    TECHNICAL GUIDE SPLIT -SYSTEM AIR CONDITIONERS 10 SEER MODELS: H*RA018 THRU 060 (1.5 THRU 5 NOMINAL TONS, 1 PH) H*RA036 THRU 090 (3 THRU 7.5 NOMINAL TONS, 3 PH) MODELS: 018 - 060 (1 PH & 3 PH) MODELS: 076 - 090 (3 PH) Due to con tinuous p roduct improve ment, speci fica- tions are subj ect to change with out notice. Visit us on the web at www . ...

  • York THRU H*RA018 THRU 060 - page 2

    036-21121-002 Rev. A (0602 ) 2 Unitary Products Group 1. Rat ed in accordance with ARI S tandard 1 10, utilization range “A”. 2. Dua l element fuses or HACR circuit br eaker . 3. All scrolls listed with a sup erscript “B” are Bristol scrolls. All sc rolls listed w ith a superscript “C” are Copeland scrolls. 4. The Unit Charg e is correc ...

  • York THRU H*RA018 THRU 060 - page 3

    036-21121-002 Rev. A (0602) Unitary Products Group 3 COOLING CAP ACITY - Wi th Air Handler Coils UNIT MODEL AIR HANDLER COIL 1 MODEL COOLING MODEL ELECTRIC 2 HEA T KW W RA TED CFM NET MBH SEER W/O TXV SEER + TXV 3 EER TOT AL SENS. 1 PH 10 SEER AC WITH N1AH / G2FD H1RA018S06 N1AHB0806 2,5,8,10 17 G2FD024S17 650 19.0 14.1 10.50 - 9.80 H1RA024S06 N1AH ...

  • York THRU H*RA018 THRU 060 - page 4

    036-21121-002 Rev. A (0602 ) 4 Unitary Products Group COOLING CAP ACITY - Up flow , Downflow , & Horizont al Furnaces and Coils UNIT MODEL FURNACE** COIL MODEL COOLING CFM RANGE (MIN.-MAX.) W RA TED CFM NET MBH SEER + TXV W/O TDR SEER + TXV 1 + TDR* EER TOT AL SE NS . H1RA018S06 575 725 14,17 G1F A024S14,17 650 18.0 13.3 10.00 - 9.20 14 G1F A03 ...

  • York THRU H*RA018 THRU 060 - page 5

    036-21121-002 Rev. A (0602) Unitary Products Group 5 * Requires a 2FD Blower T ime Delay unless a standa rd furnace is equipped with one. ** Refer to Quick Selection Chart for specific furnace match-up. *** This coil is for upflow application only . H1RA036S25,46 1050 1350 17,21 G1F A036S17,21 1200 33.6 24.9 10.00 - 9.10 21,24 G1F A048S21,24 1200 3 ...

  • York THRU H*RA018 THRU 060 - page 6

    036-21121-002 Rev. A (0602 ) 6 Unitary Products Group NOTES: 1. For condensing unit only . Does not include e ffect of evaporator motor power or heat. 2. Performance based on 1 5° superheat and 1 5° sub-cooling at condensing unit. a. Increase capacity 1% for each 2° increase in sub-cooling. b. Decrease capacity 1% for each 2° decrease in sub-co ...

  • York THRU H*RA018 THRU 060 - page 7

    036-21121-002 Rev. A (0602) Unitary Products Group 7 ACCESSORIES* Refer to Price Manual for specific model numbers. Hard St art Kit - Provides increased starting torque for areas with low voltage. Compressor Blanket - Designed to further reduce the nor- mal compressor operating sound. Refer to price pages for specific match-ups. Off Cycle Timer Del ...

  • York THRU H*RA018 THRU 060 - page 8

    036-21121-002 Rev. A (0602 ) 8 Unitary Products Group TYPICAL FIELD WIRING - 1 Phase Application TYPICAL FIELD WIRING - 3 Phase Application ALL FIELD WIRING T O BE IN ACCORDANCE WITH ELECTRIC CODE (NEC) AND/OR LOCAL CODES POWER WIRING 208/230-1-60 230-1-50 CONT ACTOR TERMINALS COIL GND. LUG CY R G W Y R GW POWER WIRING CONTROL WIRING F ACTORY WIRIN ...

  • York THRU H*RA018 THRU 060 - page 9

    036-21121-002 Rev. A (0602) Unitary Products Group 9 Multipliers for determining the performance with other indoor sections . COOLING PERFORMANCE DA T A AIR CONDITIONER MODEL NO. H1RA018S06 INDOOR COIL MODEL NO. G1F A024S14 ,17 CONDENSER ENTERING AIR TEMPERA TURE ID CFM 550 650 750 ID DB (°F) 85 80 70 85 80 70 85 80 70 ID WB (°F) 72 67 57 72 67 5 ...

  • York THRU H*RA018 THRU 060 - page 10

    036-21121-002 Rev. A (0602 ) 10 Unitary Products Group Multipliers for determining the p erformance with other indoor sections. COOLING PERFORMANCE DA T A AIR CONDITIONER MODEL NO. H1RA024S06 INDOOR COIL MODEL NO. G1F A024S14 , 17 CONDENSER ENTERING AIR TEMPERA TURE ID CFM 600 800 1000 ID DB (°F) 85 80 75 70 85 80 75 70 85 80 75 70 ID WB (°F) 72 ...

