Manual Kohler Generator Sets 20--2800 kW

56 pages 1.25 mb
Download

Go to site of 56

Summary
  • Kohler Generator Sets 20--2800 kW - page 1

    Industrial/Commercial/Residential Generator Sets Models: 20 - - 2800 kW TP-5700 7/93d Installation ...

  • Kohler Generator Sets 20--2800 kW - page 2

    Engine exhaust fr om t his produc t cont ains chemic als known t o the S tat e of California t o cause canc er , birt h defec ts , or ot her reproduc t ive harm. W ARNING California Propos ition 65 Product Identifica tion I nformat ion Produc t ident if icat ion number s det ermine serv ice part s. Record t he produc t ident if icat ion numbers in ...

  • Kohler Generator Sets 20--2800 kW - page 3

    T able of Contents TP-5700 7/93 T able of Contents Product Identification Information Inside front cover ............................................ Safety Precautions and Instructions I ........................................................ Introduction i ............................................................................... Service As ...

  • Kohler Generator Sets 20--2800 kW - page 4

    T able of Contents, continued TP-5700 7/93 T able of Contents Section 7 Electrical Requirements 35 .......................................................... 7.1 Batteries 35 ............................................................. 7.2 Electrical Connections 36 ................................................. 7.3 Load Lead Connections 36 .... ...

  • Kohler Generator Sets 20--2800 kW - page 5

    TP-5700 7/93 I Safety Precautions and Instructions Safety Precautions and Instructions IMPORT ANT SAFETY INSTRUCTIONS . Electromechanical equipment, including generator sets, transfer switches, switchgear , and accessories, can cause bodily harm and pose life-threatening danger when improperly installed, operated, or maintained. T o prevent acciden ...

  • Kohler Generator Sets 20--2800 kW - page 6

    TP-5700 7/93 II Safety Precautions and Instructions Battery short circuits. Explosion can cause severe injury or death. Short circuits can cause bodily injury and/or equipment damage. Disconnect the battery before generator set installation or maintenance. Remove wristwatch, rings, and other jewelry before servicing the equipment. Use tools with in ...

  • Kohler Generator Sets 20--2800 kW - page 7

    TP-5700 7/93 III Safety Precautions and Instructions The fuel system. Explosive fuel vapors can cause severe injury or death. V aporized fuels are highly explosive. Use extreme care when handling and storing fuels. Store fuels i naw e l l - v e n t i l a t e da r e aa w a yf r o m spark-producing equipment and out of the reach of children. Never ad ...

  • Kohler Generator Sets 20--2800 kW - page 8

    TP-5700 7/93 IV Safety Precautions and Instructions Hazardous voltage. Backfeed to the utility system can cause property damage, severe injury , or death. If the generator set is used for standby power , install an automatic transfer switch to prevent inadvertent interconnection of standby and normal sources of supply . W ARNING Grounding electrica ...

  • Kohler Generator Sets 20--2800 kW - page 9

    TP-5700 7/93 V Safety Precautions and Instructions Servicing the transfer switch controls and accessories within the enclosure. Hazardous voltage can cause severe injury or death. Disconnect the transfer switch controls at the inline connector to deenergize the circuit boards and logic circuitry but allow the transfer switch to continue to supply p ...

  • Kohler Generator Sets 20--2800 kW - page 10

    TP-5700 7/93 VI Safety Precautions and Instructions Notice NOTICE This generator set has been rewired from its nameplate voltage to 246242 NOTICE V oltage reconnection. Affix a notice to the generator set after reconnecting the set to a voltage different from the voltage on the nameplate. Order voltage reconnection decal 246242 from an authorized s ...

  • Kohler Generator Sets 20--2800 kW - page 11

    TP-5700 7/93 i Introduction Introduction This manual provides installation instructions for 20 - -2800 kW generator sets. Operation manuals and wiring diagram manuals are available separately . x:in:001:001 Information in this publication represents data available at the time of print. Kohler Co. reserves the right to change this publication and th ...

  • Kohler Generator Sets 20--2800 kW - page 12

    ...

  • Kohler Generator Sets 20--2800 kW - page 13

    TP-5700 7/93 1 Section 1 General Section 1 General Industrial power systems give years of dependable service if installed using the guidelines provided in this manual and in applicable codes. Incorrect installation can cause continuing problems. Figure 1-1 illustrates a typical installation. Y our authorized generator set distributor/dealer may als ...

