    TECHNICAL GUIDE SPLIT -SYSTEM HEA T PUMPS 14.5 SEER – R-410A MODELS: YHJF18 THRU 60 (1.5 THRU 5 NOMINAL TONS, 1 PHASE) Due to continuous prod uct improvemen t, specifications are subject to chan ge without notice. Vi si t us on the web at ww w .york.com Additional rating informa tion can be found at www .ahridirectory.org W ARRANTY S tandard 5-ye ...

  • York SPLIT-SYSTEM YHJF18 THRU 60 - page 2

    510667-YTG-B-0509 2 Johnson Controls Unitary Products All dimensions are in inche s. They are su bject to change with- out notice. Certified dimensions will be provi ded upon request. Physical and Electrica l Data MODEL YHJF18 S41S1 YHJF24 S41S1 YHJF30 S41S1 YHJF36 S41S1 YHJF42 S41S1 YHJF48 S41S1 YHJF60 S41S1 Unit Supply V oltage 208-230V , 1 ? ...

  • York SPLIT-SYSTEM YHJF18 THRU 60 - page 3

    510667-YTG-B-0509 Johnson Controls Unitary Pro ducts 3 PROCEDURES: 1. Unit factory charge listed on the u nit nameplate includes re friger ant for the condenser, the smallest evaporator and 15 feet of interconnecting line tub ing. 2. V erify the TXV and additional charge required for specific evaporator coil in the system u sing the above table. 3. ...

  • York SPLIT-SYSTEM YHJF18 THRU 60 - page 4

    510667-YTG-B-0509 4 Johnson Controls Unitary Products — = Not applicable. COOLING CAP ACITY - With Air Handler Coils UNIT MODEL AIR HANDLER COIL MODEL 1 ST AGE COOLING MODEL W RA TED CFM NET MBH SEER EER TOT AL SENS. 14.5 SEER HP WITH MV - V ARIABLE SPEED YHJF18S41S1 MV12B 17 FC/MC35B – 600 18.0 13.0 15.00 12.50 MV12B 17 FC/MC43B – 600 18.0 1 ...

  • York SPLIT-SYSTEM YHJF18 THRU 60 - page 5

    510667-YTG-B-0509 Johnson Controls Unitary Pro ducts 5 COOLING CAP ACITY - With High Efficiency Motor Furnaces UNIT MODEL FURNACE MODEL COIL MODEL 1 WS T A G E COOLING RA TED CFM Net MBH SEER EER TOT AL SENS. 14.5 SEER HP WITH V ARIABLE SPEED FURNACES 2 YHJF18S41S1 T*(8,L)X*A12 FC/MC/PC32A 14 – 590 18.0 13.0 15.00 12.50 Y*(8,L)C*A12 FC/MC/PC32A 1 ...

  • York SPLIT-SYSTEM YHJF18 THRU 60 - page 6

    510667-YTG-B-0509 6 Johnson Controls Unitary Products YHJF36S41S1 T*(8,L)X*A12 FC/MC/PC37A 14 – 1290 35.8 27.4 14.50 12.00 T*(8,L)X*B12 FC/MC/PC43B 17 – 1300 35.8 27.4 14.50 12.00 T*(8,L)X*C16 FC/MC/PC43C 21 – 1 175 35.4 26.4 15.00 12.50 T*(8,L)X*C20 FC/MC/PC43C 21 – 1250 36.0 27.4 15.00 12.50 T*9X*B12 FC/MC/PC43B 17 – 1270 35.8 27.4 14.5 ...

  • York SPLIT-SYSTEM YHJF18 THRU 60 - page 7

    510667-YTG-B-0509 Johnson Controls Unitary Pro ducts 7 CP equals MBH output divided by (total KW input x 3.412). HSPF (Heating Seasonal Performance Factor) is the total heat ing output durin g a normal annual usage period for hea ting divided by th e total electric power input during the same period. — = Not Applicable. HEA TING PERFORMANCE - W ...

