
- またはFriedrich HazardGard 60 Hzの消費電力シール
それらは全部重要ですが、デバイス使用の観点から最も重要な情報は、Friedrich HazardGard 60 Hzの取扱説明書に含まれています。

取扱説明書と呼ばれる文書のグループは、Friedrich HazardGard 60 Hzの取り付け説明書、サービスマニュアル、簡易説明書、またはFriedrich HazardGard 60 Hzのユーザーマニュアル等、より具体的なカテゴリーに分類されます。ご必要に応じてドキュメントを検索しましょう。私たちのウェブサイトでは、Friedrich HazardGard 60 Hzの製品を使用するにあたって最も人気のある説明書を閲覧できます。

関連する取扱説明書

Friedrich HazardGard 60 Hzデバイスの取扱説明書はどのようなものですか?
取扱説明書は、ユーザーマニュアル又は単に「マニュアル」とも呼ばれ、ユーザーがFriedrich HazardGard 60 Hzを使用するのを助ける技術的文書のことです。説明書は通常、全てのFriedrich HazardGard 60 Hzユーザーが容易に理解できる文章にて書かれており、その作成者はその分野の専門家です。

Friedrichの取扱説明書には、基本的な要素が記載されているはずです。その一部は、カバー/タイトルページ、著作権ページ等、比較的重要度の低いものです。ですが、その他の部分には、ユーザーにとって重要な情報が記載されているはずです。

1. Friedrich HazardGard 60 Hzの説明書の概要と使用方法。説明書にはまず、その閲覧方法に関する手引きが書かれているはずです。そこにははFriedrich HazardGard 60 Hzの目次に関する情報やよくある質問、最も一般的な問題に関する情報を見つけられるはずです。つまり、それらはユーザーが取扱説明書に最も期待する情報なのです。
2. 目次。Friedrich HazardGard 60 Hzに関してこのドキュメントで見つけることができる全てのヒントの目次
3. Friedrich HazardGard 60 Hzデバイスの基本機能を使うにあたってのヒント。 Friedrich HazardGard 60 Hzのユーザーが使い始めるのを助けてくれるはずです。
4. トラブルシューティング。Friedrich HazardGard 60 Hzに関する最も重要な問題を診断し、解決するために役立つ体系化された手続き
5. FAQ。よくある質問
6. 連絡先。一人では問題を解決できない場合に、その国におけるFriedrich HazardGard 60 Hzのメーカー/サービスへの連絡先に関する情報。

Friedrich HazardGard 60 Hzについてご質問がありますか?

次のフォームを使用してください

見つけた説明書を読んでもFriedrich HazardGard 60 Hzの問題を解決できない場合、下記のフォームを使用して質問をしましょう。ユーザーのどなたかがFriedrich HazardGard 60 Hzで同様の問題を抱えていた場合、その解決方法を共有したいと考えるかもしれません。

画像のテキストを入力してください

コメント (0)