    P OWER P ROTECTION U SER M A NUAL English 700-2200 VA 120 V PowerSure™ Interactive R DISCONTINUED PR ODUCT ...

  • Liebert 700-2200 VA - page 2

    2 IMPORTANT SAFETY INSTRUCTIONS WARNING: Do not attempt to service this product yourself except to replace the battery. Opening or removing the cover may expose you to dange rous voltages, even when the AC cord is disconne cted from the electrical outlet. Refer all servicing to qualified service pe rsonnel. 1. SAVE THESE INSTRUCTIONS. THIS MANUAL C ...

  • Liebert 700-2200 VA - page 3

    3 it, or the safety ground will be re moved. Operate UPS only from a properly grounded 120 VAC outlet (2 wire plu s ground). 9. The UPS is equipped with a grounded NEMA 5-15P or L5-30P input power plug (depending upon model ). Do not defeat the safety purpose of this plug. If unable to fully insert the plug into the wall outlet, contact a qualified ...

  • Liebert 700-2200 VA - page 4

    4 INTRODUCTION & SYS TEM DESCRIPTION Congratulations on your choice of the Liebert PowerSure™ Interactive Uninterruptible Po wer System (UPS). It provides conditioned power to microcomputers and other sensitive electronic e quipment. Upon generation, AC power is clean and stable. However, during transmission it may be subject to voltage sags, ...

  • Liebert 700-2200 VA - page 5

    5 MAJOR COMPONENTS TRANSIENT VOLTAGE SURGE SUPPRESSION (TVSS) AND EMI/RFI FILTERS These UPS components provide sur ge prot ection and filter Electromagnetic Interference (EMI) and Radio Frequenc y Interference (RFI ). They minimize any surges or interference present in the utility li ne and keep the sensitive equipment protected. AUTOMATIC VOLTA GE ...

  • Liebert 700-2200 VA - page 6

    6 MINI-TOWER INSTALLATION 1. Unpack the UPS carefully noting the packi ng method. Retain the bo x and packing material for possible future shipme nt. CAUTION: The UPS is heavy (see spec ificatio ns). Take proper precautio ns when lifting or moving it. 2. Visually inspect the UPS for freig ht dam age. Report damage to the carrier and your dealer. 3. ...

  • Liebert 700-2200 VA - page 7

    7 RACKMOUNT INSTALLATION 1. Unpack the UPS carefully noting th e packing method. Retain box and p acking material for possible future shipment. CAUTION: The UPS is heavy (see s pecifications). Take the proper precautions when lifting or moving the UPS. 2. Visually inspect the UPS for freight damage. Report any damage to the carrier and your dealer. ...

  • Liebert 700-2200 VA - page 8

    8 CONTROLS AND INDICATORS On/Off Button The On/Off button controls output power to connected load(s). CAUTION: Pressing the On/Off button w hen AC utility is not present will cause the UPS to begin operating from battery. This should not be performe d unless the UPS input is connected to a properly grounded receptacle. Load/Battery Lev el Indicator ...

  • Liebert 700-2200 VA - page 9

    9 POWERSURE™ INTERACTIVE MINI-TOWER 4 26 2 64 2 1 1 3 5 4 3 5 1 6 1 5 3 700 VA 1000 / 1400 VA 2200 VA Faul t I ndi cat or Lo ad/B att er y Lev el I ndi cat ors Alar m Silen ce/ Ba tte ry T es t B utt on On /O ff B utt on Util ity H igh /Low Indi cator Util ity/Ba ttery S t atu s Ind ic ato r 1- Output Receptacles 2- DB-9 Interface Port 3- AC Inle ...

  • Liebert 700-2200 VA - page 10

    10 POWERSURE™ INTERA CTI VE RACKMOUNT 2200 Model 1 3 4 62 3 6 1 5 5 5 700-1400 Models *700 Model has detachable cord 1- Output Receptacles 2- DB-9 Interface Port 3- AC Inlet 4- Intellislot™ Communications Port 5- Circuit Protector or Fuse 6- Site Wiring Fault Indicator On / Off Alarm Silence Load / Battery Utility High / Low Utility R On / Off ...

  • Liebert 700-2200 VA - page 11

    11 OPERATION NORMAL MODE OPERA TION During normal operation, utility po wer prov ides energ y to the UPS. The filters and the power conditioning circuit process this power to provide comp uter grade power to connected loads. The UPS maintains the batteries in a fully charged state. The front panel displa ys the percentage of load on the UPS output. ...

