Manual Liebert 700-2200 VA

26 pages 0.59 mb
Download

Go to site of 26

Summary
  • Liebert 700-2200 VA - page 1

    P OWER P ROTECTION U SER M A NUAL English 700-2200 VA 120 V PowerSure™ Interactive R DISCONTINUED PR ODUCT ...

  • Liebert 700-2200 VA - page 2

    2 IMPORTANT SAFETY INSTRUCTIONS WARNING: Do not attempt to service this product yourself except to replace the battery. Opening or removing the cover may expose you to dange rous voltages, even when the AC cord is disconne cted from the electrical outlet. Refer all servicing to qualified service pe rsonnel. 1. SAVE THESE INSTRUCTIONS. THIS MANUAL C ...

  • Liebert 700-2200 VA - page 3

    3 it, or the safety ground will be re moved. Operate UPS only from a properly grounded 120 VAC outlet (2 wire plu s ground). 9. The UPS is equipped with a grounded NEMA 5-15P or L5-30P input power plug (depending upon model ). Do not defeat the safety purpose of this plug. If unable to fully insert the plug into the wall outlet, contact a qualified ...

  • Liebert 700-2200 VA - page 4

    4 INTRODUCTION & SYS TEM DESCRIPTION Congratulations on your choice of the Liebert PowerSure™ Interactive Uninterruptible Po wer System (UPS). It provides conditioned power to microcomputers and other sensitive electronic e quipment. Upon generation, AC power is clean and stable. However, during transmission it may be subject to voltage sags, ...

  • Liebert 700-2200 VA - page 5

    5 MAJOR COMPONENTS TRANSIENT VOLTAGE SURGE SUPPRESSION (TVSS) AND EMI/RFI FILTERS These UPS components provide sur ge prot ection and filter Electromagnetic Interference (EMI) and Radio Frequenc y Interference (RFI ). They minimize any surges or interference present in the utility li ne and keep the sensitive equipment protected. AUTOMATIC VOLTA GE ...

  • Liebert 700-2200 VA - page 6

    6 MINI-TOWER INSTALLATION 1. Unpack the UPS carefully noting the packi ng method. Retain the bo x and packing material for possible future shipme nt. CAUTION: The UPS is heavy (see spec ificatio ns). Take proper precautio ns when lifting or moving it. 2. Visually inspect the UPS for freig ht dam age. Report damage to the carrier and your dealer. 3. ...

  • Liebert 700-2200 VA - page 7

    7 RACKMOUNT INSTALLATION 1. Unpack the UPS carefully noting th e packing method. Retain box and p acking material for possible future shipment. CAUTION: The UPS is heavy (see s pecifications). Take the proper precautions when lifting or moving the UPS. 2. Visually inspect the UPS for freight damage. Report any damage to the carrier and your dealer. ...

  • Liebert 700-2200 VA - page 8

    8 CONTROLS AND INDICATORS On/Off Button The On/Off button controls output power to connected load(s). CAUTION: Pressing the On/Off button w hen AC utility is not present will cause the UPS to begin operating from battery. This should not be performe d unless the UPS input is connected to a properly grounded receptacle. Load/Battery Lev el Indicator ...

  • Liebert 700-2200 VA - page 9

    9 POWERSURE™ INTERACTIVE MINI-TOWER 4 26 2 64 2 1 1 3 5 4 3 5 1 6 1 5 3 700 VA 1000 / 1400 VA 2200 VA Faul t I ndi cat or Lo ad/B att er y Lev el I ndi cat ors Alar m Silen ce/ Ba tte ry T es t B utt on On /O ff B utt on Util ity H igh /Low Indi cator Util ity/Ba ttery S t atu s Ind ic ato r 1- Output Receptacles 2- DB-9 Interface Port 3- AC Inle ...

  • Liebert 700-2200 VA - page 10

    10 POWERSURE™ INTERA CTI VE RACKMOUNT 2200 Model 1 3 4 62 3 6 1 5 5 5 700-1400 Models *700 Model has detachable cord 1- Output Receptacles 2- DB-9 Interface Port 3- AC Inlet 4- Intellislot™ Communications Port 5- Circuit Protector or Fuse 6- Site Wiring Fault Indicator On / Off Alarm Silence Load / Battery Utility High / Low Utility R On / Off ...

