    Powerware 9395 UPS 1000–1100 kVA Installation and Operation Manual ® For use with Three UPM (650–825 kVA) and Four UPM (1000–1100 kVA) UPS Models ...

  • Powerware 10001100 kVA - page 2

    IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important instructions that you should follow during installation and maintenance of the UPS and batteries. Please read all instructions before operating the equipment and save this manual for future reference. CONSIGNES DE SÉCURITÉ IMPORTANTES CONSERVER CES INSTRUCTIONS C ...

  • Powerware 10001100 kVA - page 3

    EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com i Table of Contents 1 Introduction 1−1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1.1 UPS Standard Features 1−2 . . . . . . ...

  • Powerware 10001100 kVA - page 4

    TABLE OF CONTENTS EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com ii 4.9 Installing Interface Connections 4−26 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.9.1 TB1, TB2, and ...

  • Powerware 10001100 kVA - page 5

    TABLE OF CONTENTS EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com iii 7.3 Single UPS Operation 7−11 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7.3.1 Starting t ...

  • Powerware 10001100 kVA - page 6

    TABLE OF CONTENTS EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com iv 10 Product Specifications 10−1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10.1 Model Numbers 10−1 . . . . . . . . . . . ...

  • Powerware 10001100 kVA - page 7

    TABLE OF CONTENTS EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com v List of Figures Figure 1-1. Powerware 9395 Four UPM UPS (1000–1100 kVA) 1−2 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Figure 1-2. Powerware 9395 Thr ...

  • Powerware 10001100 kVA - page 8

    TABLE OF CONTENTS EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com vi Figure 5-1. Powerware Hot Sync CAN Bridge Card 5−1 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Figure 5-2. Powerware Hot Sync CAN Bri ...

  • Powerware 10001100 kVA - page 9

    EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 1−1 Chapter 1 Introduction Eaton’s Powerware ® 9395 uninterruptible power supply (UPS) is a true online, continuous−duty, transformerless, double−conversion, solid−state, three−phase system, providing conditioned and unin ...

  • Powerware 10001100 kVA - page 10

    INTRODUCTION EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 1−2 ISBM SECTION UPM SECTION FI−UPM Figure 1-1. Powerware 9395 Four UPM UPS (1000–1100 kVA) 1.1 UPS Standard Features The UPS has many standard features that provide cost-effective and consistently reliable power pr ...

  • Powerware 10001100 kVA - page 11

    INTRODUCTION EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 1−3 ISBM SECTION UPM SECTION Figure 1-2. Powerware 9395 Three UPM UPS (650–825 kVA) 1.1.3 Customer Interface S Building Alarm Monitoring – Up to five inputs in the UPS are available to connect the facility’s alarm ...

  • Powerware 10001100 kVA - page 12

    INTRODUCTION EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 1−4 1.1.5 Power Management Software Powerware LanSafe ® Power Management Software is bundled as part of the Software Suite CD shipped with the UPS. See Chapter 8, Communication," for additional information. 1.2 ...

  • Powerware 10001100 kVA - page 13

    INTRODUCTION EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 1−5 1.2.4 Distributed Bypass System There are two types of redundancy: UPS based (based on the number of UPS units) and UPM based (based on the number of UPMs). Each UPS contains three or four UPMs. A distributed bypass ...

  • Powerware 10001100 kVA - page 14

    INTRODUCTION EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 1−6 1.4 Basic System Configurations The following basic UPS system configurations are possible: S Single UPS with three common battery UPMs, a common battery FI−UPM, and a standalone common battery system with a batte ...

  • Powerware 10001100 kVA - page 15

    INTRODUCTION EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 1−7 1.7 Symbols, Controls, and Indicators The following are examples of symbols used on the UPS or accessories to alert you to important information: RISK OF ELECTRIC SHOCK − Observe the warning associated with the ri ...

  • Powerware 10001100 kVA - page 16

    INTRODUCTION EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 1−8 1.9 Getting Help If help is needed with any of the following: S Scheduling initial startup S Regional locations and telephone numbers S A question about any of the information in this manual S A question this manual ...

  • Powerware 10001100 kVA - page 17

    EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 2−1 Chapter 2 Safety Warnings IMPORTANT SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS This manual contains important instructions that should be followed during installation and maintenance of the UPS and batteries. Read all instructi ...

  • Powerware 10001100 kVA - page 18

    SAFETY WARNINGS EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 2−2 S The operating environment should be maintained within the parameters stated in this manual. S Keep surroundings uncluttered, clean, and free from excess moisture. S Observe all DANGER, CAUTION, and WARNING noti ...

  • Powerware 10001100 kVA - page 19

    EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 2−1 Section I Installation ...

  • Powerware 10001100 kVA - page 20

    EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 2−2 ...

  • Powerware 10001100 kVA - page 21

    EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 3−1 Chapter 3 UPS Installation Plan and Unpacking Use the following basic sequence of steps to install the UPS: 1. Create an installation plan for the UPS system (Chapter 3). 2. Prepare your site for the UPS system (Chapter 3). 3. I ...

  • Powerware 10001100 kVA - page 22

    UPS INSTALLATION PLAN AND UNPACKING EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 3−2 For Field Installed UPM (FI−UPM) weights and dimensions, refe to the Powerware 9395 Field Installed UPM Mechanical Installation Manual , listed in paragraph 1.8 on page 1−7. Table 3-1. UPS ...

  • Powerware 10001100 kVA - page 23

    UPS INSTALLATION PLAN AND UNPACKING EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 3−3 Dimensions are in millimeters [inches]. Figure 3-1. UPS Cabinet Dimensions (Front View) Dimensions are in millimeters [inches]. Figure 3-2. UPS Cabinet Dimensions (Right Side View) ...

  • Powerware 10001100 kVA - page 24

    UPS INSTALLATION PLAN AND UNPACKING EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 3−4 Figure 3-3. ISBM Section Dimensions (Front View) Figure 3-4. UPM Section Dimensions (Front View) ...

  • Powerware 10001100 kVA - page 25

    UPS INSTALLATION PLAN AND UNPACKING EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 3−5 Front Dimensions are in millimeters [inches]. Figure 3-5. ISBM Section Dimensions (Top View) Front Dimensions are in millimeters [inches]. Figure 3-6. ISBM Section Dimensions (Bottom View) Fro ...

  • Powerware 10001100 kVA - page 26

    UPS INSTALLATION PLAN AND UNPACKING EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 3−6 Dimensions are in millimeters [inches]. CG CG Figure 3-8. ISBM Section Center of Gravity Dimensions are in millimeters [inches]. CG CG Figure 3-9. UPM Section Center of Gravity ...

