    TECHNICAL GUIDE SPLIT -SYSTEM HEA T PUMPS 14.5 SEER – R-410A MODELS: YHJF18 THRU 60 (1.5 THRU 5 NOMINAL TONS, 1 PHASE) Due to continuous prod uct improvemen t, specifications are subject to chan ge without notice. Vi si t us on the web at ww w .york.com Additional rating informa tion can be found at www .ahridirectory.org W ARRANTY S tandard 5-ye ...

  • York SPLIT-SYSTEM YHJF18 THRU 60 - page 2

    510667-YTG-B-0509 2 Johnson Controls Unitary Products All dimensions are in inche s. They are su bject to change with- out notice. Certified dimensions will be provi ded upon request. Physical and Electrica l Data MODEL YHJF18 S41S1 YHJF24 S41S1 YHJF30 S41S1 YHJF36 S41S1 YHJF42 S41S1 YHJF48 S41S1 YHJF60 S41S1 Unit Supply V oltage 208-230V , 1 ? ...

  • York SPLIT-SYSTEM YHJF18 THRU 60 - page 3

    510667-YTG-B-0509 Johnson Controls Unitary Pro ducts 3 PROCEDURES: 1. Unit factory charge listed on the u nit nameplate includes re friger ant for the condenser, the smallest evaporator and 15 feet of interconnecting line tub ing. 2. V erify the TXV and additional charge required for specific evaporator coil in the system u sing the above table. 3. ...

  • York SPLIT-SYSTEM YHJF18 THRU 60 - page 4

    510667-YTG-B-0509 4 Johnson Controls Unitary Products — = Not applicable. COOLING CAP ACITY - With Air Handler Coils UNIT MODEL AIR HANDLER COIL MODEL 1 ST AGE COOLING MODEL W RA TED CFM NET MBH SEER EER TOT AL SENS. 14.5 SEER HP WITH MV - V ARIABLE SPEED YHJF18S41S1 MV12B 17 FC/MC35B – 600 18.0 13.0 15.00 12.50 MV12B 17 FC/MC43B – 600 18.0 1 ...

  • York SPLIT-SYSTEM YHJF18 THRU 60 - page 5

    510667-YTG-B-0509 Johnson Controls Unitary Pro ducts 5 COOLING CAP ACITY - With High Efficiency Motor Furnaces UNIT MODEL FURNACE MODEL COIL MODEL 1 WS T A G E COOLING RA TED CFM Net MBH SEER EER TOT AL SENS. 14.5 SEER HP WITH V ARIABLE SPEED FURNACES 2 YHJF18S41S1 T*(8,L)X*A12 FC/MC/PC32A 14 – 590 18.0 13.0 15.00 12.50 Y*(8,L)C*A12 FC/MC/PC32A 1 ...

  • York SPLIT-SYSTEM YHJF18 THRU 60 - page 6

    510667-YTG-B-0509 6 Johnson Controls Unitary Products YHJF36S41S1 T*(8,L)X*A12 FC/MC/PC37A 14 – 1290 35.8 27.4 14.50 12.00 T*(8,L)X*B12 FC/MC/PC43B 17 – 1300 35.8 27.4 14.50 12.00 T*(8,L)X*C16 FC/MC/PC43C 21 – 1 175 35.4 26.4 15.00 12.50 T*(8,L)X*C20 FC/MC/PC43C 21 – 1250 36.0 27.4 15.00 12.50 T*9X*B12 FC/MC/PC43B 17 – 1270 35.8 27.4 14.5 ...

  • York SPLIT-SYSTEM YHJF18 THRU 60 - page 7

    510667-YTG-B-0509 Johnson Controls Unitary Pro ducts 7 CP equals MBH output divided by (total KW input x 3.412). HSPF (Heating Seasonal Performance Factor) is the total heat ing output durin g a normal annual usage period for hea ting divided by th e total electric power input during the same period. — = Not Applicable. HEA TING PERFORMANCE - W ...

  • York SPLIT-SYSTEM YHJF18 THRU 60 - page 8

    510667-YTG-B-0509 8 Johnson Controls Unitary Products HEA TING CAP ACIT Y - With High Efficiency Motor Fu rnaces MODEL FURNACE MODEL COIL 1 MODEL ARI HEA TING 2 47  F1 7  FH S P F MBH COP KW MBH COP KW STD 14.5 SEER HP WITH V ARIABLE SPEED FUR NACES 3 YHJF18S41S1 T*(8,L)X*A12 FC/MC/PC32A 17. 9 3.84 1.37 10.8 2.54 1 .25 9.00 Y*(8,L)C*A12 F C/M ...

  • York SPLIT-SYSTEM YHJF18 THRU 60 - page 9

    510667-YTG-B-0509 Johnson Controls Unitary Pro ducts 9 CP equals MBH output divided by (total KW input x 3.412). HSPF (Heating Seasonal Performance Factor) is the total heat ing output durin g a normal annual usage period for hea ting divided by th e total electric power input during the same period. — = Not Applicable. YHJF36S41S1 T*(8,L)X*A12 F ...