  • Liebert 700-2200 VA - page 11

    11 OPERATION NORMAL MODE OPERA TION During normal operation, utility po wer prov ides energ y to the UPS. The filters and the power conditioning circuit process this power to provide comp uter grade power to connected loads. The UPS maintains the batteries in a fully charged state. The front panel displa ys the percentage of load on the UPS output. ...

  • Liebert 700-2200 VA - page 12

    12 BATTERY MODE OPERATION Battery mode occurs in event of extreme input conditions or comp lete utility failure. The battery system along with the bi-directional conv erter generates power for the connected load. During battery mode an alarm so unds every 10 seconds. This will change to 2 beeps every 5 secon ds when battery runs low (approximatel y ...

  • Liebert 700-2200 VA - page 13

    13 COMMUNICATIONS INTERFACE PORT The PowerSure™ Interactive UPS contains a standar d DB-9F recepticle loc ated on the rear of the UPS unit. Several si gnals are provid ed on this port and are assigned as follows: PIN ASSIGNMENT DESCRIPTION 1 Low Battery (open collector) 2 UPS TxD (typical RS-232 levels) 3 UPS RxD (typical RS-232 levels) 4 Remote ...

  • Liebert 700-2200 VA - page 14

    14 UPS INTELLIGENT COMMUNICATIONS The PowerSure™ Interactive UPS has the capabi lity to communicate intelli gently with stand alone computers, network workstations, net work servers, or UNIX hosts via the DB-9 female connector locat ed on the rear of the UPS. By purchasi ng the optional Liebert SiteNet® 2 software package (sold sep arately), int ...

  • Liebert 700-2200 VA - page 15

    15 MINI-TOWER BATTERY REPLACEMENT CAUTION- A battery can present a risk of electrical shock and h igh short circuit current. The following precautions should be obs erved before replaci ng the batteries: • Turn off and disconnect the UPS from utility power prior to ope ning the battery replacement door. • Remove rings, watches, and other metal ...

  • Liebert 700-2200 VA - page 16

    16 MINI-TOWER BATTERY REPLACEMENT 700 VA Model To Disconnect: Gentl y pull wiring away To Connect: Connect red wire to red terminal, then black wire to black terminal by pushing towards connector 1000/1400 VA Model To Disconnect: Gentl y pull wiring away To Connect: Connect red wire to red terminal, then black wire to black terminal by pushing upwa ...

  • Liebert 700-2200 VA - page 17

    17 RACKMOUNT BATTERY REPLACEMENT CAUTION- A battery can present a risk of electrical shock and h igh short circuit current. The following precautions should be obs erved before replacin g the batteries: • Turn off and disconnect the UPS from utility power prior to ope ning the battery replacement door. • Remove rings, watches, and other metal o ...

  • Liebert 700-2200 VA - page 18

    18 Figure 3 Figure 5 Figure 4 Figure 1 Figure 2 Fi g ure 6 Figure 7 DISCONTINUED P R O D U C T ...

  • Liebert 700-2200 VA - page 19

    19 TROUBLESHOOTING The information b elow indicates vario us symptoms a user may encounter in the event the PowerSure™ Interactive UPS dev elo ps a problem. Use this inf ormation to determine whether external factors ca use the problem and ho w to remedy the situation. 1. The fault indicator will flash ever y second to indic ate the UPS detected ...

  • Liebert 700-2200 VA - page 20

    20 TROUBLESHOOTING GUIDE PROBLEM CAUSE SOLUTION UPS output short circuited or overloaded. Ensure UPS is off. Disco nnect all loads and ensure noth ing is lodged in output r eceptacles. Ensure loads are not de fective or shorted internally. UPS fails to start when On/Off button is pressed Internal fuse is blown, indicating internal fault. Do not att ...