  • Powerware 10001100 kVA - page 27

    UPS INSTALLATION PLAN AND UNPACKING EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 3−7 Dimensions are in millimeters [inches]. 115.8 [4.56] 114.3 [4.50] 0.87 [0.22] 88.9 [3.50] Front View 1.57 [0.40] Needed to remove key 95.3 [3.57] (Square) 1/2" Knockout Pattern (Typical 5 ...

  • Powerware 10001100 kVA - page 28

    UPS INSTALLATION PLAN AND UNPACKING EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 3−8 3.2.2 UPS System Power Wiring Preparation Read and understand the following notes while planning and performing the installation: S Refer to national and local electrical codes for acceptable ...

  • Powerware 10001100 kVA - page 29

    UPS INSTALLATION PLAN AND UNPACKING EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 3−9 For four UPM external wiring requirements, including the minimum AWG size of external wiring, see Table 3-4 for installations using a common battery system or Table 3-5 for installations using ...

  • Powerware 10001100 kVA - page 30

    UPS INSTALLATION PLAN AND UNPACKING EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 3−10 Table 3-5. Input/Output Ratings and External Wiring Requirements for the Four UPM Powerware 9395−1100/1000, and 9395−1100/1100 – Separate Battery Basic Unit Rating Units Rating 50/60 Hz ...

  • Powerware 10001100 kVA - page 31

    UPS INSTALLATION PLAN AND UNPACKING EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 3−11 Table 3-6. Input/Output Ratings and External Wiring Requirements for the Three UPM Powerware 9395−1100/650, 9395−1100/750, and 9395−1100/825 – Common Battery Basic Unit Rating Units R ...

  • Powerware 10001100 kVA - page 32

    UPS INSTALLATION PLAN AND UNPACKING EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 3−12 Table 3-7. Input/Output Ratings and External Wiring Requirements for the Three UPM Powerware 9395−1100/650, 9395−1100/750, and 9395−1100/825 – Separate Battery Basic Unit Rating Units ...

  • Powerware 10001100 kVA - page 33

    UPS INSTALLATION PLAN AND UNPACKING EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 3−13 Table 3-8. UPS Intercabinet Power Cable Terminations for the Four UPM Powerware 9395−1100/1000 and 9395−1100/1100, and the Thre e UPM Powerware 9395−1100/650, 9395−1100/750, and 9395? ...

  • Powerware 10001100 kVA - page 34

    UPS INSTALLATION PLAN AND UNPACKING EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 3−14 Terminals E1 through E12 are 2-hole busbar mountings for standard NEMA 2-hole barrel lugs. The power wiring connections for this equipment are rated at 90 ° C. See Table 3-10 for power cable ...

  • Powerware 10001100 kVA - page 35

    UPS INSTALLATION PLAN AND UNPACKING EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 3−15 Table 3-11. Supplied External Wiring Terminal Hardware Kit Part Size Quantity Terminals Used On Eaton Part Number Bolt, Grade 5 M10 x 25 mm 15 Ground 180190078−087 Bolt, Grade 5 M12 x 50 mm ...

  • Powerware 10001100 kVA - page 36

    UPS INSTALLATION PLAN AND UNPACKING EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 3−16 Conduit sizes were chosen from NEC Table 4, Electrical Metallic Tubing (EMT). See Table 3-13 for conduit requirements. Per NEC article 300, 3(B)(1), all three-phase conductors must be run in ...

  • Powerware 10001100 kVA - page 37

    UPS INSTALLATION PLAN AND UNPACKING EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 3−17 External overcurrent protection and disconnect are not provided by this product, but are required by codes. Refer to Table 3-4, Table 3-5, Table 3-6, or Table 3-7 starting on page 3−9 for w ...

  • Powerware 10001100 kVA - page 38

    UPS INSTALLATION PLAN AND UNPACKING EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 3−18 There is no manual DC disconnect device within the UPS. A battery disconnect switch is required for battery systems and may also be required by NEC or local codes. The battery disconnect swit ...

  • Powerware 10001100 kVA - page 39

    UPS INSTALLATION PLAN AND UNPACKING EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 3−19 3.2.3 UPS System Interface Wiring Preparation Control wiring for features and options should be connected at the customer interface terminal blocks located inside the UPS. W A R N I N G Do no ...

  • Powerware 10001100 kVA - page 40

    UPS INSTALLATION PLAN AND UNPACKING EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 3−20 S The REPO switch wiring must be in accordance with NEC Article 725 Class 2 requirements. S The maximum distance between the REPO and the UPS cannot exceed 150 meters (500 feet). S Alarm rela ...

  • Powerware 10001100 kVA - page 41

    UPS INSTALLATION PLAN AND UNPACKING EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 3−21 3.3 Inspecting and Unpacking the UPS Cabinets The UPS cabinet is divided into two sections palleted separately for shipping. The sections are shipped bolted to wooden pallets (see Figure 3-11 ...

  • Powerware 10001100 kVA - page 42

    UPS INSTALLATION PLAN AND UNPACKING EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 3−22 4. Remove the protective covering from the cabinets. 5. Remove the packing material, and discard or recycle in a responsible manner. 6. Inspect the contents for any evidence of physical damag ...

  • Powerware 10001100 kVA - page 43

    UPS INSTALLATION PLAN AND UNPACKING EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 3−23 Figure 3-12. UPS Cabinet as Shipped on Pallet (UPM Section) ...

  • Powerware 10001100 kVA - page 44

    UPS INSTALLATION PLAN AND UNPACKING EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 3−24 This page intentionally left blank. ...

  • Powerware 10001100 kVA - page 45

    EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 4−1 Chapter 4 UPS System Installation 4.1 Preliminary Installation Information W A R N I N G Installation should be performed only by qualified personnel. Refer to the following while installing the UPS system: S Chapter 3 for cabin ...

  • Powerware 10001100 kVA - page 46

    UPS SYSTEM INSTALLATION EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 4−2 NOTE For the following steps, verify that the forklift or pallet jack is rated to handle the weight of the cabinet (see Table 3-1 on page 3−2 for cabinet weight). 1. If not already accomplished, use a f ...

  • Powerware 10001100 kVA - page 47

    UPS SYSTEM INSTALLATION EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 4−3 Shipping Bracket Bolts Shipping Bracket Bolts Pallet Right Side Shipping Bracket ISBM Removable Front Panels Figure 4-2. Removing the ISBM Section Right Side Shipping Bracket 4. Using a forklift (see the ...

  • Powerware 10001100 kVA - page 48

    UPS SYSTEM INSTALLATION EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 4−4 Shipping Bracket Bolts Shipping Bracket Bolts Pallet Left Side Shipping Bracket UPM Removable Front Panels Wireway Panel Figure 4-3. Removing the UPM Section Left Side Shipping Bracket ...