  • Liebert 700-2200 VA - page 12

    12 BATTERY MODE OPERATION Battery mode occurs in event of extreme input conditions or comp lete utility failure. The battery system along with the bi-directional conv erter generates power for the connected load. During battery mode an alarm so unds every 10 seconds. This will change to 2 beeps every 5 secon ds when battery runs low (approximatel y ...

  • Liebert 700-2200 VA - page 13

    13 COMMUNICATIONS INTERFACE PORT The PowerSure™ Interactive UPS contains a standar d DB-9F recepticle loc ated on the rear of the UPS unit. Several si gnals are provid ed on this port and are assigned as follows: PIN ASSIGNMENT DESCRIPTION 1 Low Battery (open collector) 2 UPS TxD (typical RS-232 levels) 3 UPS RxD (typical RS-232 levels) 4 Remote ...

  • Liebert 700-2200 VA - page 14

    14 UPS INTELLIGENT COMMUNICATIONS The PowerSure™ Interactive UPS has the capabi lity to communicate intelli gently with stand alone computers, network workstations, net work servers, or UNIX hosts via the DB-9 female connector locat ed on the rear of the UPS. By purchasi ng the optional Liebert SiteNet® 2 software package (sold sep arately), int ...

  • Liebert 700-2200 VA - page 15

    15 MINI-TOWER BATTERY REPLACEMENT CAUTION- A battery can present a risk of electrical shock and h igh short circuit current. The following precautions should be obs erved before replaci ng the batteries: • Turn off and disconnect the UPS from utility power prior to ope ning the battery replacement door. • Remove rings, watches, and other metal ...

  • Liebert 700-2200 VA - page 16

    16 MINI-TOWER BATTERY REPLACEMENT 700 VA Model To Disconnect: Gentl y pull wiring away To Connect: Connect red wire to red terminal, then black wire to black terminal by pushing towards connector 1000/1400 VA Model To Disconnect: Gentl y pull wiring away To Connect: Connect red wire to red terminal, then black wire to black terminal by pushing upwa ...

  • Liebert 700-2200 VA - page 17

    17 RACKMOUNT BATTERY REPLACEMENT CAUTION- A battery can present a risk of electrical shock and h igh short circuit current. The following precautions should be obs erved before replacin g the batteries: • Turn off and disconnect the UPS from utility power prior to ope ning the battery replacement door. • Remove rings, watches, and other metal o ...

  • Liebert 700-2200 VA - page 18

    18 Figure 3 Figure 5 Figure 4 Figure 1 Figure 2 Fi g ure 6 Figure 7 DISCONTINUED P R O D U C T ...

  • Liebert 700-2200 VA - page 19

    19 TROUBLESHOOTING The information b elow indicates vario us symptoms a user may encounter in the event the PowerSure™ Interactive UPS dev elo ps a problem. Use this inf ormation to determine whether external factors ca use the problem and ho w to remedy the situation. 1. The fault indicator will flash ever y second to indic ate the UPS detected ...

  • Liebert 700-2200 VA - page 20

    20 TROUBLESHOOTING GUIDE PROBLEM CAUSE SOLUTION UPS output short circuited or overloaded. Ensure UPS is off. Disco nnect all loads and ensure noth ing is lodged in output r eceptacles. Ensure loads are not de fective or shorted internally. UPS fails to start when On/Off button is pressed Internal fuse is blown, indicating internal fault. Do not att ...

  • Liebert 700-2200 VA - page 21

    21 POWERSURE™ INTERACTIVE TYPICAL BATTERY DISCHARGE CURVES (Discharge times are at 25° C ambient ) 0 25 50 75 100 0 20 40 60 80 Percent Load R un Ti me (Mi ns ) 0 25 50 75 100 0 20 40 60 80 Percent Load Run Tim e (Mins ) 0 25 50 75 100 0 20 40 60 80 P e r ce n t L oad R un Ti me (Mi ns ) 0 25 50 75 100 0 20 40 60 80 P e r ce n t L oad Run Tim e ...

  • Liebert 700-2200 VA - page 22

    22 AUDIBLE ALARM CONDITIONS CONDITION ALARM Battery mode (utility failure) One short beep every ten seconds; more than t wo minutes of run time remaining Low battery Two short beeps every five seconds; less than t wo minutes of run time remaining Battery replacement Two second beep every minute UPS output overload One short beep ever y second UPS f ...