  • Kohler Generator Sets 20--2800 kW - page 14

    TP-5700 7/93 2 Section 1 General TP-5700-1 1. Exhaust thimble (for wall or ceiling) 2. Silencer 3. Supports 4. Flexible sections 5. Duct work for cooling air outlet 6. Mounting base 7. Controller 8. Electrical conduit 9 . W a t e rt r a pw i t hd r a i n 10. Fresh air intake 1 2 3 4 5 6 7 8 9 10 Figure 1-1 T ypical Stationary-Duty Generator Set Ins ...

  • Kohler Generator Sets 20--2800 kW - page 15

    TP-5700 7/93 3 Section 2 Load and Transport Section 2 Load a nd T ransport T o ensure personal safety while preventing damage to the product, we strongly recommend the following guidelines be observed when loading and transporting standby generator sets. Due to the different designs, dimensions and weights of the generators involved, specific instr ...

  • Kohler Generator Sets 20--2800 kW - page 16

    TP-5700 7/93 4 Section 2 Load and Transport D A four-point lifting method is necessary to lift the generator set. T o maintain generator balance during lifting, the lifting apparatus must utilize the four skid lifting holes mentioned in the previous paragraph. One method of lifting standby generators uses an apparatus of hooks and cables joined at ...

  • Kohler Generator Sets 20--2800 kW - page 17

    TP-5700 7/93 5 Section 2 Load and Transport D Do not attach lifting hooks to outside reinforcing plate on skid. Attach lifting hooks to skid exactly as shown in Figure 2-4. This method utilizes the strongest portion of the mounting skid and also prevents the lifting hooks from slipping. Generators without skid reinforcing plates can be raised with ...

  • Kohler Generator Sets 20--2800 kW - page 18

    TP-5700 7/93 6 Section 2 Load and Transport Notes ...

  • Kohler Generator Sets 20--2800 kW - page 19

    TP-5700 7/93 7 Section 3 Location Section 3 Location 3.1 Location Factors Location is the key to a proper installation. The following sections will deal with the factors to consider in a proper installation. Before final plans are made for locating a generator set, the following questions should be raised concerning the set and the proposed site. 1 ...

  • Kohler Generator Sets 20--2800 kW - page 20

    TP-5700 7/93 8 Section 3 Location 3.3 Mounting T ypical mounting surface details and dimensions are shown in Figure 3-1. The recommended mounting surface is a concrete mounting pad. This must be a level surface as shown in Figure 3-2, or raised pads as shown in Figure 3-3 and Figure 3-4. The advantage of the arrangement shown in Figure 3-3 is that ...

  • Kohler Generator Sets 20--2800 kW - page 21

    TP-5700 7/93 9 Section 3 Location The composition of the mounting pad should follow standard practice for the required loading. Common specifications call for 2500-3000 psi (176-21 1 kg/cm 2 ) concrete reinforced with eight-gauge wire mesh or number 6 reinforcing bars on 12-inch (30-cm) centers. The total weight of the mounting pad should be at lea ...

  • Kohler Generator Sets 20--2800 kW - page 22

    TP-5700 7/93 10 Section 3 Location Notes ...

  • Kohler Generator Sets 20--2800 kW - page 23

    TP-5700 7/93 11 Section 4 Air Requirements Section 4 Air Requirements 4.1 General An ample flow of clean, cool air is required to support combustion and dissipate heat. Approximately 70% of the heat value of fuel consumed by an engine will be rejected to the cooling system and exhaust. Battery compartment ventilation. T o prevent the accumulation o ...

  • Kohler Generator Sets 20--2800 kW - page 24

    TP-5700 7/93 12 Section 4 Air Requirements In many installations it may be desirable to install louvers in the inlet and outlet openings. Louvers may be either stationary or movable. In areas of great temperature variation, it is often best to install movable louvers that can be thermostatically adjusted to regulate air flow and room temperature. S ...

  • Kohler Generator Sets 20--2800 kW - page 25

    TP-5700 7/93 13 Section 4 Air Requirements 4.3 Forced Air With the forced-air system, cooling air is drawn in through the front of the engine, circulated around finned areas of the cylinder block and head, then ejected toward the rear or generator end of the set. This system is best suited to wide-open, well-ventilated areas. It is not recommended ...

  • Kohler Generator Sets 20--2800 kW - page 26

    TP-5700 7/93 14 Section 4 Air Requirements 4.4 Air - V ac  Cooling System The air flow direction with the Air-V ac  system is the opposite of the conventional forced air cooling system. Use the Air-V ac  system in confined areas since it includes a blower scroll which easily connects to the ductwork. For duct dimensions refer to the dimens ...