  • Powerware 10001100 kVA - page 49

    UPS SYSTEM INSTALLATION EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 4−5 Shipping Bracket Bolts Shipping Bracket Bolts Pallet Right Side Shipping Bracket Figure 4-4. Removing the UPM Section Right Side Shipping Bracket 4.3 Mechanically Joining the Sections NOTE The following p ...

  • Powerware 10001100 kVA - page 50

    UPS SYSTEM INSTALLATION EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 4−6 Left Top Panel Wireway Panel Left Middle Panel Corner Channel UPM Section Interior Left Side Panel Figure 4-5. Section Joining 5. Remove the screws securing the left top panel and remove the panel (see Fi ...

  • Powerware 10001100 kVA - page 51

    UPS SYSTEM INSTALLATION EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 4−7 UPM Wireway (Power wiring harnesses are coiled in this area.) Figure 4-6. ISBM and UPM Sections Joined 10. Reinstall the left top panel (see Figure 4-5) and secure using the retained hardware. NOTE Three ...

  • Powerware 10001100 kVA - page 52

    UPS SYSTEM INSTALLATION EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 4−8 Front View Base Bracket UPM Section Base ISBM Section Base Bracket from Kit Screw from Kit Screw from Kit Top View Rear Bracket UPM Section Top ISBM Section Top Screw from Kit Screw from Kit Bracket from ...

  • Powerware 10001100 kVA - page 53

    UPS SYSTEM INSTALLATION EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 4−9 NOTE Two cable lugs will be connected to each terminal stud. When connecting the cable lugs, install the first lug on the stud with the raised barrel portion facing the back of the cabinet. Install the se ...

  • Powerware 10001100 kVA - page 54

    UPS SYSTEM INSTALLATION EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 4−10 13. Locate the ground braid in the bottom left front corner of the UPM section. The ground braid is secured at the factory to the UPM section ground bolt. Route the ground braid through the wiring access ...

  • Powerware 10001100 kVA - page 55

    UPS SYSTEM INSTALLATION EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 4−11 (See Figure 4-9 for detail.) AC Input to UPMs AC Output from UPMs Phase C Phase A Phase B Neutral from UPMs (See Figure 4-11 for detail.) (See Figure 4-11 for detail.) Phase A Phase C Phase B (See Figure ...

  • Powerware 10001100 kVA - page 56

    UPS SYSTEM INSTALLATION EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 4−12 NOTE Two cable lugs will be connected to each terminal stud. When connecting the cable lugs, install the first lug on the stud with the raised barrel portion facing the back of the cabinet. Install the s ...

  • Powerware 10001100 kVA - page 57

    UPS SYSTEM INSTALLATION EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 4−13 DC Input to UPMs + Cable 1G3 Black UPM 1 (1E5A) Cable 1G3 Black DC Input to UPM s Cable 1G3 Red UPM 1 (1E4A) Cable 1G3 Red – Cable 2G3 Black UPM 2 (2E5A) Cable 2G3 Black Cable 3G3 Black UPM 3 (3E5A) Ca ...

  • Powerware 10001100 kVA - page 58

    UPS SYSTEM INSTALLATION EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 4−14 Wiring Access Location of J50, J51, J61, and J70 Coiled Harnesses Location of RJ−45 Coiled CAN Cable UPM Wireway Location of P61 Harness Location of P50, P51, and P70 Harnesses UPM Section Left Side Vi ...

  • Powerware 10001100 kVA - page 59

    UPS SYSTEM INSTALLATION EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 4−15 ISBM Section Right Side Inside View Pl1 Interface Board Front Figure 4-13. Pl1 Interface Board Location Pl1 Interface Board J39 Inverter CAN Connector Figure 4-14. J39 Location on Pl1 Interface Board ...

  • Powerware 10001100 kVA - page 60

    UPS SYSTEM INSTALLATION EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 4−16 4.5 Field Installed UPM Installation NOTE FI−UPM installation is not applicable to a three UPM model. If installing a four UPM model, install the FI−UPM using the instructions in the Powerware 9395 F ...

  • Powerware 10001100 kVA - page 61

    UPS SYSTEM INSTALLATION EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 4−17 Ventilation Grill Debris Shield (Remove shield before operating system.) ISBM Section Front Ventilation Grill Debris Shields (Remove shields before operating system.) UPM Section Front Figure 4-15. ISBM ...

  • Powerware 10001100 kVA - page 62

    UPS SYSTEM INSTALLATION EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 4−18 Top Entry Conduit Landing for AC Input and Output, and DC Input (Remove panel to drill or punch conduit holes.) TOP VIEW Interface Entry Conduit Landings for TB1 through TB3 Wiring and X−Slot Connectio ...

  • Powerware 10001100 kVA - page 63

    UPS SYSTEM INSTALLATION EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 4−19 3. Route the input and output cables through either the top or bottom of the cabinet to the UPS terminals. See Figure 4-16 through Figure 4-19 for wiring access information and terminal locations. Top Ac ...

  • Powerware 10001100 kVA - page 64

    UPS SYSTEM INSTALLATION EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 4−20 NOTE Required parallel system wiring length must be equal to ensure approximately equal current sharing when in Bypass mode. For proper operation the following must be true: 1A = 2A = 3A = 4A 1B = 2B = 3 ...

  • Powerware 10001100 kVA - page 65

    UPS SYSTEM INSTALLATION EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 4−21 (See Figure 4-19 for Detail AA.) DC Input from Battery + (E4) – (E5) DC Input from Battery AC Input to UPS Rectifier (A, B, C) AC Input to UPS Bypass (A, B, C) (See Figure 4-19 for Detail AA.) ISBM (Se ...

  • Powerware 10001100 kVA - page 66

    UPS SYSTEM INSTALLATION EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 4−22 Phase A (E6) Phase C (E8) Phase B (E7) AC Input to UPS Rectifier Phase A (E1) Phase C (E3) Phase B (E2) AC Input to UPS Bypass ‘ Front Section A–A Ground Terminals Figure 4-19. ISBM Section Power Ter ...

  • Powerware 10001100 kVA - page 67

    UPS SYSTEM INSTALLATION EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 4−23 4.8.2 Battery Power Wiring C A U T I O N When sizing the battery system, do not exceed the internal battery charger capabilities. See Chapter 10, Product Specifications," for maximum battery char ...

  • Powerware 10001100 kVA - page 68

    UPS SYSTEM INSTALLATION EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 4−24 DC Input from Battery + (E4) – (E5) DC Input from Battery Section B–B Front Figure 4-20. ISBM Section Power Terminal Detail BB – Common Battery ...

  • Powerware 10001100 kVA - page 69

    UPS SYSTEM INSTALLATION EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 4−25 DC Input from Battery + (E4) – (E5) DC Input from Battery DC Input from Battery + (E4) (UPM 1) (UPM 3) – (E5) DC Input from Battery (UPM 2) Section B–B Front – (E5) DC Input from Battery – (E5) ...

