    246819-BTG-H-0208 FOR DISTRIBUTION USE ONLY - NOT TO BE USED AT POINT OF RETAIL SALE SPLIT - SYSTEM HEA T PUMPS 13 SEER – R-22 MODELS: E*BD-F018 THRU 060 (1.5 THRU 5 NOMINAL T ONS, 1 PHASE) E*BD-(T ,W)036 THRU 060 (2.5 THRU 5 NOMINAL T ONS, 3 PHASE) Due to continuo us product imp rovement, speci fications are subject to chan ge without notice. Vi ...

  • York E*BD-F018 THRU 060 - page 2

    246819-BTG-H-0208 2 Unitary Products Group All dimensions are in inches. They are subject to cha nge without notice. Ce rtif ied dimensio ns will be provide d upon request. Physical and Electrical Dat a - 1 Phase MODEL EABD-F018S EABD-F024S EABD-F030S EABD-F036S EABD-F042S EABD-F048S EABD-F060S Unit Supply V oltage 208-230V , 1 φ, 60Hz Normal V ol ...

  • York E*BD-F018 THRU 060 - page 3

    246819-BTG-H-0208 Unitary Products Group 3 Additional R-22 Charge / Orifice Size for V arious Matched Syste ms - 1 Phase Outdoor Unit EABD-F018S EABD-F024S EABD-F030S EAB D-F036S EABD-F042S EABD-F048S EABD-F060S Required TXV 1 TVM2A1 1 TVM2A1 1 TVM2A1 1 TVM2A1 1 TVM2C1 1 TVM2C1 1 TVM2C1 Factory Charge, lbs-oz 7 - 1 6 - 9 8 - 9 8 - 7 8 - 7 12 - 8 16 ...

  • York E*BD-F018 THRU 060 - page 4

    246819-BTG-H-0208 4 Unitary Products Group * This loose coil match does not achieve 13 SEER. PROCEDURES: 1. Unit factory charge listed on the unit nameplate includes re frigerant for the condenser , the smallest evaporator and 15 feet of inter- connecting line tubing. 2. V erify the orifice size and the additional charge required for t he specific ...

  • York E*BD-F018 THRU 060 - page 5

    246819-BTG-H-0208 Unitary Products Group 5 All dimensions are in inche s. Th ey are su bject to change with- out notice. Certified dimensions will be pro vided upon request. Physical and Elect rical Dat a - 3 Ph ase MODEL EABD- T030S EABD- T036S EABD- T042S EABD- T048S EABD- T060S EABD- W030S EABD- W036S EABD- W042S EABD- W048S EABD- W060S Unit Sup ...

  • York E*BD-F018 THRU 060 - page 6

    246819-BTG-H-0208 6 Unitary Products Group PROCEDURES: 1. U nit factory charge listed on the unit nameplate includes refr igerant for the condenser , the smallest evaporator and 15 feet of inter-con- necting line tubing. 2. Verify the TXV and additional charge required for specific evaporator coil in the system using th e above table. 3. Additional ...

  • York E*BD-F018 THRU 060 - page 7

    246819-BTG-H-0208 Unitary Products Group 7 COOLING CAP ACITY - Wi th Air Handler Coils UNIT MODEL AIR HANDLER COIL MODEL 1 COOLING MODEL W RA TED CFM NET MBH SEER EER TOT AL SENS. 1 & 3 PH 13 SEER HP WITH MA EABD-F018S MA08B 17 FC/MC18B 600 18 .0 12.4 13 .00 1 1.00 EABD-F024S MA08B 17 FC/MC24B 800 23.2 16.8 13.00 1 1.00 MA08B 17 FC/MC30B 800 23 ...