  • Liebert 700-2200 VA - page 23

    23 MINI-TOWER SPECIFICATIONS Model Number PS700MT-120 PS1000MT- 120 PS1400MT-120 PS2200MT-120 Model Rating VA/W 700 / 450 1000 / 670 1400 / 950 2200 / 1600 DIMENSIONS: in (mm) Unit W x D x H 5.5 x 14.4 x 7.0 (140 x 365 x 178) 6.8 x 17.5 x 8.9 (172 x 447 x 227) 6.8 x 17.5 x 8.9 (172 x 447 x 227) 7.6 x 20.1 x 13.2 (194 x 511 x 336) Shipping W x D x H ...

  • Liebert 700-2200 VA - page 24

    24 RACKMOUNT SPECIFICATIONS Model Number PS700RM-120 PS1000RM-120 PS1400RM-120 PS2200RM-120 Model Rating VA/W 700 / 450 1000 / 670 1400 / 950 2200 / 1600 DIMENSIONS: in (mm) Unit W x D x H 19 x 18 x 5.25 (483 x 457 x 133) 19 x 18 x 5.25 (483 x 457 x 133) 19 x 18 x 5.25 (483 x 457 x 133) 19 x 18 x 7 (483 x 457 x 178) Shipping W x D x H 27.5 x 24 x 1 ...

  • Liebert 700-2200 VA - page 25

    2 5 DISCONTINUED P R O D U C T ...

  • Liebert 700-2200 VA - page 26

    1050 Dearborn Drive Columbus, OH 43229 614-888-0246 Technical Support U.S.A........................... ....................................1-800-222-5877 Outside the U.S.A ..................... ......................614-841-6755 U.K..................................... ........................... +44 (0) 1793 553355 France ......................... ...

メーカー Liebert カテゴリー Power Supply

Liebert 700-2200 VAのメーカーから受け取ることができるドキュメントは、いくつかのグループに分けられます。その一部は次の通りです:
- #BRANDの図面#
- 700-2200 VAの取扱説明書
- Liebertの製品カード
- パンフレット
- またはLiebert 700-2200 VAの消費電力シール
それらは全部重要ですが、デバイス使用の観点から最も重要な情報は、Liebert 700-2200 VAの取扱説明書に含まれています。

取扱説明書と呼ばれる文書のグループは、Liebert 700-2200 VAの取り付け説明書、サービスマニュアル、簡易説明書、またはLiebert 700-2200 VAのユーザーマニュアル等、より具体的なカテゴリーに分類されます。ご必要に応じてドキュメントを検索しましょう。私たちのウェブサイトでは、Liebert 700-2200 VAの製品を使用するにあたって最も人気のある説明書を閲覧できます。

関連する取扱説明書

Liebert 700-2200 VAデバイスの取扱説明書はどのようなものですか?
取扱説明書は、ユーザーマニュアル又は単に「マニュアル」とも呼ばれ、ユーザーがLiebert 700-2200 VAを使用するのを助ける技術的文書のことです。説明書は通常、全てのLiebert 700-2200 VAユーザーが容易に理解できる文章にて書かれており、その作成者はその分野の専門家です。

Liebertの取扱説明書には、基本的な要素が記載されているはずです。その一部は、カバー/タイトルページ、著作権ページ等、比較的重要度の低いものです。ですが、その他の部分には、ユーザーにとって重要な情報が記載されているはずです。

1. Liebert 700-2200 VAの説明書の概要と使用方法。説明書にはまず、その閲覧方法に関する手引きが書かれているはずです。そこにははLiebert 700-2200 VAの目次に関する情報やよくある質問、最も一般的な問題に関する情報を見つけられるはずです。つまり、それらはユーザーが取扱説明書に最も期待する情報なのです。
2. 目次。Liebert 700-2200 VAに関してこのドキュメントで見つけることができる全てのヒントの目次
3. Liebert 700-2200 VAデバイスの基本機能を使うにあたってのヒント。 Liebert 700-2200 VAのユーザーが使い始めるのを助けてくれるはずです。
4. トラブルシューティング。Liebert 700-2200 VAに関する最も重要な問題を診断し、解決するために役立つ体系化された手続き
5. FAQ。よくある質問
6. 連絡先。一人では問題を解決できない場合に、その国におけるLiebert 700-2200 VAのメーカー/サービスへの連絡先に関する情報。

Liebert 700-2200 VAについてご質問がありますか?

次のフォームを使用してください

見つけた説明書を読んでもLiebert 700-2200 VAの問題を解決できない場合、下記のフォームを使用して質問をしましょう。ユーザーのどなたかがLiebert 700-2200 VAで同様の問題を抱えていた場合、その解決方法を共有したいと考えるかもしれません。

画像のテキストを入力してください

コメント (0)