    P OWER A VAILABILITY GXT5000R-208 with GXT5VBA TTW120 / GXT5VBA TT Batter y Cabinets U SER M ANUAL 5000 V A / 3750 W 208 V olt ...

  • Emerson GXT5000R-208 - page 2

    ...

  • Emerson GXT5000R-208 - page 3

    i T ABLE OF CONTENTS I MPORT ANT S AFETY I NSTRUCTIO NS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 G LOSSARY OF S YMBOLS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 I NTRODUCTIO N AND S YST EM D ESCRIPTION . . . . . . . . . . . . . . . . . . . . . . ...

  • Emerson GXT5000R-208 - page 4

    ii UPS C OMMUNI CATIONS WITH I NTELLISLOT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 M AINTENAN CE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 T ROUBLESHOOTIN G . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . ...

  • Emerson GXT5000R-208 - page 5

    1 IMPORT ANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS This manual co ntains important safe ty instructions. R ead all safety, in stallation, and o perat- ing instructions before operati ng the Uninterruptible Power System (UPS). Ad here to all warnings on th e unit and in this manua l. Follow all o perating and u ser instructions. Individ- uals ...

  • Emerson GXT5000R-208 - page 6

    2 SERVICE PERSONNEL INFORMA TION Servicing of batteri es should be performed by qualified p ersonnel knowle dgeable about ba tter- ies and the required precautio ns. Keep unaut horized personnel away from the batteries. PROPER DISPOSAL OF BATTERIES IS RE QUIRED. REFER TO YOUR LOCAL LAW S AND REGULATIONS FOR BATTERY DISPOSAL REQUIREMENTS. When repla ...

  • Emerson GXT5000R-208 - page 7

    3 GLOSSARY OF SYMBOLS • Risk of ele ctrical shock Indicates caution followed by important instructions Requests the user to consult the manual Indicates the unit contains a valve-regulated lead acid batter y Recycle DC voltage Equipment grounding conductor Bonded to ground AC voltage ON Standby i ...

  • Emerson GXT5000R-208 - page 8

    4 INTRODUCTION AND SYSTEM DESCRIPTION Congratulations on your choice of the Liebert GXT5 000R-208 U ninterruptible Pow er System (UPS). It provides conditioned power to microco mputers and other sensitiv e electronic equip- ment. Upon generation, AC power is cl ean and stable. However, during transmission and distribu- tion it may be subject to vol ...

  • Emerson GXT5000R-208 - page 9

    5 MAJOR COMPONENT S T ransient V olt age Surge Suppress ion (TVSS) & EMI/RFI Filters These UPS components provide surge protection and filter both elect romagnetic interference (EMI) and radio frequency interferen ce (RFI). They minimize any surg es or interference present in the ut ility line and k eep sensitive equipment protected. Rectifier/ ...

  • Emerson GXT5000R-208 - page 10

    6 Auxiliary 120 V / 400 V A Power The GXT5VBATTW120 battery cabinet also provides a tran sformer to provide up to 400 VA of 120 V power. Dynamic Byp ass The GXT5000R-208 provides a n alternate path fo r util ity power to the connected load in the unlikely event of a U PS malfuncti on, such as overload, ove rtemp erature, or an internal UPS failure. ...

  • Emerson GXT5000R-208 - page 11

    7 GENERAL DESCRIPTION Figure 1 GXT5000R-208 UPS - Front view Figure 2 GXT5000R-208 UPS - Rear view Air vents Control panel 20 A AC output with circuit breaker L6-20R Input cord L6-30P 30 A inpu t circuit breaker RELA YCARD-INT alarm contact s EPO DB-9 connector No user connection Cooling fans 30 A AC output L6-30R 208 V AC power to auxiliary power ...

  • Emerson GXT5000R-208 - page 12

    8 Figure 3 GXT5VBA TTW120 battery cabinet with auxiliary 120 V AC power - Rear view Figure 4 GXT5VBA TT batt ery cabinet - Rear view 208 V AC power from rear of GXT5000R-208 to auxiliar y power input connec tor (see Figure 2) DC cable from rear of GXT5000R-208 to external battery cabin et (see Figure 2) External battery connectors Auxiliary power 1 ...

  • Emerson GXT5000R-208 - page 13

    9 GENERAL INST ALLATION 1. Verify that the 30 A input circuit breaker on the GXT5000R-208 is in the OFF position. 2. For GXT5VBATTW120 only - C onnect the 208 V , one-foot-lon g cord, from the rear of the GXT5000R-208 to the mating external battery connector on the rear of the GXT5VBATTW120. 3. Connect the L6-20P from the load to the L6-20R on the ...

  • Emerson GXT5000R-208 - page 14

    10 CONTROLS AND INDICATORS ON / Manual Battery T e st button This button controls output power to connected load(s) and has two functions: • Transfer load to inverter • Manual battery test Pressing the ON / Manual Battery Test button will transfer the load from bypass to inverter in order to provide conditioned and protected power to the output ...