  • York E*BD-F018 THRU 060 - page 8

    246819-BTG-H-0208 8 Unitary Products Group — = Not Applicable. Go to www.ari. org/aridirectory for the latest additiona l matches. 1 PH 13 SEER AC WITH A V / SV - V ARIABLE SPEED EABD-F018S A V24 17 – 600 18.0 12.6 14.00 12.00 EABD-F024S A V24 17 – 800 23.8 16.7 14.00 12.00 EABD-F030S A V36 17 – 1000 29.2 20.1 14 .00 12.00 EABD-F036S A V36 ...

  • York E*BD-F018 THRU 060 - page 9

    246819-BTG-H-0208 Unitary Products Group 9 COOLING CAP ACITY - Upflow , Downflow , and Horizont al Furnaces and Coils UNIT MODEL FURNACE** COIL MODEL COOLING CFM RANGE (MIN.-MAX.) W RA TED CFM NET MBH SEER 1 EER TOT AL SENS. EABD-F018S 450 750 14,17 FC/MC/PC/UC18 600 18.0 12 .4 13.00 1 1.00 14 HC18 600 17.8 12 .1 13.00 1 1.00 EABD-F024S 600 1000 14 ...

  • York E*BD-F018 THRU 060 - page 10

    246819-BTG-H-0208 10 Unitary Products Group COOLING CAP ACITY - With V ariable S peed Furnac es UNIT MODEL V ARIABLE SPEED FURNACE MODEL COIL MODEL 1 W COOLING RA TED CFM NET MBH SEER EER T OTAL SENS. 1 PH 13 SEER HP WITH V ARIABLE SPEED FURNACES 2 EABD-F018S (F ,L)L8V A12 FC/MC/PC18A 14 600 18.0 12.5 14.00 12.00 FL9V A12 FC/MC/PC18A 14 600 18.0 12 ...

  • York E*BD-F018 THRU 060 - page 11

    246819-BTG-H-0208 Unitary Products Group 11 EABD-F048S FL9(C,V)D20 FC/MC/PC60D 24 1600 46.0 35 .5 13.25 1 1.00 (F ,L)L8VC16 FC/PC60C 21 1500 45.5 35.1 13 .25 1 1.00 (F ,L)L8VC20 FC/PC60C 21 1600 46.0 35.4 13 .25 1 1.00 FL9(C,V)C16 FC/PC60C 21 1600 46.0 35 .5 13.25 1 1.00 FL9(C,V)C20 FC/PC60C 21 1600 46.0 34 .5 13.25 1 1.00 FL9(C,V)D20 HC60 24 1600 ...

  • York E*BD-F018 THRU 060 - page 12

    246819-BTG-H-0208 12 Unitary Products Group HEA TING PERFORMANCE - With Air Handler UNIT MODEL* AIR HANDLER COIL 1 MODEL ARI HEA T ING 2 47 ° F1 7 ° FH S P F MBH COP KW MBH COP KW STD 1 & 3 PH 13 SEER HP WITH MA EABD-F018S MA08B FC/MC18B 18.0 3.62 1.46 10.5 2.28 1 .35 8.00 EABD-F024S M A 0 8 B F C / M C 2 4 B 2 3 . 03 . 4 41 . 9 61 3 . 12 . 3 ...

  • York E*BD-F018 THRU 060 - page 13

    246819-BTG-H-0208 Unitary Products Group 13 CP equals MBH output divided by (t otal KW input x 3.412). HSPF (Heating Seasonal Performance Factor) is the total heating ou tput during a normal annual usage period for heating divided by the total electric power input during the same period. — = Not Applicable. 1 PH 13 SEER HP WITH A V - V ARIABLE SP ...

  • York E*BD-F018 THRU 060 - page 14

    246819-BTG-H-0208 14 Unitary Products Group CP equals MBH output divided by (total KW input x 3.412). HSPF (Heating Seasonal Performance Factor) is the total heat ing output during a normal annual usage period for heating divided by the total electric power input during the same period. — = Not Applicable. HEA TING PERFOR MANCE - Upflow Furnace C ...