  • Powerware 10001100 kVA - page 70

    UPS SYSTEM INSTALLATION EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 4−26 4.9 Installing Interface Connections W A R N I N G Hazardous voltages are present near the user interface terminal area if the UPS is not totally disconnected. Use the procedures in the following paragra ...

  • Powerware 10001100 kVA - page 71

    UPS SYSTEM INSTALLATION EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 4−27 11. Reinstall the front door removed in Step 3 and secure with the retained hardware. 12. Close the door and secure the latch. X−Slot Communication Bays TB3 TB1 and TB2 (See Figure 4-23 for detail.) (S ...

  • Powerware 10001100 kVA - page 72

    UPS SYSTEM INSTALLATION EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 4−28 Table 4-1. TB1, TB2, and TB3 Interface Connections Terminal TB1 Name Description 1 REPO NC Input: Normally-closed dry contact used to activate UPS EPO from a remote switch. 2 REPO Return 3 REPO NO Input: ...

  • Powerware 10001100 kVA - page 73

    UPS SYSTEM INSTALLATION EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 4−29 X−Slot Communication Bays TB1 TB2 See Figure 4-25 for terminal assignments. Figure 4-23. Interface Terminal Detail TB2 NOTE Alarm relay contacts have a maximum current rating of 5A and a switched volta ...

  • Powerware 10001100 kVA - page 74

    UPS SYSTEM INSTALLATION EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 4−30 UPS Building Alarm 3 Building Alarm 3 Return Building Alarm 4 Building Alarm 5 Building Alarm 4 Return Building Alarm 5 Return NOTE All building alarm inputs require an isolated normally−open or normal ...

  • Powerware 10001100 kVA - page 75

    UPS SYSTEM INSTALLATION EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 4−31 4.9.2 TB1 Battery Interface Connections To install wiring to connections: 1. Verify the UPS system is turned off and all power sources are removed. See Chapter 7, UPS Operating Instructions," for ...

  • Powerware 10001100 kVA - page 76

    UPS SYSTEM INSTALLATION EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 4−32 Battery Disconnect TB1 Battery Aux Battery Aux Common 48 Vdc Battery Shunt Trip + 48 Vdc Battery Shunt Trip – UPS ST 5 6 7 8 NOTE Battery aux and DC shunt trip wiring should be a minimum of 18 AWG. 48 ...

  • Powerware 10001100 kVA - page 77

    UPS SYSTEM INSTALLATION EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 4−33 4.9.3 X−Slot Connections NOTE LAN and telephone drops for use with X−Slot cards must be provided by the customer. NOTE When installing external wiring to X−Slot cards, conduit must be installed to ...

  • Powerware 10001100 kVA - page 78

    UPS SYSTEM INSTALLATION EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 4−34 4.10 Installing a REPO Switch A latching−type Remote Emergency Power−off (REPO) switch can be used in an emergency to shut down the UPS and remove power to the critical load from a location away from ...

  • Powerware 10001100 kVA - page 79

    UPS SYSTEM INSTALLATION EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 4−35 5. To gain access to terminal block TB1 and the interface entry conduit landing plate, remove the screws securing the top internal safety shield panel and remove the panel. Retain the hardware for later ...

  • Powerware 10001100 kVA - page 80

    UPS SYSTEM INSTALLATION EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 4−36 12. If required, install wiring from the REPO switch to the trip circuitry of the upstream protective devices. A second contact block is provided on the REPO switch for this function (see Figure 4-29). T ...

  • Powerware 10001100 kVA - page 81

    UPS SYSTEM INSTALLATION EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 4−37 3 (NO) UPS TB1 REPO Switch (NO) Twisted Wires 1 (NC) 2 (Return) 4 (Return) REPO Switch (NC) NOTE REPO switch rating is 24 Vdc, 1A minimum. NOTE T he REPO switch must be a latching−type switch not tied ...

  • Powerware 10001100 kVA - page 82

    UPS SYSTEM INSTALLATION EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 4−38 Installation Checklist - All packing materials and restraints have been removed from each cabinet. - Each cabinet in the UPS system is placed in its installed location. - Joining brackets are installed b ...

  • Powerware 10001100 kVA - page 83

    UPS SYSTEM INSTALLATION EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 4−39 Distributed Bypass Installation Checklist - Each cabinet in the distributed bypass system is placed in its installed location. - All conduits and cables are properly routed to the UPS cabinets and to the ...

  • Powerware 10001100 kVA - page 84

    UPS SYSTEM INSTALLATION EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 4−40 Notes _________________________________________________________________________ _________________________________________________________________________ _________________________________________________ ...

  • Powerware 10001100 kVA - page 85

    EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 5−1 Chapter 5 Installing Options and Accessories 5.1 Installing an Optional Powerware Hot Sync CAN Bridge Card As an option, a Powerware Hot Sync Controller Area Network (CAN) Bridge Card, shown in Figure 5-1, can be installed to pr ...

  • Powerware 10001100 kVA - page 86

    INSTALLING OPTIONS AND ACCESSORIES EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 5−2 4. Read and understand the following notes while planning and performing the wiring installation: S Conduit must be installed between the UPS cabinet and the device for signal wiring. Conduit m ...

  • Powerware 10001100 kVA - page 87

    INSTALLING OPTIONS AND ACCESSORIES EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 5−3 Connections for Parallel System Control Connections for RMP II, RIM II, or SCM II Alarm J3 Connections for Bypass Status Figure 5-2. Powerware Hot Sync CAN Bridge Card Connections Table 5-1. Po ...

  • Powerware 10001100 kVA - page 88

    INSTALLING OPTIONS AND ACCESSORIES EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 5−4 5.2 Installing Distributed Bypass Control Wiring NOTE When installing external wiring to the Powerware Hot Sync CAN Bridge Card, conduit must be installed to the UPS cabinet. When installing in ...

  • Powerware 10001100 kVA - page 89

    INSTALLING OPTIONS AND ACCESSORIES EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 5−5 UPS 1 UPS 2 UPS 3 UPS 4 CAN (If Installed) (If Installed) Pull Chain NOTE This drawing is for distributed bypass wiring purposes and is not a floor layout plan. UPSs can be placed in any physic ...

  • Powerware 10001100 kVA - page 90

    INSTALLING OPTIONS AND ACCESSORIES EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 5−6 1 2 3 4 5 7 8 6 9 10 UPS 1 Twisted Pair Twisted Pair Twisted Pair Twisted Pair Twisted Pair Twisted Pair 1 2 3 4 5 7 8 6 9 10 1 2 3 4 5 7 8 6 9 10 UPS 2 1 2 3 4 5 7 8 6 9 10 1 2 3 4 5 7 8 6 9 1 ...