  • Emerson GXT5000R-208 - page 15

    11 Load Level indicators - 4 green, 1 amber , 1 red LEDs The Load Level indicators display the approximate load level at all times. • The four green LEDs indicate acceptable levels up to 95%. • The amber light comes on when the load level is 96-105%. • The last LED at right (red) indicates an overload (more than 105%) and warns of immi- nent ...

  • Emerson GXT5000R-208 - page 16

    12 MODES OF OPERATION Normal Mode Operation During normal operation, utility power provid es energy to the UPS. The filters, the power fac- tor correction circuit and the inverter process th is power to provide computer-grade pow er to connected loads. The UPS maintains the batteries in a fully charged sta te. Battery Mode Operation The UPS will en ...

  • Emerson GXT5000R-208 - page 17

    13 Byp ass Mode Bypass mode provides an alternate path for util ity power to the connecte d load in the unlikely event of a UPS malfunctio n, such as overload, ove rtemperat ure, or an internal UPS failure. Battery Recharge Mode Once utility power is restored, the UPS resu mes normal operation and the Battery Charger begins recharging the battery. ...

  • Emerson GXT5000R-208 - page 18

    14 OPERATING INSTRUCTIONS Tu r n O n Once the AC supply has been applied to the unit, power will be applied to the load ( bypass mode) immedia tely when the 30 A input circuit breaker i s initially cl osed. Turn the u nit ON (inverter mode) by pressing the ON button once. Manual Byp ass To manually put the unit in Bypass mode, press the Stand b y b ...

  • Emerson GXT5000R-208 - page 19

    15 OPTIONAL BATTERIES - PROGRAMMABLE RUN T IME The GXT5000R-208 may be equipp ed with up to five battery GXT5VBATT cabinets. At least one battery cabinet is required. The first bat tery cabinet may be a GXT5VBATTW120 if a 120V, 400V A auxiliary vo ltage source is nee ded. The enhanced communication provides an estima ted run time in minutes , takin ...

  • Emerson GXT5000R-208 - page 20

    16 Procedure to confirm the battery count 1. Apply AC inpu t power to the U PS. 2. Turn the UPS output off using the Standby bu tton. If the U PS is in inverter mod e, the load must first be transferred to bypass and then to off. 3. Once the UPS output is off, press and ho ld the Standby button continuously. The Sta ndby button must be held continu ...

  • Emerson GXT5000R-208 - page 21

    17 COMMUNICATIONS Do not exceed NEC Class 2 limits for any co nnection to the DB-25 connector on the Relay Interface card, the DB-9 communication port, and the EPO connector. Relay Interface Card Your GXT5000R-208 comes equi pped with the RELAYCARD-INT relay card. Connections must not exceed NEC Class 2 limits. The Intellislot ® Interface for Rela ...

  • Emerson GXT5000R-208 - page 22

    18 EPO This unit is equipped with provisions for the terminal connections for a UPS Emergency Power OFF Switch (EPO). The term inal is located on the rear of the UPS next to the DB-9 connector. If an EPO switch is used, it must have the characteristic s of an emergency but- ton—closed under normal conditions and held op en mechanically when opera ...

  • Emerson GXT5000R-208 - page 23

    19 SERIAL COMMUNICATIONS The UPStationGXT5000R-208 has a DB- 9 serial port male connector on the rear of the unit. Contact closure signals are not provided on this connector. Serial signals are provided on this port and are assigned as follows: This port is not directly compatible with th e Liebert M3LS9 P9S seri al communication cable supplied wit ...

  • Emerson GXT5000R-208 - page 24

    20 UPS COMMUNICATIONS WITH INTELLISLOT Your GXT5000R-208 come s equipped with the RELAYCAR D-IN T relay card. The addition of serial communi cations now ex pands the list of cards that may be used in the Intellislot. The UPStation GXT5000R-208 UPS is equipped wi th an Intellislot bay to provide advanced communication and mo nitoring op tions. Liebe ...

  • Emerson GXT5000R-208 - page 25

    21 MAINTENANCE The GXT5000R-208 UPS requires very little main tenance. The batteries are valve-regulated, nonspillab le, lead acid a nd should be kept charge d to obtain th eir design life . The UPS contin - uously charges the batteries when connected to the utility supply. When storing the UP S for an exte nded period, connect it to util ity power ...

  • Emerson GXT5000R-208 - page 26

    22 T ROUBLESHOOTING This section presents vario us problems a user mig ht encounter. Use this in formation to deter- mine whether external factors cause the problem an d how to remedy the situation. 1. The Fault LED will illuminate, in di cating the UPS detected a problem. 2. An alarm will sound , alerting that the UPS requires attention. 3. One or ...

  • Emerson GXT5000R-208 - page 27

    23 T able 3 T roubleshooting guide Fault classification LED display Audible alarm Condition Response time Bus fault C & F LEDs Continuous ± Bus V > 450 VDC 80 ms ± Bus V > 41 0 VDC 1.5 seconds ± Bus V < 230 VDC 80 ms |(Abnormal + Bus V)-(|-Bus V |)| > 40 VDC or |(+Bus V)-(Abnormal |-Bus V|)| > 35 VDC 2 minutes Inverter fault B ...