  • York SPLIT-SYSTEM YHJF18 THRU 60 - page 10

    510667-YTG-B-0509 10 Johnson Controls Unitary Products CP equals MBH output divided by (total KW input x 3.412). HSPF (Heating Seasonal Performance Factor) is the total heat ing output during a normal annual usage period for heating divided by the total electric power input during the same period. — = Not Applicable. ACCESSORIES Refer to Price Ma ...

  • York SPLIT-SYSTEM YHJF18 THRU 60 - page 11

    510667-YTG-B-0509 Johnson Controls Unitary Pro ducts 11 SOUND LEVEL - TYPICAL OCT A VE BAND SPE CTRUM (without tone adjustment) * Rated in accordance with ARI 270-200 8 S tandards. TYPICAL INST ALLA TION TYPICAL FIELD WIRING Size T est Condition 63 125 250 500 1000 2000 4000 8000 dBA SQI RSS Sound Power Calibration 1091 402 82.8 85.4 85.9 85.3 88.1 ...

  • York SPLIT-SYSTEM YHJF18 THRU 60 - page 12

    510667-YTG-B-0509 12 Johnson Controls Unitary Products Multipliers for determining the perfo rman ce with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (between 73- 87 F), sensible capacity incr eases by 1060 BTUH per 1000 CFM per degree above the listed temperature and decr eases by 1060 BTUH per 1000 CFM per ...

  • York SPLIT-SYSTEM YHJF18 THRU 60 - page 13

    510667-YTG-B-0509 Johnson Controls Unitary Pro ducts 13 Multipliers for determining the perform ance with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (between 73-87 F), se nsible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed temperature and decrease s by 1060 BTUH per 1000 CFM per d ...

  • York SPLIT-SYSTEM YHJF18 THRU 60 - page 14

    510667-YTG-B-0509 14 Johnson Controls Unitary Products Multipliers for determining the perfo rman ce with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (between 73- 87 F), sensible capacity incr eases by 1060 BTUH per 1000 CFM per degree above the listed temperature and decr eases by 1060 BTUH per 1000 CFM per ...

  • York SPLIT-SYSTEM YHJF18 THRU 60 - page 15

    510667-YTG-B-0509 Johnson Controls Unitary Pro ducts 15 Multipliers for determining the perform ance with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (between 73-87 F), se nsible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed temperature and decrease s by 1060 BTUH per 1000 CFM per d ...

  • York SPLIT-SYSTEM YHJF18 THRU 60 - page 16

    510667-YTG-B-0509 16 Johnson Controls Unitary Products Multipliers for determining the perfo rman ce with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (between 73- 87 F), sensible capacity incr eases by 1060 BTUH per 1000 CFM per degree above the listed temperature and decr eases by 1060 BTUH per 1000 CFM per ...

  • York SPLIT-SYSTEM YHJF18 THRU 60 - page 17

    510667-YTG-B-0509 Johnson Controls Unitary Pro ducts 17 Multipliers for determining the perform ance with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (between 73-87 F), se nsible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed temperature and decrease s by 1060 BTUH per 1000 CFM per d ...

  • York SPLIT-SYSTEM YHJF18 THRU 60 - page 18

    510667-YTG-B-0509 18 Johnson Controls Unitary Products Multipliers for determining the perfo rman ce with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (between 73- 87 F), sensible capacity incr eases by 1060 BTUH per 1000 CFM per degree above the listed temperature and decr eases by 1060 BTUH per 1000 CFM per ...

  • York SPLIT-SYSTEM YHJF18 THRU 60 - page 19

    510667-YTG-B-0509 Johnson Controls Unitary Pro ducts 19 Multipliers for determining the perform ance with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (between 73-87 F), se nsible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed temperature and decrease s by 1060 BTUH per 1000 CFM per d ...

  • York SPLIT-SYSTEM YHJF18 THRU 60 - page 20

    510667-YTG-B-0509 20 Johnson Controls Unitary Products Multipliers for determining the perfo rman ce with other indoor sections. HEA TING PERFORMANCE DA T A CONDENSING UNIT MO DEL NO YHJF18S41S1 EV APORA TOR COIL MODEL NO AHX30 AIR TEMP . ENTERING OUTDOOR UNIT AIR TEMP . ENTERING INDOOR COIL ID CFM 450 600 750 MBTUH KW C.O.P . MBTUH KW C.O.P . MBTU ...