  • Kohler Generator Sets 20--2800 kW - page 27

    TP-5700 7/93 15 Section 4 Air Requirements 4.5 Air V ent The air vent system is used on some air-cooled gas and has been used on some diesel models. It includes special ductwork which directs the flow of heated air to the outlet at the top or side of t he engine. The air vent air flow is not reversed as it is with the Air-V ac  system. Choose to ...

  • Kohler Generator Sets 20--2800 kW - page 28

    TP-5700 7/93 16 Section 4 Air Requirements 4.6 Liquid -Cooled Models The three most common liquid cooling systems used for generator sets are unit-mounted radiator , city water , and remote radiator cooling. Since each involves somewhat different installation considerations, they will be discussed separately . 4.7 Unit -Mounted Radiator Cooling Thi ...

  • Kohler Generator Sets 20--2800 kW - page 29

    TP-5700 7/93 17 Section 4 Air Requirements The connection from the radiator duct flange to the ductwork should be heavy canvas, silicone or similar flexible material to prevent noise and vibration transmission. Sheet metal ductwork should be self-supporting. In general, the outlet duct should have an unrestricted area 150% greater than that enclose ...

  • Kohler Generator Sets 20--2800 kW - page 30

    TP-5700 7/93 18 Section 4 Air Requirements The engine water pump can be used to circulate water through the remote radiator providing that the vertical distance from the engine water pump does not exceed the engine manufacturer ’s recommendations. The allowable static head may range from 17-50 feet (5.2-15.2 m). Consult the Specification Sheet fo ...

  • Kohler Generator Sets 20--2800 kW - page 31

    TP-5700 7/93 19 Section 4 Air Requirements 7 1 2 3 4 6 5 1. V entilation fan (for heat rejected from exhaust and engine) 2. City water in 3. Flexible section 4. Manual shutoff valve 5. Heated water into drain 6. Solenoid valve 7. Heat Exchanger Figure 4-1 1 Installation Using City Water Cooling System with Heat Exchanger 1 2 3 4 5 6 1. Engine water ...

  • Kohler Generator Sets 20--2800 kW - page 32

    TP-5700 7/93 20 Section 4 Air Requirements 4.1 1 Block Heaters Block heaters are recommended on all standby applications where the generator is subject to temperatures below 60 ° F( 1 6 ° C) and are available as installed accessories on all generator sets. The block heater should be connected to a source of power , which is determined by the part ...

  • Kohler Generator Sets 20--2800 kW - page 33

    TP-5700 7/93 21 Section 5 Exhaust System Section 5 Exhaust System Proper installation of the exhaust system is essential to obtain satisfactory performance from a generator set. The most important factor is that the installed system must not exceed the engine manufacturer ’s maximum exhaust back pressure limit. Any exhaust back pressure will limi ...

  • Kohler Generator Sets 20--2800 kW - page 34

    TP-5700 7/93 22 Section 5 Exhaust System 5.1 Flexible Section A section of flexible exhaust line should be installed within 2 feet (51 mm) of the engine exhaust outlet. This limits the stress on the engine exhaust manifold or turbocharger resulting from engine motion on its vibration mounts and temperature-induced changes in pipe dimensions. Never ...

  • Kohler Generator Sets 20--2800 kW - page 35

    TP-5700 7/93 23 Section 5 Exhaust System 5.4 Double -Sleeve Thimbles If the exhaust pipe should need to pass through a wall or roof, an exhaust thimble must be used to prevent exhaust pipe heat from being transmitted to the combustible material. Construction details for a typical double-sleeve thimble to be used where exhaust piping passes through ...

  • Kohler Generator Sets 20--2800 kW - page 36

    TP-5700 7/93 24 Section 5 Exhaust System Notes ...

  • Kohler Generator Sets 20--2800 kW - page 37

    TP-5700 7/93 25 Section 6 Fuel Systems Section 6 Fuel Systems When planning an installation, check state and local regulations regarding fuel storage and handling. Piping and fuel system components must conform to these regulations. 6.1 Diesel Fuel Systems Since diesel fuel is less volatile than gas or gasoline, it may be considered safer fuel from ...

  • Kohler Generator Sets 20--2800 kW - page 38

    TP-5700 7/93 26 Section 6 Fuel Systems 1 2 3 4 TP-5700-6 1. Generator set skid 2. Side view 3. Subbase fuel tank 4. End view Figure 6-2 Subbase Fuel T ank 6.2 Main Fuel T ank All main tanks should be vented so that air and other gases can escape to the atmosphere. The vent must prevent dust, dirt, and moisture from entering the tank. Return lines s ...