  • York E*BD-F018 THRU 060 - page 15

    246819-BTG-H-0208 Unitary Products Group 15 HEA TING CAP ACITY - W ith V ariable Speed Furnaces UNIT MODEL V ARIABLE SPEED FURNACE COIL 1 MODEL ARI HEA T ING 2 47 ° F1 7 ° FH S P F MBH COP KW MBH COP KW STD EABD-F018S (F ,L)L8V A12 FC/MC/PC18A 17.5 3.88 1.32 10 .0 2.42 1.21 8.60 FL9V A12 FC/MC/PC18A 17.6 3.82 1.35 10 .1 2.40 1.23 8.40 FL9(C,V)B12 ...

  • York E*BD-F018 THRU 060 - page 16

    246819-BTG-H-0208 16 Unitary Products Group CP equals MBH output divided by (to tal KW input x 3.412). HSPF (Heating Seasonal Performance Factor) is the total heat ing output during a normal annual usage period for heating divided by the total electric power input during the same period. — = Not Applicable. EABD-F042S ( F , L ) L 8 V C 2 0 F C / ...

  • York E*BD-F018 THRU 060 - page 17

    246819-BTG-H-0208 Unitary Products Group 17 ACCESSORIES Refer to Price Manual for specific model numbers. St art Assist Kit (2SA067*) Blower Time Delay - A vailable to increase efficiency when installed. Installs on indoor section and maintains blower for approximately one minute a fter cooling thermostat has been satisfied. Hard St art Kit s - Pro ...

  • York E*BD-F018 THRU 060 - page 18

    246819-BTG-H-0208 18 Unitary Products Group Multipliers for determining th e performance with other indoor sections . NOTE: For dry bulb temperatures dif ferent than those listed (bet ween 73-87 F), sensible capacity increases by 1060 BTUH per 100 0 CFM per degree above the listed temperatu re and decre ases by 1060 BTUH per 1000 CFM per degree bel ...

  • York E*BD-F018 THRU 060 - page 19

    246819-BTG-H-0208 Unitary Products Group 19 Multipliers for determining th e performance with other indoor sections . NOTE: For dry bulb temperatures dif ferent than those listed (bet ween 73-87 F), sensible capacity increase s by 1060 BTUH per 100 0 CFM per degree above the listed temperature and decreases by 1060 BTUH per 1 000 CFM per degree bel ...

  • York E*BD-F018 THRU 060 - page 20

    246819-BTG-H-0208 20 Unitary Products Group Multipliers for determining th e performance with other indoor sections . NOTE: For dry bulb temperatures dif ferent than those listed (bet ween 73-87 F), sensible capacity increases by 1060 BTUH per 100 0 CFM per degree above the listed temperatu re and decre ases by 1060 BTUH per 1000 CFM per degree bel ...

  • York E*BD-F018 THRU 060 - page 21

    246819-BTG-H-0208 Unitary Products Group 21 Multipliers for determining th e performance with other indoor sections NOTE: For dry bulb temperatures dif ferent than those listed (bet ween 73-87 F), sensible capacity increase s by 1060 BTUH per 100 0 CFM per degree above the listed temperature and decreases by 1060 BTUH per 1 000 CFM per degree below ...

  • York E*BD-F018 THRU 060 - page 22

    246819-BTG-H-0208 22 Unitary Products Group Multipliers for determining th e performance with other indoor sections . NOTE: For dry bulb temperatures dif ferent than those listed (bet ween 73-87 F), sensible capacity increases by 1060 BTUH per 100 0 CFM per degree above the listed temperatu re and decre ases by 1060 BTUH per 1000 CFM per degree bel ...

  • York E*BD-F018 THRU 060 - page 23

    246819-BTG-H-0208 Unitary Products Group 23 Multipliers for determining th e performance with other indoor sections . NOTE: For dry bulb temperatures dif ferent than those listed (bet ween 73-87 F), sensible capacity increase s by 1060 BTUH per 100 0 CFM per degree above the listed temperature and decreases by 1060 BTUH per 1 000 CFM per degree bel ...