  • York SPLIT-SYSTEM YHJF18 THRU 60 - page 21

    510667-YTG-B-0509 Johnson Controls Unitary Pro ducts 21 Multipliers for determining the perform ance with other indoor sections. HEA TING PERFORMANCE DA T A CONDENSING UNIT MODEL NO YHJF24S41S1 EV APORA TOR COIL MODEL NO AHX30 AIR TEMP . ENTERING OUTDOOR UNIT AIR TEMP . ENTERING INDOOR COIL ID CFM 600 800 1000 MBTUH KW C.O.P . MBTUH KW C.O.P . MBTU ...

  • York SPLIT-SYSTEM YHJF18 THRU 60 - page 22

    510667-YTG-B-0509 22 Johnson Controls Unitary Products Multipliers for determining the perfo rman ce with other indoor sections. HEA TING PERFORMANCE DA T A CONDENSING UNIT MO DEL NO YHJF30S41S1 EV APORA TOR COIL MODEL NO AHX36 AIR TEMP . ENTERING OUTDOOR UNIT AIR TEMP . ENTERING INDOOR COIL ID CFM 800 1000 1200 MBTUH KW C.O.P . MBTUH KW C.O.P . MB ...

  • York SPLIT-SYSTEM YHJF18 THRU 60 - page 23

    510667-YTG-B-0509 Johnson Controls Unitary Pro ducts 23 Multipliers for determining the perform ance with other indoor sections. HEA TING PERFORMANCE DA T A CONDENSING UNIT MODEL NO YHJF36S41S1 EV APORA TOR COIL MODEL NO AHX36 AIR TEMP . ENTERING OUTDOOR UNIT AIR TEMP . ENTERING INDOOR COIL ID CFM 1000 1200 1400 MBTUH KW C.O.P . MBTUH KW C.O.P . MB ...

  • York SPLIT-SYSTEM YHJF18 THRU 60 - page 24

    510667-YTG-B-0509 24 Johnson Controls Unitary Products Multipliers for determining the perfo rman ce with other indoor sections. HEA TING PERFORMANCE DA T A CONDENSING UNIT MO DEL NO YHJF42S41S1 EV APORA TOR COIL MODEL NO AHX60 AIR TEMP . ENTERING OUTDOOR UNIT AIR TEMP . ENTERING INDOOR COIL ID CFM 1200 1400 1600 MBTUH KW C.O.P . MBTUH KW C.O.P . M ...

  • York SPLIT-SYSTEM YHJF18 THRU 60 - page 25

    510667-YTG-B-0509 Johnson Controls Unitary Pro ducts 25 Multipliers for determining the perform ance with other indoor sections. HEA TING PERFORMANCE DA T A CONDENSING UNIT MODEL NO YHJF48S41S1 EV APORA TOR COIL MODEL NO F6FP060 AIR TEMP . ENTERING OUTDOOR UNIT AIR TEMP . ENTERING INDOOR COIL ID CFM 1400 1600 1800 MBTUH KW C.O.P . MBTUH KW C.O.P . ...

  • York SPLIT-SYSTEM YHJF18 THRU 60 - page 26

    Subject to change without notice. Publishe d in U.S.A. 510667-YTG-B-0509 Copyright © 2009 by Johnson Controls, Inc. All ri ghts reserved. Supersedes: 510667-YTG-A-0409 Johnson Controls Unitary Product s 5005 Y ork Drive Norman, OK 73069 Multipliers for determining the perfo rman ce with other indoor sections. HEA TING PERFORMANCE DA T A CONDENSING ...

Manufacturer York Category Heat Pump

Documents that we receive from a manufacturer of a York SPLIT-SYSTEM YHJF18 THRU 60 can be divided into several groups. They are, among others:
- York technical drawings
- SPLIT-SYSTEM YHJF18 THRU 60 manuals
- York product data sheets
- information booklets
- or energy labels York SPLIT-SYSTEM YHJF18 THRU 60
All of them are important, but the most important information from the point of view of use of the device are in the user manual York SPLIT-SYSTEM YHJF18 THRU 60.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals York SPLIT-SYSTEM YHJF18 THRU 60, service manual, brief instructions and user manuals York SPLIT-SYSTEM YHJF18 THRU 60. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product York SPLIT-SYSTEM YHJF18 THRU 60.

Similar manuals

A complete manual for the device York SPLIT-SYSTEM YHJF18 THRU 60, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use York SPLIT-SYSTEM YHJF18 THRU 60 by users. Manuals are usually written by a technical writer, but in a language understandable to all users of York SPLIT-SYSTEM YHJF18 THRU 60.

A complete York manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual York SPLIT-SYSTEM YHJF18 THRU 60 - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the York SPLIT-SYSTEM YHJF18 THRU 60, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the York SPLIT-SYSTEM YHJF18 THRU 60, that we can find in the current document
3. Tips how to use the basic functions of the device York SPLIT-SYSTEM YHJF18 THRU 60 - which should help us in our first steps of using York SPLIT-SYSTEM YHJF18 THRU 60
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with York SPLIT-SYSTEM YHJF18 THRU 60
5. FAQ - Frequently Asked Questions