  • Powerware 10001100 kVA - page 91

    INSTALLING OPTIONS AND ACCESSORIES EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 5−7 NOTE NC and NO designations on MOB AUX contacts are defined with breaker in OFF (open) position. NOTE If MOB contacts have pigtail leads, use the same wire gauge to connect to UPS and use the c ...

  • Powerware 10001100 kVA - page 92

    INSTALLING OPTIONS AND ACCESSORIES EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 5−8 Table 5-4. Pull−Chain Wiring Terminations with MOBs From To Function UPS 1 CAN Bridge Card J3–1 (Alarm) MOB 1 Aux 1 NC MOB Open Alarm UPS 1 CAN Bridge Card J3–2 (Alarm Return) MOB 1 Aux 1 ...

  • Powerware 10001100 kVA - page 93

    INSTALLING OPTIONS AND ACCESSORIES EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 5−9 5.3 Installing an Optional Remote Monitor Panel II To install RMP II wiring: 1. Verify the UPS system is turned off and all power sources are removed. See Chapter 7, UPS Operating Instructio ...

  • Powerware 10001100 kVA - page 94

    INSTALLING OPTIONS AND ACCESSORIES EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 5−10 Terminal TB1 Signal Connections from the UPS Ground Terminal Terminal TB3 120 Vac Power Figure 5-7. Remote Monitor Panel II and Relay Interface Module II Terminal Locations UPS Can Card J3 120 ...

  • Powerware 10001100 kVA - page 95

    INSTALLING OPTIONS AND ACCESSORIES EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 5−11 NOTE Setup of the Powerware Hot Sync CAN Bridge Card must be performed by an authorized Eaton Customer Service Engineer. Contact an Eaton service representative to schedule a date. 11. To chec ...

  • Powerware 10001100 kVA - page 96

    INSTALLING OPTIONS AND ACCESSORIES EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 5−12 10. Restart the UPS. See Chapter 7, UPS Operating Instructions," for startup instructions. NOTE Setup of the Powerware Hot Sync CAN Bridge Card must be performed by an authorized Eaton ...

  • Powerware 10001100 kVA - page 97

    INSTALLING OPTIONS AND ACCESSORIES EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 5−13 5.5 Installing an Optional Supervisory Contact Module II To install SCM II wiring: 1. Verify the UPS system is turned off and all power sources are removed. See Chapter 7, UPS Operating Ins ...

  • Powerware 10001100 kVA - page 98

    INSTALLING OPTIONS AND ACCESSORIES EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 5−14 NOTE Setup of the Powerware Hot Sync CAN Bridge Card must be performed by an authorized Eaton Customer Service Engineer. Contact an Eaton service representative to schedule a date. 9. Install ...

  • Powerware 10001100 kVA - page 99

    INSTALLING OPTIONS AND ACCESSORIES EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 5−15 5.6 Accessory Mounting Dimensions Figure 5-12 through Figure 5-14 show the dimensions of the RMP II, the RIM II, and the SCM II. Flush Mount using #10 Pan Head Screws. (Mount with vent holes f ...

  • Powerware 10001100 kVA - page 100

    INSTALLING OPTIONS AND ACCESSORIES EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 5−16 Knockouts Provided on Five Surfaces Surface Mount using #10 Pan Head Screws for Hanging. (Mount with vent holes facing up.) Flush Mount using #10 Pan Head Screws. (Mount with vent holes facing ...

  • Powerware 10001100 kVA - page 101

    INSTALLING OPTIONS AND ACCESSORIES EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 5−17 Knockouts Provided on Five Surfaces Surface Mount using #10 Pan Head Screws for Hanging. (Mount with vent holes facing up.) Flush Mount using #10 Pan Head Screws. (Mount with vent holes facing ...

  • Powerware 10001100 kVA - page 102

    INSTALLING OPTIONS AND ACCESSORIES EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 5−18 This page intentionally left blank. ...

  • Powerware 10001100 kVA - page 103

    EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 5−19 Section II Operation ...

  • Powerware 10001100 kVA - page 104

    EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 5−20 ...

  • Powerware 10001100 kVA - page 105

    EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 6−1 Chapter 6 Understanding UPS Operation 6.1 UPS System Overview The Powerware 9395 UPS is a continuous−duty, solid-state, transformerless (at 480 Vac), three−phase, true online system that provides conditioned and uninterrupti ...

  • Powerware 10001100 kVA - page 106

    UNDERSTANDING UPS OPERATION EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 6−2 6.2 Single UPS A single UPS operates independently to support an applied load from the inverter, providing conditioned and uninterruptible AC power to the critical load from the output of the module. ...

  • Powerware 10001100 kVA - page 107

    UNDERSTANDING UPS OPERATION EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 6−3 Static Switch Rectifier Inverter K1 K3 Battery Converter Battery Battery Breaker Main Power Flow Trickle Current Energized De−Energized Closed Open Breakers Contactors Static Switch K5 Rectifier Inv ...

  • Powerware 10001100 kVA - page 108

    UNDERSTANDING UPS OPERATION EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 6−4 The internal bypass is comprised of a solid−state, silicon−controlled rectifier (SCR) static switch (SSW), a motorized wraparound bypass breaker CB4, and a backfeed protection contactor K5. The st ...

  • Powerware 10001100 kVA - page 109

    UNDERSTANDING UPS OPERATION EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 6−5 During a utility power failure, the rectifier no longer has an AC utility source from which to supply the DC output current required to support the inverter. The input contactor K1 opens and the batte ...

  • Powerware 10001100 kVA - page 110

    UNDERSTANDING UPS OPERATION EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 6−6 6.3 Single UPS Unit System Oneline Configurations The system oneline drawings in this section show the simplified internal structure of the UPS, battery supply, and basic maintenance bypass. Oneline D ...

  • Powerware 10001100 kVA - page 111

    UNDERSTANDING UPS OPERATION EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 6−7 Input Breaker (CB1) (optional) X−Slot Interface E1, E2, E3 E6, E7, E8, E12 48V Battery Shunt Trip NOTE Callout letters A , B , C , and D map to Table 3-4 on page 3−9. NOTE If the load requires a n ...

  • Powerware 10001100 kVA - page 112

    UNDERSTANDING UPS OPERATION EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 6−8 Input Breaker (CB1) (optional) E1, E2, E3 E6, E7, E8, E12 NOTE Callout letters A , B , C , and D map to Table 3-5 on page 3−10. NOTE If the load requires a neutral, a bypass source neutral must be p ...

  • Powerware 10001100 kVA - page 113

    UNDERSTANDING UPS OPERATION EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 6−9 Input Breaker (CB1) (optional) X−Slot Interface E1, E2, E3 E6, E7, E8, E12 48V Battery Shunt Trip NOTE Callout letters A , B , C , and D map to Table 3-4 on page 3−9. NOTE If the load requires a n ...