  • Kohler Generator Sets 20--2800 kW - page 39

    TP-5700 7/93 27 Section 6 Fuel Systems Flexible connections must be used wherever there may be relative motion between piping and supplied equipment. Always use flexible lines at the engine connections. These should be a minimum of six inches (15.3 cm) long. Diesel engines require at least two fuel lines: one supply and at least one return from the ...

  • Kohler Generator Sets 20--2800 kW - page 40

    TP-5700 7/93 28 Section 6 Fuel Systems 6.5 Auxiliary Fuel Pumps Engine-driven fuel transfer pumps usually develop a maximum of 7 psi (48 kPa) pressure and have a lift capacity of 4-6 feet (1.2-1.8 m). Even if the engine pump can draw fuel a greater distance, a more reliable system results if a transfer tank and/or auxiliary pump are used when the v ...

  • Kohler Generator Sets 20--2800 kW - page 41

    TP-5700 7/93 29 Section 6 Fuel Systems 6.6 Gasoline Fuel Systems Due to code restrictions which do not allow storage of more than one gallon (3.8 L) of gasoline inside a building, gasoline fuel systems are usually limited to housed generator sets installed outdoors or portable trailer-mounted units. Gasoline will deteriorate if stored for more than ...

  • Kohler Generator Sets 20--2800 kW - page 42

    TP-5700 7/93 30 Section 6 Fuel Systems 6.7 Natural or LP Gas Fuel Systems Natural and LP (liquified petroleum) gas fuel systems should be designed and installed in accordance with the requirements of NFP A 54, National Fuel Gas Code, and all applicable local codes. V arious types of gas fuel systems are available as follows: D LP Gas V apor (Figure ...

  • Kohler Generator Sets 20--2800 kW - page 43

    TP-5700 7/93 31 Section 6 Fuel Systems 1 2 3 5 TP-5700-6 4 91 0 87 6 1. Carburetor 2. Load adjustment valve 3. Converter (vaporizer) 4. Solenoid valve 5. LP gas filter (supplied by gas supplier or installer) 6. LP gas supply 7. Natural gas supply 8. Primary regulator (supplied by gas supplier or installer) 9. Secondary regulator 10. Pressure gauge ...

  • Kohler Generator Sets 20--2800 kW - page 44

    TP-5700 7/93 32 Section 6 Fuel Systems 6.8 Flexible Connector An approved flexible connector should always be used between stationary gas piping and the engine-mounted fuel system components. It should be at least six inches (15.3 cm) long or as recommended by the generator supplier based upon engine specifications. 6.9 Gas Piping Gas piping should ...

  • Kohler Generator Sets 20--2800 kW - page 45

    TP-5700 7/93 33 Section 6 Fuel Systems 6.1 1 LP Gas Fuel Characteristics LP gas is supplied as a liquid in pressure tanks. It is easily adaptable to stationary applications where complete independence of an outside fuel supply is required. Since LP gas does not deteriorate in long periods of storage as gasoline is known to do, a large supply of fue ...

  • Kohler Generator Sets 20--2800 kW - page 46

    TP-5700 7/93 34 Section 6 Fuel Systems 6.15 Natural Gas Natural gas is in a vapor state as supplied from the utility . This fuel system, therefore, consists of the same basic components and is used in the same general sequence as LP gas systems. When the heating content of the fuel falls below 1000 BTU, as it does with manufactured sewage and some ...

  • Kohler Generator Sets 20--2800 kW - page 47

    TP-5700 7/93 35 Section 7 Electrical Requirements Section 7 Electrical Requirements Before installing the generator set, provide for electrical connections through conduit to the transfer switch and other accessories for the generator set. Carefully install the selected generator set accessories. Route wiring to the generator set through flexible c ...

  • Kohler Generator Sets 20--2800 kW - page 48

    TP-5700 7/93 36 Section 7 Electrical Requirements 7.2 Electrical Connections Several electrical connections must be made between the generator set and other components of the system for proper operation. Because of the large number of accessories and possible combinations, this manual does not address specific applications. Refer to the submittal c ...

  • Kohler Generator Sets 20--2800 kW - page 49

    TP-5700 7/93 37 Section 7 Electrical Requirements 7.4 T erminal Connector T orque Use the torque values shown in Figure 7-4 or Figure 7-5 for terminal connectors. Refer to UL-486A, UL-486B, and UL-486E for information on terminal connectors for aluminum and/or copper conductors. See Section 7.2, Electrical Connections, for information on the temper ...

  • Kohler Generator Sets 20--2800 kW - page 50

    TP-5700 7/93 38 Section 7 Electrical Requirements 7.5 Automatic T ransfer Switches A typical standby system has at least one automatic transfer switch connected to the generator set output to automatically transfer the electrical load to the generator set if the normal source fails. When normal power returns, the switch transfers the load back to t ...