  • York SPLIT-SYSTEM YHJF18 THRU 60 - page 8

    510667-YTG-B-0509 8 Johnson Controls Unitary Products HEA TING CAP ACIT Y - With High Efficiency Motor Fu rnaces MODEL FURNACE MODEL COIL 1 MODEL ARI HEA TING 2 47  F1 7  FH S P F MBH COP KW MBH COP KW STD 14.5 SEER HP WITH V ARIABLE SPEED FUR NACES 3 YHJF18S41S1 T*(8,L)X*A12 FC/MC/PC32A 17. 9 3.84 1.37 10.8 2.54 1 .25 9.00 Y*(8,L)C*A12 F C/M ...

  • York SPLIT-SYSTEM YHJF18 THRU 60 - page 9

    510667-YTG-B-0509 Johnson Controls Unitary Pro ducts 9 CP equals MBH output divided by (total KW input x 3.412). HSPF (Heating Seasonal Performance Factor) is the total heat ing output durin g a normal annual usage period for hea ting divided by th e total electric power input during the same period. — = Not Applicable. YHJF36S41S1 T*(8,L)X*A12 F ...

  • York SPLIT-SYSTEM YHJF18 THRU 60 - page 10

    510667-YTG-B-0509 10 Johnson Controls Unitary Products CP equals MBH output divided by (total KW input x 3.412). HSPF (Heating Seasonal Performance Factor) is the total heat ing output during a normal annual usage period for heating divided by the total electric power input during the same period. — = Not Applicable. ACCESSORIES Refer to Price Ma ...

  • York SPLIT-SYSTEM YHJF18 THRU 60 - page 11

    510667-YTG-B-0509 Johnson Controls Unitary Pro ducts 11 SOUND LEVEL - TYPICAL OCT A VE BAND SPE CTRUM (without tone adjustment) * Rated in accordance with ARI 270-200 8 S tandards. TYPICAL INST ALLA TION TYPICAL FIELD WIRING Size T est Condition 63 125 250 500 1000 2000 4000 8000 dBA SQI RSS Sound Power Calibration 1091 402 82.8 85.4 85.9 85.3 88.1 ...

  • York SPLIT-SYSTEM YHJF18 THRU 60 - page 12

    510667-YTG-B-0509 12 Johnson Controls Unitary Products Multipliers for determining the perfo rman ce with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (between 73- 87 F), sensible capacity incr eases by 1060 BTUH per 1000 CFM per degree above the listed temperature and decr eases by 1060 BTUH per 1000 CFM per ...

  • York SPLIT-SYSTEM YHJF18 THRU 60 - page 13

    510667-YTG-B-0509 Johnson Controls Unitary Pro ducts 13 Multipliers for determining the perform ance with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (between 73-87 F), se nsible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed temperature and decrease s by 1060 BTUH per 1000 CFM per d ...

  • York SPLIT-SYSTEM YHJF18 THRU 60 - page 14

    510667-YTG-B-0509 14 Johnson Controls Unitary Products Multipliers for determining the perfo rman ce with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (between 73- 87 F), sensible capacity incr eases by 1060 BTUH per 1000 CFM per degree above the listed temperature and decr eases by 1060 BTUH per 1000 CFM per ...

  • York SPLIT-SYSTEM YHJF18 THRU 60 - page 15

    510667-YTG-B-0509 Johnson Controls Unitary Pro ducts 15 Multipliers for determining the perform ance with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (between 73-87 F), se nsible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed temperature and decrease s by 1060 BTUH per 1000 CFM per d ...

  • York SPLIT-SYSTEM YHJF18 THRU 60 - page 16

    510667-YTG-B-0509 16 Johnson Controls Unitary Products Multipliers for determining the perfo rman ce with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (between 73- 87 F), sensible capacity incr eases by 1060 BTUH per 1000 CFM per degree above the listed temperature and decr eases by 1060 BTUH per 1000 CFM per ...

  • York SPLIT-SYSTEM YHJF18 THRU 60 - page 17

    510667-YTG-B-0509 Johnson Controls Unitary Pro ducts 17 Multipliers for determining the perform ance with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (between 73-87 F), se nsible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed temperature and decrease s by 1060 BTUH per 1000 CFM per d ...

  • York SPLIT-SYSTEM YHJF18 THRU 60 - page 18

    510667-YTG-B-0509 18 Johnson Controls Unitary Products Multipliers for determining the perfo rman ce with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (between 73- 87 F), sensible capacity incr eases by 1060 BTUH per 1000 CFM per degree above the listed temperature and decr eases by 1060 BTUH per 1000 CFM per ...