  • Powerware 10001100 kVA - page 114

    UNDERSTANDING UPS OPERATION EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 6−10 Input Breaker (CB1) (optional) X−Slot Interface E1, E2, E3 E6, E7, E8, E12 48V Battery Shunt Trip NOTE Callout letters A , B , C , and D map to Table 3-5 on page 3−10. NOTE If the load requires a ...

  • Powerware 10001100 kVA - page 115

    UNDERSTANDING UPS OPERATION EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 6−11 MAINTENANCE BYPASS PANEL Output from UPS MIS To UPS Rectifier Input RIB: Rectifier Input Breaker BIB: Bypass Input Breaker MIS: Maintenance Isolation Breaker MBP: Maintenance Bypass Breaker MBP Backf ...

  • Powerware 10001100 kVA - page 116

    UNDERSTANDING UPS OPERATION EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 6−12 6.4 Multiple UPS Distributed Bypass System Distributed bypass parallel operation extends the normal operation of Powerware 9395 UPSs by offering increased capacity and/or redundant capability. The pa ...

  • Powerware 10001100 kVA - page 117

    UNDERSTANDING UPS OPERATION EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 6−13 The UPSs continually monitor themselves and the incoming utility power and automatically switch between these modes as required, without operator intervention, except when manually switching to Bypas ...

  • Powerware 10001100 kVA - page 118

    UNDERSTANDING UPS OPERATION EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 6−14 If the utility AC power is interrupted or is out of specification, the UPSs automatically switch to Battery mode to support the critical load without interruption. When utility power returns, the UPS ...

  • Powerware 10001100 kVA - page 119

    UNDERSTANDING UPS OPERATION EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 6−15 In a distributed bypass system, each UPS operates similar to a single UPS, but in parallel with each other. The bypass source for the load is derived from the bypass input of one, two, three, or four ...

  • Powerware 10001100 kVA - page 120

    UNDERSTANDING UPS OPERATION EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 6−16 Main Power Flow UPS 1 UPS 2 UPS 3 UPS 4 Output to Critical Load Battery UPS Input Tie Cabinet UPS 1 Output Bypass Input UPS 2 Output UPS 3 Output UPS 4 Output Battery Battery Battery Closed Open Brea ...

  • Powerware 10001100 kVA - page 121

    UNDERSTANDING UPS OPERATION EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 6−17 6.5 Multiple UPS Distributed Bypass System Oneline Configurations The distributed bypass system oneline drawings in this section show the simplified internal structure of the UPS, battery supply, and ...

  • Powerware 10001100 kVA - page 122

    UNDERSTANDING UPS OPERATION EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 6−18 Battery Breaker Battery Converter Inverter K3 Fuse Rectifier K1 K2 Fuse Fuse Fuse E6 E7 E8 E12 K5 Static Switch Fuse CB4 E1 E2 E3 CB1 (optional) UPS 1 A B TIE CABINET (Optional) E AC Output to Critic ...

  • Powerware 10001100 kVA - page 123

    UNDERSTANDING UPS OPERATION EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 6−19 Battery Breaker Battery Converter Inverter K3 Fuse Rectifier K1 K2 Fuse Fuse Fuse E6 E7 E8 E12 K5 Static Switch Fuse CB4 E1 E2 E3 CB1 (optional) UPS 1 A B TIE CABINET (Optional) E AC Output to Critic ...

  • Powerware 10001100 kVA - page 124

    UNDERSTANDING UPS OPERATION EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 6−20 Battery Breaker Battery Converter Inverter K3 Fuse Rectifier K1 K2 Fuse Fuse Fuse E6 E7 E8 E12 K5 Static Switch Fuse CB4 E1 E2 E3 CB1 (optional) UPS 1 A B TIE CABINET (Optional) E AC Output to Critic ...

  • Powerware 10001100 kVA - page 125

    EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 7−1 Chapter 7 UPS Operating Instructions This section describes how to operate the UPS. NOTE Before starting the UPS, ensure all installation tasks are complete and a preliminary startup has been performed by authorized service pers ...

  • Powerware 10001100 kVA - page 126

    UPS OPERATING INSTRUCTIONS EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 7−2 7.1.1 Control Panel The control panel is used to set up and control the UPS, and to monitor UPS operation. For a description of the UPS control panel functions, see paragraph 7.2. 7.1.2 Circuit Breaker ...

  • Powerware 10001100 kVA - page 127

    UPS OPERATING INSTRUCTIONS EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 7−3 7.2.1 Status Indicators The four symbols on the right side of the control panel are status indicators . These colored light emitting diode (LED) lamps, work with the alarm horn to let you know the oper ...

  • Powerware 10001100 kVA - page 128

    UPS OPERATING INSTRUCTIONS EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 7−4 7.2.3 Using the LCD and Pushbuttons The LCD on the control panel provides an operator interface with the UPS system. Figure 7-3 identifies the display areas discussed in the following sections. METERS ...

  • Powerware 10001100 kVA - page 129

    UPS OPERATING INSTRUCTIONS EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 7−5 7.2.4 Using the Menu The UPS menu bar allows you to display data in the information area to help you monitor and control UPS operation. Table 7-2 shows the basic menu structure. Table 7-2. Display Func ...

  • Powerware 10001100 kVA - page 130

    UPS OPERATING INSTRUCTIONS EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 7−6 7.2.6 Display Menu Operation Table 7-3 describes the menu functions and and how to use them. Table 7-3. Display Menu Operation Function Subfunction Operation Events Press the EVENTS pushbutton on the m ...

  • Powerware 10001100 kVA - page 131

    UPS OPERATING INSTRUCTIONS EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 7−7 Table 7-3. Display Menu Operation (continued) Operation Subfunction Function Contrast Adjust Select CONTRAST from the System Setup Level 0 menu to display the Contrast Adjust screen. Use the left or ri ...

  • Powerware 10001100 kVA - page 132

    UPS OPERATING INSTRUCTIONS EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 7−8 Table 7-3. Display Menu Operation (continued) Operation Subfunction Function Com Port Selection The Com Port Setup screen allows selection of the serial COM port to set up. Select COM PORT SETUP from t ...

  • Powerware 10001100 kVA - page 133

    UPS OPERATING INSTRUCTIONS EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 7−9 Table 7-4. Typical System Status Messages Function Message UPS Shutdown; Bypass; Online Bypass Off; On; Available Maintenance Bypass Off; On Charger Charger Off; Charging UPM (during startup) DC Starti ...