  • York E*BD-F018 THRU 060 - page 24

    246819-BTG-H-0208 24 Unitary Products Group Multipliers for determining th e performance with other indoor sections . NOTE: For dry bulb temperatures dif ferent than those listed (bet ween 73-87 F), sensible capacity increases by 1060 BTUH per 100 0 CFM per degree above the listed temperatu re and decre ases by 1060 BTUH per 1000 CFM per degree bel ...

  • York E*BD-F018 THRU 060 - page 25

    246819-BTG-H-0208 Unitary Products Group 25 Multipliers for determining the performance with other indoor sections . HEA TING PERFORMA NCE DA T A CONDENSING UNIT MODEL NO EABD-F018S EV APORA T OR COIL MODEL NO FC /MC/PC/UC18 AIR TEMP . ENTERING OUTDOOR UNIT AIR TEMP . ENTERING INDOOR COIL ID CFM 450 600 750 MBTUH KW C.O.P . MBTUH KW C.O.P . MBTUH K ...

  • York E*BD-F018 THRU 060 - page 26

    246819-BTG-H-0208 26 Unitary Products Group Multipliers for determining the perfo rman ce with other indoor sections. HEA TING PERFORMANCE DA T A CONDENSING UNIT MODEL NO EABD-F024S EV APORA T OR COIL MODEL NO FC /MC/PC/UC24 AIR TEMP . ENTERING OUTDOOR UNIT AIR TEMP . ENTERING INDOOR COIL ID CFM 600 800 1000 MBTUH KW C.O.P . MBTUH KW C.O.P . MBTU H ...

  • York E*BD-F018 THRU 060 - page 27

    246819-BTG-H-0208 Unitary Products Group 27 Multipliers for determining the performance with other indoor sections . * = Single-phase outdoor units only . * = Single-phase outdoor units only . HEA TING PERFORMA NCE DA T A CONDENSING UNIT MODEL NO E ABD-F030S, EABD-(T ,W)030S** EV APORA T OR COIL MODEL NO FC /MC/PC35 AIR TEMP . ENTERING OUTDOOR UNIT ...

  • York E*BD-F018 THRU 060 - page 28

    246819-BTG-H-0208 28 Unitary Products Group Multipliers for determining the perfo rman ce with other indoor sections. * = Single-phase outdoor units only . * = Single-phase outdoor units only . HEA TING PERFORMANCE DA T A CONDENSING UNIT MODEL NO E ABD-F036S, EABD-(T ,W)036S** EV APORA T OR COIL MODEL NO FC /MC/PC/UC48 AIR TEMP . ENTERING OUTDOOR U ...

  • York E*BD-F018 THRU 060 - page 29

    246819-BTG-H-0208 Unitary Products Group 29 Multipliers for determining the performance with other indoor sections . * = Single-phase outdoor units only . * = Single-phase outdoor units only . HEA TING PERFORMA NCE DA T A CONDENSING UNIT MODEL NO E ABD-F042S, EABD-(T ,W)042S** EV APORA T OR COIL MODEL NO FC /MC/PC/UC48 AIR TEMP . ENTERING OUTDOOR U ...

  • York E*BD-F018 THRU 060 - page 30

    246819-BTG-H-0208 30 Unitary Products Group Multipliers for determining the perfo rman ce with other indoor sections. * = Single-phase outdoor units only . * = Single-phase outdoor units only . HEA TING PERFORMANCE DA T A CONDENSING UNIT MODEL NO E ABD-F048S, EABD-(T ,W)048S** EV APORA T OR COIL MODEL NO FC /MC/PC/UC60 AIR TEMP . ENTERING OUTDOOR U ...