  • York SPLIT-SYSTEM YHJF18 THRU 60 - page 19

    510667-YTG-B-0509 Johnson Controls Unitary Pro ducts 19 Multipliers for determining the perform ance with other indoor sections. NOTE: For dry bulb temperatures dif ferent than those listed (between 73-87 F), se nsible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed temperature and decrease s by 1060 BTUH per 1000 CFM per d ...

  • York SPLIT-SYSTEM YHJF18 THRU 60 - page 20

    510667-YTG-B-0509 20 Johnson Controls Unitary Products Multipliers for determining the perfo rman ce with other indoor sections. HEA TING PERFORMANCE DA T A CONDENSING UNIT MO DEL NO YHJF18S41S1 EV APORA TOR COIL MODEL NO AHX30 AIR TEMP . ENTERING OUTDOOR UNIT AIR TEMP . ENTERING INDOOR COIL ID CFM 450 600 750 MBTUH KW C.O.P . MBTUH KW C.O.P . MBTU ...

  • York SPLIT-SYSTEM YHJF18 THRU 60 - page 21

    510667-YTG-B-0509 Johnson Controls Unitary Pro ducts 21 Multipliers for determining the perform ance with other indoor sections. HEA TING PERFORMANCE DA T A CONDENSING UNIT MODEL NO YHJF24S41S1 EV APORA TOR COIL MODEL NO AHX30 AIR TEMP . ENTERING OUTDOOR UNIT AIR TEMP . ENTERING INDOOR COIL ID CFM 600 800 1000 MBTUH KW C.O.P . MBTUH KW C.O.P . MBTU ...

  • York SPLIT-SYSTEM YHJF18 THRU 60 - page 22

    510667-YTG-B-0509 22 Johnson Controls Unitary Products Multipliers for determining the perfo rman ce with other indoor sections. HEA TING PERFORMANCE DA T A CONDENSING UNIT MO DEL NO YHJF30S41S1 EV APORA TOR COIL MODEL NO AHX36 AIR TEMP . ENTERING OUTDOOR UNIT AIR TEMP . ENTERING INDOOR COIL ID CFM 800 1000 1200 MBTUH KW C.O.P . MBTUH KW C.O.P . MB ...

  • York SPLIT-SYSTEM YHJF18 THRU 60 - page 23

    510667-YTG-B-0509 Johnson Controls Unitary Pro ducts 23 Multipliers for determining the perform ance with other indoor sections. HEA TING PERFORMANCE DA T A CONDENSING UNIT MODEL NO YHJF36S41S1 EV APORA TOR COIL MODEL NO AHX36 AIR TEMP . ENTERING OUTDOOR UNIT AIR TEMP . ENTERING INDOOR COIL ID CFM 1000 1200 1400 MBTUH KW C.O.P . MBTUH KW C.O.P . MB ...

  • York SPLIT-SYSTEM YHJF18 THRU 60 - page 24

    510667-YTG-B-0509 24 Johnson Controls Unitary Products Multipliers for determining the perfo rman ce with other indoor sections. HEA TING PERFORMANCE DA T A CONDENSING UNIT MO DEL NO YHJF42S41S1 EV APORA TOR COIL MODEL NO AHX60 AIR TEMP . ENTERING OUTDOOR UNIT AIR TEMP . ENTERING INDOOR COIL ID CFM 1200 1400 1600 MBTUH KW C.O.P . MBTUH KW C.O.P . M ...

  • York SPLIT-SYSTEM YHJF18 THRU 60 - page 25

    510667-YTG-B-0509 Johnson Controls Unitary Pro ducts 25 Multipliers for determining the perform ance with other indoor sections. HEA TING PERFORMANCE DA T A CONDENSING UNIT MODEL NO YHJF48S41S1 EV APORA TOR COIL MODEL NO F6FP060 AIR TEMP . ENTERING OUTDOOR UNIT AIR TEMP . ENTERING INDOOR COIL ID CFM 1400 1600 1800 MBTUH KW C.O.P . MBTUH KW C.O.P . ...