  • Liebert 700-2200 VA - page 21

    21 POWERSURE™ INTERACTIVE TYPICAL BATTERY DISCHARGE CURVES (Discharge times are at 25° C ambient ) 0 25 50 75 100 0 20 40 60 80 Percent Load R un Ti me (Mi ns ) 0 25 50 75 100 0 20 40 60 80 Percent Load Run Tim e (Mins ) 0 25 50 75 100 0 20 40 60 80 P e r ce n t L oad R un Ti me (Mi ns ) 0 25 50 75 100 0 20 40 60 80 P e r ce n t L oad Run Tim e ...

  • Liebert 700-2200 VA - page 22

    22 AUDIBLE ALARM CONDITIONS CONDITION ALARM Battery mode (utility failure) One short beep every ten seconds; more than t wo minutes of run time remaining Low battery Two short beeps every five seconds; less than t wo minutes of run time remaining Battery replacement Two second beep every minute UPS output overload One short beep ever y second UPS f ...

  • Liebert 700-2200 VA - page 23

    23 MINI-TOWER SPECIFICATIONS Model Number PS700MT-120 PS1000MT- 120 PS1400MT-120 PS2200MT-120 Model Rating VA/W 700 / 450 1000 / 670 1400 / 950 2200 / 1600 DIMENSIONS: in (mm) Unit W x D x H 5.5 x 14.4 x 7.0 (140 x 365 x 178) 6.8 x 17.5 x 8.9 (172 x 447 x 227) 6.8 x 17.5 x 8.9 (172 x 447 x 227) 7.6 x 20.1 x 13.2 (194 x 511 x 336) Shipping W x D x H ...

  • Liebert 700-2200 VA - page 24

    24 RACKMOUNT SPECIFICATIONS Model Number PS700RM-120 PS1000RM-120 PS1400RM-120 PS2200RM-120 Model Rating VA/W 700 / 450 1000 / 670 1400 / 950 2200 / 1600 DIMENSIONS: in (mm) Unit W x D x H 19 x 18 x 5.25 (483 x 457 x 133) 19 x 18 x 5.25 (483 x 457 x 133) 19 x 18 x 5.25 (483 x 457 x 133) 19 x 18 x 7 (483 x 457 x 178) Shipping W x D x H 27.5 x 24 x 1 ...

  • Liebert 700-2200 VA - page 25

    2 5 DISCONTINUED P R O D U C T ...

  • Liebert 700-2200 VA - page 26

    1050 Dearborn Drive Columbus, OH 43229 614-888-0246 Technical Support U.S.A........................... ....................................1-800-222-5877 Outside the U.S.A ..................... ......................614-841-6755 U.K..................................... ........................... +44 (0) 1793 553355 France ......................... ...

Manufacturer Liebert Category Power Supply

Documents that we receive from a manufacturer of a Liebert 700-2200 VA can be divided into several groups. They are, among others:
- Liebert technical drawings
- 700-2200 VA manuals
- Liebert product data sheets
- information booklets
- or energy labels Liebert 700-2200 VA
All of them are important, but the most important information from the point of view of use of the device are in the user manual Liebert 700-2200 VA.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals Liebert 700-2200 VA, service manual, brief instructions and user manuals Liebert 700-2200 VA. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product Liebert 700-2200 VA.

Similar manuals

A complete manual for the device Liebert 700-2200 VA, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use Liebert 700-2200 VA by users. Manuals are usually written by a technical writer, but in a language understandable to all users of Liebert 700-2200 VA.

A complete Liebert manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual Liebert 700-2200 VA - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the Liebert 700-2200 VA, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the Liebert 700-2200 VA, that we can find in the current document
3. Tips how to use the basic functions of the device Liebert 700-2200 VA - which should help us in our first steps of using Liebert 700-2200 VA
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with Liebert 700-2200 VA
5. FAQ - Frequently Asked Questions
6. Contact detailsInformation about where to look for contact to the manufacturer/service of Liebert 700-2200 VA in a specific country, if it was not possible to solve the problem on our own.

Do you have a question concerning Liebert 700-2200 VA?

Use the form below

If you did not solve your problem by using a manual Liebert 700-2200 VA, ask a question using the form below. If a user had a similar problem with Liebert 700-2200 VA it is likely that he will want to share the way to solve it.

Copy the text from the picture

Comments (0)