  • York E*BD-F018 THRU 060 - page 31

    246819-BTG-H-0208 Unitary Products Group 31 Multipliers for determining the performance with other indoor sections . * = Single-phase outdoor units only . * = Single-phase outdoor units only . HEA TING PERFORMA NCE DA T A CONDENSING UNIT MODEL NO E ABD-F060S, EABD-(T ,W)060S** EV APORA T OR COIL MODEL NO FC /MC/PC/UC60 AIR TEMP . ENTERING OUTDOOR U ...

  • York E*BD-F018 THRU 060 - page 32

    Subject to change without notice. Printed in U.S.A. 246819-BTG-H-0208 Copyright © by Unitary Products Group. 2008. Al l rights reserved. Supersedes: 246819-BTG-G-0607 Unitary 5005 Norman Product Y ork OK Group Drive 73069 NOTES ...

Производитель York Категория Heat Pump

Документы, которые мы получаем от производителя устройства York E*BD-F018 THRU 060 мы можем разделить на несколько групп. Это в частности:
- технические чертежи York
- инструкции обслуживания E*BD-F018 THRU 060
- паспорта изделия York
- информационные брошюры
- энергетические этикетки York E*BD-F018 THRU 060
Все из них важны, однако самую важную информацию с точки зрения пользователя мы найдем в инструкции обслуживания York E*BD-F018 THRU 060.

Группа документов, определяемая как инструкции обслуживания, делится также на более подробные типы, такие как: Инструкции монтажа York E*BD-F018 THRU 060, инструкции обслуживания, короткие инструкции или инструкции пользователя York E*BD-F018 THRU 060. В зависимости от потребностей, Вам необходимо поискать требуемый документ. На нашем сайте Вы можете просмотреть самую популярную инструкцию использования изделия York E*BD-F018 THRU 060.

Похожие инструкции обслуживания

Полная инструкция обслуживания устройства York E*BD-F018 THRU 060, как должна выглядеть?
Инструкция обслуживания, определяемая также как пособие пользователя, или просто "руководство" - это технический документ, цель которого заключается в использовании York E*BD-F018 THRU 060 пользователями. Инструкции пишет, как правило технический писатель, языком, доступным для всех пользователей York E*BD-F018 THRU 060.

Полная инструкция обслуживания York, должна заключать несколько основных элементов. Часть из них менее важная, как например: обложка / титульный лист или авторские страницы. Однако остальная часть, должна дать нам важную с точки зрения пользователя информацию.

1. Вступление и рекомендации, как пользоваться инструкцией York E*BD-F018 THRU 060 - В начале каждой инструкции, необходимо найти указания, как пользоваться данным пособием. Здесь должна находится информация, касающаяся местонахождения содержания York E*BD-F018 THRU 060, FAQ и самых распространенных проблем - то есть мест, которые чаще всего ищут пользователи в каждой инструкции обслуживания
2. Содержание - индекс всех советов, касающихся York E*BD-F018 THRU 060, которое найдем в данном документе
3. Советы по использованию основных функций устройства York E*BD-F018 THRU 060 - которые должны облегчить нам первые шаги во время использования York E*BD-F018 THRU 060
4. Troubleshooting - систематизированный ряд действия, который поможет нам диагностировать а в дальнейшем очередность решения важнейших проблем York E*BD-F018 THRU 060
5. FAQ - чаще всего задаваемые вопросы
6. Контактные данные Информация о том, где искать контактные данные производителя / сервисного центра York E*BD-F018 THRU 060 в данной стране, если самостоятельно не получится решить проблему.

У вас вопрос, касающийся York E*BD-F018 THRU 060?

Воспользуйтесь формуляром, находящимся ниже

Если с помощью найденной инструкции Вы не решили свою проблему с York E*BD-F018 THRU 060, задайте вопрос, заполнив следующий формуляр. Если у какого то из пользователей была похожая проблема с York E*BD-F018 THRU 060 со всей вероятностью он захочет поделиться методом ее решения.

Перепишите текст с картинки

Комментарии (0)