    CC1A7865.1en 31.10.2002 Sie mens Bu ildi ng Tech nolo gies HVAC Product s 7 865.1 Interface RS-485 RWF40... The RS-485 interface is used f or integrati ng RW F40… controllers into data networks via MOD bus protocol. Application examples: - Process v isualiz ation - Plant control - Reporting Master-slave principle Communication between a PC (maste ...

  • Siemens RS-485 - page 2

    2/14 Siemens Building Technologie s CC1A7865.1e n HVAC Produ cts 31.10.2002 Transmission mode (RT U) The transmission mode used is the RTU (re mote terminal unit) mode. Data are trans- mitted in binary format (hexadecimal) with 8 bits. The LSB (least significant bit) is transmitted first. ASCII mode is not supported. The data format describes the s ...

  • Siemens RS-485 - page 3

    3/14 Siemens Building Technologie s CC1A7865.1e n HVAC Produ cts 31.10.2002 Communication se quence Both the start and end of a data block are c haracterized by transmiss ion pauses. The maximum period of tim e that m ay elapse between 2 successi ve characters is 3 times the period of time required for the transmis sion of one character. The charac ...

  • Siemens RS-485 - page 4

    4/14 Siemens Building Technologie s CC1A7865.1e n HVAC Produ cts 31.10.2002 Data query sequence The time sequence of a data query looks as follows: Master Sl ave Data qu er y Rep ly Data qu ery t 0 t 1 t 0 t 2 7865z12e/1102 t0 Identification of end = 3 characters (time is dependent on the Baud rate) t1 This time is dependent on internal handling. T ...

  • Siemens RS-485 - page 5

    5/14 Siemens Building Technologie s CC1A7865.1e n HVAC Produ cts 31.10.2002 Structure of the data blocks All data blocks use the same structure: Slave address Function c ode Data field Checksum CRC16 1 byte 1 byte x byte 2 bytes Every data block contains 4 fields: Slave address Device address of a certain slave Function c ode Function selection (re ...

  • Siemens RS-485 - page 6

    6/14 Siemens Building Technologie s CC1A7865.1e n HVAC Produ cts 31.10.2002 Checksum (CRC16) The che cksum ( CRC1 6) is used to det ect tra nsmissio n err ors. If the evaluation reveals an error , the relevant device will not respond. CRC = 0xFFF CRC = CRC XOR ByteOfMessage For (1 to 8) CRC = SHR (CRC) if (flag to the right = 1) then CRC = CRC XOR ...

  • Siemens RS-485 - page 7

    7/14 Siemens Building Technologie s CC1A7865.1e n HVAC Produ cts 31.10.2002 Reading n words This function is used to read n words from a certain address. Slave address Function 0x03 or 0x04 Address of the first w ord Number of wor d s (max. 12) Checksum CRC16 1 byte 1 byte 2 bytes 2 bytes 2 bytes Slave address Function 0x03 or 0x04 Number of bytes ...

  • Siemens RS-485 - page 8

    8/14 Siemens Building Technologie s CC1A7865.1e n HVAC Produ cts 31.10.2002 Writing n w ords Slave address Function 0x10 Address of first word Number of words Number of by t es (max. 2) Word value(s) Check- sum CRC16 1 byte 1 byte 2 by tes 2 bytes 1 byte x byte(s) 2 bytes Slave address Function 0x10 Address of first w ord Number of wor ds Checksum ...

  • Siemens RS-485 - page 9

    9/14 Siemens Building Technologie s CC1A7865.1e n HVAC Produ cts 31.10.2002 Address tables Address Data typ e Access Parameter Value range Default valu e 0x0000 f loat R / O Actual value E1 0x0002 f loat R / O Actual value E2 0x0004 f loat R / O Actual value E3 0x0006 f loat R / W Current setpoint 0x0008 f loat R / W SP1 First setpoint SPL...SPH 0 ...

  • Siemens RS-485 - page 10

    10/14 Siemens Building Technologie s CC1A7865.1e n HVAC Produ cts 31.10.2002 Address Data typ e Access Parameter Value range Default valu e 0x0300 word [13] R / O Device data 0x0300 char SW Version [11+1] Software version 0x0306 char VDNNr [13+1] VdN number Address Data typ e Access Parameter Value range Default valu e 0x0400 f loat R / O TEMP Actu ...

  • Siemens RS-485 - page 11

    11/14 Siemens Building Technologie s CC1A7865.1e n HVAC Produ cts 31.10.2002 Address Data type Access Parameter 0x0200 word R / O Outputs and states B15 B14 B13 B12 B11 B10 B9 B8 B7 B6 B5 B4 B3 B2 B1 B0 B8 Hysteresis limitation B0 Output 1 off (for remote operation) B1 Output 3 off B9 Management system off B2 Output 2 off (for remote operation) B3 ...

  • Siemens RS-485 - page 12

    12/14 Siemens Building Technologie s CC1A7865.1e n HVAC Produ cts 31.10.2002 Description of operati ng modes Parameter «RemoteStatus» is used to switch between the operating modes «LOCAL», «REMOTE SETPOINT» and «FULLY REMOTE». The change is always accomplished via the MOD bus. In the event the master fails or communication is lost, the R W ...

  • Siemens RS-485 - page 13

    13/14 Siemens Building Technologie s CC1A7865.1e n HVAC Produ cts 31.10.2002 The previous functions of the RW F40... are maintained (apart from mem ory usage). The R W F40... can be parameterized and uploaded via the MOD bus, whereby the out- puts cannot be changed. After «Power-up», the R W F40... will normally assume oper- ating mode «LOCAL». ...

  • Siemens RS-485 - page 14

    14/14 Siemens Building Technologie s CC1A7865.1e n HVAC Produ cts 31.10.2002 Modulating controller: The management system predefines the va lue (degree of modulat ion) for the analog output via «RY». Setting the «RK2» and «RK3» by the management system has no impact. Both relays «K2» and «K3», are deenergized. Floating step controller: Th ...

Manufacturer Siemens Category Cell Phone

Documents that we receive from a manufacturer of a Siemens RS-485 can be divided into several groups. They are, among others:
- Siemens technical drawings
- RS-485 manuals
- Siemens product data sheets
- information booklets
- or energy labels Siemens RS-485
All of them are important, but the most important information from the point of view of use of the device are in the user manual Siemens RS-485.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals Siemens RS-485, service manual, brief instructions and user manuals Siemens RS-485. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product Siemens RS-485.

Similar manuals

A complete manual for the device Siemens RS-485, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use Siemens RS-485 by users. Manuals are usually written by a technical writer, but in a language understandable to all users of Siemens RS-485.

A complete Siemens manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual Siemens RS-485 - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the Siemens RS-485, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the Siemens RS-485, that we can find in the current document
3. Tips how to use the basic functions of the device Siemens RS-485 - which should help us in our first steps of using Siemens RS-485
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with Siemens RS-485