  • Kohler Generator Sets 20--2800 kW - page 51

    TP-5700 7/93 39 Section 7 Electrical Requirements 7.9 Remote Emergency Stop Switch The emergency stop switch allows immediate shutdown of the generator from a remote location. If the emergency stop switch is activated, the emergency stop lamp on the generator controller lights and the unit shuts down immediately . The generator cannot be restarted ...

  • Kohler Generator Sets 20--2800 kW - page 52

    TP-5700 7/93 40 Section 7 Electrical Requirements TP-5700 7/93 GENERA TOR JUNCTION BOX SAFEGUARD CIRCUIT BREAKER TERMINAL STRIP (IN JUNCTION BOX) RUN RELA Y KIT BA TTERY HEA TER KIT GENERA TOR HEA TER KIT BLOCK HEA TER KIT AC CONNECTION BOX (Installer Supplied) BA TTERY CHARGER KIT LOW FUEL SWITCH KIT 10-RELA Y DRY CONT ACT KIT TRANSFER SWITCH (OPT ...

  • Kohler Generator Sets 20--2800 kW - page 53

    TP-5700 7/93 Appendix A-1 Appendix A Abbreviations The following list contains abbreviations that may appear in this publication. A, amp ampere ABDC after bottom dead center AC alternating current A/D analog to digital ADC analog to digital converter adj. adjust, adjustment ADV advertising dimensional drawing AHWT anticipatory high water temperatur ...

  • Kohler Generator Sets 20--2800 kW - page 54

    TP-5700 7/93 A-2 Appendix kg kilogram kg/cm 2 kilograms per square centimeter kgm kilogram-meter kg/m 3 kilograms per cubic meter kHz kilohertz kJ kilojoule km kilometer kOhm, k Ω kilo-ohm kPa kilopascal kph kilometers per hour kV kilovolt kV A kilovolt ampere kV AR kilovolt ampere reactive kW kilowatt kWh kilowatt-hour kWm kilowatt mechanical L ...

  • Kohler Generator Sets 20--2800 kW - page 55

    ...

  • Kohler Generator Sets 20--2800 kW - page 56

    E 1993, 2001, 2003 by Kohler Co. All rights reserved. TP-5700 7/93d KOHLER CO. Kohler , Wisconsin 53044 Phone 920-565-3381, Web site www .kohlergenerators.com Fax 920-459-1646 (U.S.A. Sales), Fax 920-459-1614 (International) For the nearest sales and service outlet in U.S.A. and Canada Phone 1-800-544-2444 Kohler Power Systems Asia Pacific Headquar ...

Manufacturer Kohler Category Portable Generator

Documents that we receive from a manufacturer of a Kohler Generator Sets 20--2800 kW can be divided into several groups. They are, among others:
- Kohler technical drawings
- Generator Sets 20--2800 kW manuals
- Kohler product data sheets
- information booklets
- or energy labels Kohler Generator Sets 20--2800 kW
All of them are important, but the most important information from the point of view of use of the device are in the user manual Kohler Generator Sets 20--2800 kW.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals Kohler Generator Sets 20--2800 kW, service manual, brief instructions and user manuals Kohler Generator Sets 20--2800 kW. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product Kohler Generator Sets 20--2800 kW.

Similar manuals

A complete manual for the device Kohler Generator Sets 20--2800 kW, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use Kohler Generator Sets 20--2800 kW by users. Manuals are usually written by a technical writer, but in a language understandable to all users of Kohler Generator Sets 20--2800 kW.

A complete Kohler manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual Kohler Generator Sets 20--2800 kW - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the Kohler Generator Sets 20--2800 kW, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the Kohler Generator Sets 20--2800 kW, that we can find in the current document
3. Tips how to use the basic functions of the device Kohler Generator Sets 20--2800 kW - which should help us in our first steps of using Kohler Generator Sets 20--2800 kW
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with Kohler Generator Sets 20--2800 kW
5. FAQ - Frequently Asked Questions
6. Contact detailsInformation about where to look for contact to the manufacturer/service of Kohler Generator Sets 20--2800 kW in a specific country, if it was not possible to solve the problem on our own.

Do you have a question concerning Kohler Generator Sets 20--2800 kW?

Use the form below

If you did not solve your problem by using a manual Kohler Generator Sets 20--2800 kW, ask a question using the form below. If a user had a similar problem with Kohler Generator Sets 20--2800 kW it is likely that he will want to share the way to solve it.

Copy the text from the picture

Comments (0)