  • Emerson GXT5000R-208 - page 28

    24 S PECIFICATIONS MODEL NUMBER GXT5000R-208 MODEL RATING VA/W 5000 / 3750 DIMENSIONS: inches (mm) Unit: W x D x H 16.1 x 23.6 x 5.1(410 x 600 x 130) Shipping: W x D x H 23.2 x 31.1 x 12.8 (590 x 790 x 325) WEIGHT: lbs (kg) Unit 41.2 (18.7) Shipping 53.8 (24.4) INPUT AC PARAMETERS Voltage Range 208 VAC Nominal: 176-276 VAC Frequency 50/60 Hz, ±5%; ...

  • Emerson GXT5000R-208 - page 29

    25 BATTERY CABINET S PECIFICATIONS GXT5VBA TTW120 MODEL NUMBER GXT5VBATTW120 DIMENSIONS: inches (mm) Unit: W x D x H 16.1 x 23.6 x 5.1 (410 x 600 x 130) Shipping: W x D x H 23.2 x 31.1 x 12.8 (590 x 790 x 325) WEIGHT: lbs (kg) Unit 121.7 (55. 2) Shipping 132.3 (60.0) AC PARAMETER S – AUXILIARY AC POWER Nominal AC Input 208 VAC, 50/60 Hz, 400 VA, ...

  • Emerson GXT5000R-208 - page 30

    26 ...

  • Emerson GXT5000R-208 - page 31

    ...

  • Emerson GXT5000R-208 - page 32

    The Comp any Behind the Products With over a million installations around th e globe, Liebert is the world leader in computer protection systems. Since its founding in 1965, Liebert has developed a complete range of support and protection systems fo r sensitive electronics: • Environmental systems —Close-control air conditioning from 1 to 60 to ...

メーカー Emerson カテゴリー Power Supply

Emerson GXT5000R-208のメーカーから受け取ることができるドキュメントは、いくつかのグループに分けられます。その一部は次の通りです:
- #BRANDの図面#
- GXT5000R-208の取扱説明書
- Emersonの製品カード
- パンフレット
- またはEmerson GXT5000R-208の消費電力シール
それらは全部重要ですが、デバイス使用の観点から最も重要な情報は、Emerson GXT5000R-208の取扱説明書に含まれています。

取扱説明書と呼ばれる文書のグループは、Emerson GXT5000R-208の取り付け説明書、サービスマニュアル、簡易説明書、またはEmerson GXT5000R-208のユーザーマニュアル等、より具体的なカテゴリーに分類されます。ご必要に応じてドキュメントを検索しましょう。私たちのウェブサイトでは、Emerson GXT5000R-208の製品を使用するにあたって最も人気のある説明書を閲覧できます。

関連する取扱説明書

Emerson GXT5000R-208デバイスの取扱説明書はどのようなものですか?
取扱説明書は、ユーザーマニュアル又は単に「マニュアル」とも呼ばれ、ユーザーがEmerson GXT5000R-208を使用するのを助ける技術的文書のことです。説明書は通常、全てのEmerson GXT5000R-208ユーザーが容易に理解できる文章にて書かれており、その作成者はその分野の専門家です。

Emersonの取扱説明書には、基本的な要素が記載されているはずです。その一部は、カバー/タイトルページ、著作権ページ等、比較的重要度の低いものです。ですが、その他の部分には、ユーザーにとって重要な情報が記載されているはずです。

1. Emerson GXT5000R-208の説明書の概要と使用方法。説明書にはまず、その閲覧方法に関する手引きが書かれているはずです。そこにははEmerson GXT5000R-208の目次に関する情報やよくある質問、最も一般的な問題に関する情報を見つけられるはずです。つまり、それらはユーザーが取扱説明書に最も期待する情報なのです。
2. 目次。Emerson GXT5000R-208に関してこのドキュメントで見つけることができる全てのヒントの目次
3. Emerson GXT5000R-208デバイスの基本機能を使うにあたってのヒント。 Emerson GXT5000R-208のユーザーが使い始めるのを助けてくれるはずです。
4. トラブルシューティング。Emerson GXT5000R-208に関する最も重要な問題を診断し、解決するために役立つ体系化された手続き
5. FAQ。よくある質問
6. 連絡先。一人では問題を解決できない場合に、その国におけるEmerson GXT5000R-208のメーカー/サービスへの連絡先に関する情報。

Emerson GXT5000R-208についてご質問がありますか?

次のフォームを使用してください

見つけた説明書を読んでもEmerson GXT5000R-208の問題を解決できない場合、下記のフォームを使用して質問をしましょう。ユーザーのどなたかがEmerson GXT5000R-208で同様の問題を抱えていた場合、その解決方法を共有したいと考えるかもしれません。

画像のテキストを入力してください

コメント (0)