  • York SPLIT-SYSTEM YHJF18 THRU 60 - page 26

    Subject to change without notice. Publishe d in U.S.A. 510667-YTG-B-0509 Copyright © 2009 by Johnson Controls, Inc. All ri ghts reserved. Supersedes: 510667-YTG-A-0409 Johnson Controls Unitary Product s 5005 Y ork Drive Norman, OK 73069 Multipliers for determining the perfo rman ce with other indoor sections. HEA TING PERFORMANCE DA T A CONDENSING ...

Производитель York Категория Heat Pump

Документы, которые мы получаем от производителя устройства York SPLIT-SYSTEM YHJF18 THRU 60 мы можем разделить на несколько групп. Это в частности:
- технические чертежи York
- инструкции обслуживания SPLIT-SYSTEM YHJF18 THRU 60
- паспорта изделия York
- информационные брошюры
- энергетические этикетки York SPLIT-SYSTEM YHJF18 THRU 60
Все из них важны, однако самую важную информацию с точки зрения пользователя мы найдем в инструкции обслуживания York SPLIT-SYSTEM YHJF18 THRU 60.

Группа документов, определяемая как инструкции обслуживания, делится также на более подробные типы, такие как: Инструкции монтажа York SPLIT-SYSTEM YHJF18 THRU 60, инструкции обслуживания, короткие инструкции или инструкции пользователя York SPLIT-SYSTEM YHJF18 THRU 60. В зависимости от потребностей, Вам необходимо поискать требуемый документ. На нашем сайте Вы можете просмотреть самую популярную инструкцию использования изделия York SPLIT-SYSTEM YHJF18 THRU 60.

Похожие инструкции обслуживания

Полная инструкция обслуживания устройства York SPLIT-SYSTEM YHJF18 THRU 60, как должна выглядеть?
Инструкция обслуживания, определяемая также как пособие пользователя, или просто "руководство" - это технический документ, цель которого заключается в использовании York SPLIT-SYSTEM YHJF18 THRU 60 пользователями. Инструкции пишет, как правило технический писатель, языком, доступным для всех пользователей York SPLIT-SYSTEM YHJF18 THRU 60.

Полная инструкция обслуживания York, должна заключать несколько основных элементов. Часть из них менее важная, как например: обложка / титульный лист или авторские страницы. Однако остальная часть, должна дать нам важную с точки зрения пользователя информацию.

1. Вступление и рекомендации, как пользоваться инструкцией York SPLIT-SYSTEM YHJF18 THRU 60 - В начале каждой инструкции, необходимо найти указания, как пользоваться данным пособием. Здесь должна находится информация, касающаяся местонахождения содержания York SPLIT-SYSTEM YHJF18 THRU 60, FAQ и самых распространенных проблем - то есть мест, которые чаще всего ищут пользователи в каждой инструкции обслуживания
2. Содержание - индекс всех советов, касающихся York SPLIT-SYSTEM YHJF18 THRU 60, которое найдем в данном документе
3. Советы по использованию основных функций устройства York SPLIT-SYSTEM YHJF18 THRU 60 - которые должны облегчить нам первые шаги во время использования York SPLIT-SYSTEM YHJF18 THRU 60
4. Troubleshooting - систематизированный ряд действия, который поможет нам диагностировать а в дальнейшем очередность решения важнейших проблем York SPLIT-SYSTEM YHJF18 THRU 60
5. FAQ - чаще всего задаваемые вопросы
6. Контактные данные Информация о том, где искать контактные данные производителя / сервисного центра York SPLIT-SYSTEM YHJF18 THRU 60 в данной стране, если самостоятельно не получится решить проблему.

У вас вопрос, касающийся York SPLIT-SYSTEM YHJF18 THRU 60?

Воспользуйтесь формуляром, находящимся ниже

Если с помощью найденной инструкции Вы не решили свою проблему с York SPLIT-SYSTEM YHJF18 THRU 60, задайте вопрос, заполнив следующий формуляр. Если у какого то из пользователей была похожая проблема с York SPLIT-SYSTEM YHJF18 THRU 60 со всей вероятностью он захочет поделиться методом ее решения.

Перепишите текст с картинки

Комментарии (0)