  • Powerware 10001100 kVA - page 134

    UPS OPERATING INSTRUCTIONS EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 7−10 7.2.8 Load Off Screen The Load Off screen (Figure 7-6) is displayed when the LOAD OFF pushbutton is selected from the main menu bar, the UPS Control Command screen, or the Bypass Control Command scree ...

  • Powerware 10001100 kVA - page 135

    UPS OPERATING INSTRUCTIONS EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 7−11 7.3 Single UPS Operation NOTE A Field Installed UPM (FI−UPM) is always designated as UPM 4. 7.3.1 Starting the UPS in Normal Mode To start the UPS system: 1. If the UPS contains input breaker CB1, v ...

  • Powerware 10001100 kVA - page 136

    UPS OPERATING INSTRUCTIONS EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 7−12 7.3.2 Starting the UPS in Bypass Mode If the inverter output of the UPS is not available and the critical load needs to be energized: C A U T I O N In Bypass mode, the critical load is not protected f ...

  • Powerware 10001100 kVA - page 137

    UPS OPERATING INSTRUCTIONS EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 7−13 10. Press the CONTROLS pushbutton on the System Status menu bar. The UPM 1 Control Command screen is displayed. 11. On the UPM 1 Control Command screen, select UPM ON . 12. Press the SELECT pushbutton ...

  • Powerware 10001100 kVA - page 138

    UPS OPERATING INSTRUCTIONS EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 7−14 7.3.4 Transfer from Normal to Bypass Mode To transfer the critical load to Bypass mode: C A U T I O N In Bypass mode, the critical load is not protected from commercial power interruptions and abnorma ...

  • Powerware 10001100 kVA - page 139

    UPS OPERATING INSTRUCTIONS EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 7−15 7.3.6 Transfer from Normal to Bypass Mode and Shut Down UPS To transfer the critical load to Bypass mode and shut down the UPS: 1. Transfer the critical load to bypass by performing the procedure in p ...

  • Powerware 10001100 kVA - page 140

    UPS OPERATING INSTRUCTIONS EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 7−16 7.3.8 UPS and Critical Load Shutdown To perform maintenance or service on the critical load, shut down power to the load: 1. Turn off all equipment that is being powered by the UPS. 2. Perform the LOA ...

  • Powerware 10001100 kVA - page 141

    UPS OPERATING INSTRUCTIONS EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 7−17 7.3.10 Using the UPS LOAD OFF Pushbutton or Command A UPS Load Off is initiated by the LOAD OFF pushbutton from the main menu bar, the Load Off command on the UPS Control Command screen, or Load Off c ...

  • Powerware 10001100 kVA - page 142

    UPS OPERATING INSTRUCTIONS EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 7−18 C A U T I O N All power to the critical load is lost when the LOAD OFF is selected in the following step. You should use this feature only when you want to de-energize the critical load. 6. To shut do ...

  • Powerware 10001100 kVA - page 143

    UPS OPERATING INSTRUCTIONS EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 7−19 C A U T I O N Do not attempt to restart the system after the REPO until the cause of the shutdown has been identified and cleared. 2. To deactivate the REPO switch in preparation for restarting the UP ...

  • Powerware 10001100 kVA - page 144

    UPS OPERATING INSTRUCTIONS EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 7−20 7.4 Multiple UPS Distributed Bypass Operation 7.4.1 Starting the Distributed Bypass System in Normal Mode To start the distributed bypass system: 1. If the UPSs contain input breakers (CB1), verify th ...

  • Powerware 10001100 kVA - page 145

    UPS OPERATING INSTRUCTIONS EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 7−21 7.4.2 Starting the Distributed Bypass System in Bypass Mode If the inverter output of the distributed bypass system is not available and the critical load needs to be energized: C A U T I O N In Bypas ...

  • Powerware 10001100 kVA - page 146

    UPS OPERATING INSTRUCTIONS EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 7−22 8. On the System Status screen, select the UPM command. 9. On the UPS Control Command screen, select the UPM 1 command. 10. Press the CONTROLS pushbutton on the System Status menu bar. The UPM 1 Contr ...

  • Powerware 10001100 kVA - page 147

    UPS OPERATING INSTRUCTIONS EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 7−23 20. Repeat Steps 8 through 19 for each UPS in the distributed bypass system. NOTE To transfer to Normal mode after starting individual UPMs, follow the procedure in paragraph 7.4.5 . 7.4.4 Transfer fr ...

  • Powerware 10001100 kVA - page 148

    UPS OPERATING INSTRUCTIONS EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 7−24 7.4.6 Transfer from Normal to Bypass Mode and Shut Down all UPSs To transfer the critical load to Bypass mode and shut down all UPSs: 1. Transfer the critical load to bypass by performing the procedur ...

  • Powerware 10001100 kVA - page 149

    UPS OPERATING INSTRUCTIONS EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 7−25 5. On the UPM Control Command screen, select UPM OFF . 6. Press the SELECT pushbutton on the UPM Command menu bar. The UPM status indicates SHUTDOWN . The input, output, and battery contactors open, a ...

  • Powerware 10001100 kVA - page 150

    UPS OPERATING INSTRUCTIONS EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 7−26 7.4.10 Using the UPS LOAD OFF Pushbutton or Command A UPS Load Off is initiated by the LOAD OFF pushbutton from the main menu bar, the Load Off command on the UPS Control Command screen, or Load Off c ...

  • Powerware 10001100 kVA - page 151

    UPS OPERATING INSTRUCTIONS EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 7−27 C A U T I O N All power to the critical load is lost when the LOAD OFF is selected in the following step. You should use this feature only when you want to de-energize the critical load. 6. To shut do ...

  • Powerware 10001100 kVA - page 152

    UPS OPERATING INSTRUCTIONS EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 7−28 C A U T I O N Do not attempt to restart the system after the REPO until the cause of the shutdown has been identified and cleared. 2. To deactivate the REPO switch in preparation for restarting the UP ...

  • Powerware 10001100 kVA - page 153

    EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 8−1 Chapter 8 Communication This chapter describes the communication features of the Powerware 9395 UPS and provides information about connecting hardware and using Terminal mode. For terminal wiring information, see paragraph 3.2.3 ...

  • Powerware 10001100 kVA - page 154

    COMMUNICATION EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 8−2 LAN and telephone drops for use with X−Slot connectivity cards must be provided by facility planners or the customer. For installation and setup of an X−Slot card, contact an Eaton service representative (see p ...

  • Powerware 10001100 kVA - page 155

    COMMUNICATION EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 8−3 The eNotify Service relies on a ConnectUPS−X Web/SNMP Card (or Power Xpert card) installed with the UPS sending one−way status and event e−mails to Powerware Remote Monitoring servers that analyze and store t ...

  • Powerware 10001100 kVA - page 156

    COMMUNICATION EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 8−4 Remote Notification differs from the basic Terminal mode with the addition the following functions: S Call Answer The Call Answer function allows the user to call into the UPS from a remote location and enter Termi ...

  • Powerware 10001100 kVA - page 157

    COMMUNICATION EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 8−5 8.5.2 Event History Log This key sequence prints the entire Event History Log of the UPS at the time the data is requested. The printout begins with the oldest alarm entry in the queue and ends with the most recent ...

  • Powerware 10001100 kVA - page 158

    COMMUNICATION EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 8−6 MODEL: POWERWARE 9395 CTO: TF12710000000 SERIAL: MCU DSP: 70.81.14 MCU BOOTLOADER: 80.40 MCU PLD: 1.00 PMF 1 DSP: 80.81.14 PMF 1 BOOTLOADER: 80.40 PMF 1 PLD: 1.00 XSLOT CAN BRIDGE: 0.00 CSB DSP: 70.81.14 CSB BOOTLO ...

  • Powerware 10001100 kVA - page 159

    COMMUNICATION EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 8−7 8.6 Building Alarm Monitoring This standard feature lets you connect the UPS to your building alarms, such as smoke detectors or overtemperature alarms. The customer interface terminals for external connections are ...

  • Powerware 10001100 kVA - page 160

    COMMUNICATION EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 8−8 The RMP II contains a local horn and the backlit status indicators listed in Table 8-1. Table 8-1. RMP II Status Indicators SYSTEM NORMAL The UPS is energized (either with utility power or battery backup) and is su ...

  • Powerware 10001100 kVA - page 161

    COMMUNICATION EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 8−9 8.9 Relay Interface Module II An optional Relay Interface Module II (RIM II) uses relay contact closures to indicate the operating status and alarm condition of the UPS system. The module uses a serial interface li ...

  • Powerware 10001100 kVA - page 162

    COMMUNICATION EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 8−10 8.10 Supervisory Contact Module II An optional Supervisory Contact Module II (SCM II) establishes an interface between the UPS system and the customer’s monitor. This interface allows the customer to monitor ope ...

  • Powerware 10001100 kVA - page 163

    EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 9−1 Chapter 9 UPS Maintenance The components inside the UPS cabinet are secured to a sturdy metal frame. All repairable parts and assemblies are located for easy removal, with very little disassembly. This design allows authorized s ...

  • Powerware 10001100 kVA - page 164

    UPS MAINTENANCE EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 9−2 S Proper disposal of batteries is required. Refer to your local codes for disposal requirements. S Do not dispose of batteries in a fire. Batteries may explode when exposed to flame. S Do not open or mutilate bat ...

  • Powerware 10001100 kVA - page 165

    UPS MAINTENANCE EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 9−3 ISBM Air Filters Figure 9-1. ISBM Section Air Filter Locations C A U T I O N Verify washed filters are thoroughly dry before reinstalling. d. Push the washed or new foam filters over the screw heads on the cabine ...

  • Powerware 10001100 kVA - page 166

    UPS MAINTENANCE EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 9−4 UPM Air Filters Figure 9-2. UPM Section Air Filter Locations 3. If the UPS is a four UPM model, check the Field Installed UPM (FI−UPM) air filter (located behind the front panel) and wash or replace as necessar ...

  • Powerware 10001100 kVA - page 167

    UPS MAINTENANCE EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 9−5 FI−UPM Air Filter Figure 9-3. FI−UPM Air Filter Location 9.2.3 PERIODIC Maintenance Periodic inspections of the UPS should be made to determine if components, wiring, and connections exhibit evidence of overh ...

  • Powerware 10001100 kVA - page 168

    UPS MAINTENANCE EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 9−6 9.4 Recycling the Used Battery or UPS Contact your local recycling or hazardous waste center for information on proper disposal of the used battery or UPS. W A R N I N G S Do not dispose of the battery or batteri ...

  • Powerware 10001100 kVA - page 169

    EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 10−1 Chapter 10 Product Specifications 10.1 Model Numbers The UPS is housed in a free-standing cabinet, divided into two sections with safety shields behind the door and front panels. The UPS is available in 50 or 60 Hz with various ...

  • Powerware 10001100 kVA - page 170

    PRODUCT SPECIFICATIONS EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com 10−2 10.2.2 UPS Output UPS Output Capacity 100% rated current Output Voltage Regulation " 1% (10% to 100% load) Output Voltage Adjustment (Nominal +/–3%) 480 Vac nominal, adjustable from 466 Vac to 494 ...

  • Powerware 10001100 kVA - page 171

    EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com W−1 Warranty LIMITED FACTORY WARRANTY FOR THREE-PHASE POWERWARE ® UPS PRODUCTS WARRANTOR: The warrantor for the limited warranties set forth herein is Eaton Corporation, a Delaware Corporation (Eaton"). LIMITED WARRANTY: Th ...

  • Powerware 10001100 kVA - page 172

    WARRANTY EATON Powerware ® 9395 UPS (1000–1100 kVA) Installation and Operation Manual S 164201764 Rev 1 www.powerware.com W−2 This page intentionally left blank. ...

  • Powerware 10001100 kVA - page 173

    ...

  • Powerware 10001100 kVA - page 174

    *1642017641* 164201764 1 ...

Manufacturer Powerware Category Power Supply

Documents that we receive from a manufacturer of a Powerware 10001100 kVA can be divided into several groups. They are, among others:
- Powerware technical drawings
- 10001100 kVA manuals
- Powerware product data sheets
- information booklets
- or energy labels Powerware 10001100 kVA
All of them are important, but the most important information from the point of view of use of the device are in the user manual Powerware 10001100 kVA.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals Powerware 10001100 kVA, service manual, brief instructions and user manuals Powerware 10001100 kVA. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product Powerware 10001100 kVA.

Similar manuals

A complete manual for the device Powerware 10001100 kVA, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use Powerware 10001100 kVA by users. Manuals are usually written by a technical writer, but in a language understandable to all users of Powerware 10001100 kVA.

A complete Powerware manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual Powerware 10001100 kVA - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the Powerware 10001100 kVA, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the Powerware 10001100 kVA, that we can find in the current document
3. Tips how to use the basic functions of the device Powerware 10001100 kVA - which should help us in our first steps of using Powerware 10001100 kVA
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with Powerware 10001100 kVA
5. FAQ - Frequently Asked Questions
6. Contact detailsInformation about where to look for contact to the manufacturer/service of Powerware 10001100 kVA in a specific country, if it was not possible to solve the problem on our own.

Do you have a question concerning Powerware 10001100 kVA?

Use the form below

If you did not solve your problem by using a manual Powerware 10001100 kVA, ask a question using the form below. If a user had a similar problem with Powerware 10001100 kVA it is likely that he will want to share the way to solve it.

Copy the text from the picture

Comments (0)