  • York THRU H*RA018 THRU 060 - page 11

    036-21121-002 Rev. A (0602) Unitary Products Group 11 Multipliers for determining th e performance with other indoo r sections. COOLING PERFORMANCE DA T A AIR CONDITIONER MODEL NO. H2RA030S06 INDOOR COIL MODEL NO. G1F A036S17 ,21 CONDENSER ENTERING AIR TEMPERA TURE ID CFM 800 1000 1200 ID DB (°F) 85 80 75 70 85 80 75 70 85 80 75 70 ID WB (°F) 72 ...

  • York THRU H*RA018 THRU 060 - page 12

    036-21121-002 Rev. A (0602 ) 12 Unitary Products Group Multipliers for determining th e performance with other indoo r sections. 1 Phase 3 Phase COOLING PERFORMANCE DA T A AIR CONDITIONER MODEL NO . H2RA036S06, H1RA03 6S(25,46) INDOOR COIL MODEL NO. G1F A036S17 ,21 CONDENSER ENTERING AIR TEMPERA TURE ID CFM 1 150 1250 1350 ID DB (°F) 85 80 70 85 8 ...

  • York THRU H*RA018 THRU 060 - page 13

    036-21121-002 Rev. A (0602) Unitary Products Group 13 Multipliers for determining th e performance with other indoo r sections. 1 Phase 3 Phase COOLING PERFORMANCE DA T A AIR CONDITIONER MODEL NO. H 1RA042S06, H1RA04 2S(25,46) INDOOR COIL MODEL NO. G1F A048S21 ,24 CONDENSER ENTERING AIR TEMPERA TURE ID CFM 1200 1400 1600 ID DB (°F) 85 80 70 85 80 ...

  • York THRU H*RA018 THRU 060 - page 14

    036-21121-002 Rev. A (0602 ) 14 Unitary Products Group Multipliers for determining th e performance with other indoo r sections. 1 Phase 3 Phase COOLING PERFORMANCE DA T A AIR CONDITIONER MODEL NO . H1RA048S06, H1RA04 8S(25,46) INDOOR COIL MODEL NO. G1F A048S21 ,24 CONDENSER ENTERING AIR TEMPERA TURE ID CFM 1200 1400 1600 ID DB (°F) 85 80 75 70 85 ...

  • York THRU H*RA018 THRU 060 - page 15

    036-21121-002 Rev. A (0602) Unitary Products Group 15 Multipliers for determining th e performance with other indoo r sections. COOLING PERFORMANCE DA T A AIR CONDITIONER MODEL NO. H3RA060S06 INDOOR COIL MODEL NO. G1F A060S21 ,24 CONDENSER ENTERING AIR TEMPERA TURE ID CFM 2050 1800 1550 ID DB (°F) 85 80 70 85 80 70 85 80 70 ID WB (°F) 72 67 57 72 ...

  • York THRU H*RA018 THRU 060 - page 16

    036-21121-002 Rev. A (0602 ) 16 Unitary Products Group Multipliers for determining th e performance with other indoo r sections. COOLING PERFORMANCE DA T A AIR CONDITIONER MODEL NO. H1RA060S(25,46) INDOOR COIL MODEL NO. G2FD060S24A CONDENSER ENTERING AIR TEMPERA TURE ID CFM 1450 1700 1950 ID DB (°F) 85 80 70 85 80 70 85 80 70 ID WB (°F) 72 67 57 ...

  • York THRU H*RA018 THRU 060 - page 17

    036-21121-002 Rev. A (0602) Unitary Products Group 17 Multipliers for determining th e performance with other indoo r sections. COOLING PERFORMANCE DA T A AIR CONDITIONER MODEL NO. H1RA076S(25,46) INDOOR COIL MODEL NO. K4EV090 CONDENSER ENTERING AIR TEMPERA TURE ID CFM 2100 2600 3100 ID DB (°F) 85 80 70 85 80 70 85 80 70 ID WB (°F) 72 67 57 72 67 ...

  • York THRU H*RA018 THRU 060 - page 18

    036-21121-002 Rev. A (0602 ) 18 Unitary Products Group Multipliers for determining th e performance with other indoo r sections. COOLING PERFORMANCE DA T A AIR CONDITIONER MODEL NO. H1RA090S(25,46) INDOOR COIL MODEL NO. K4EV090 CONDENSER ENTERING AIR TEMPERA TURE ID CFM 2400 3000 3600 ID DB (°F) 85 80 70 85 80 70 85 80 70 ID WB (°F) 72 67 57 72 6 ...

  • York THRU H*RA018 THRU 060 - page 19

    036-21121-002 Rev. A (0602) Unitary Products Group 19 MA TCHING INDOOR COMPONENTS G1UA 1/2 CASED UPFLOW G1HD HORIZONT AL DUCT G2FD* MUL TI-POSITION (UPFLOW , HORIZONT AL AND DOWNFLOW) * Available with factory installed horizontal drain pan. ADD-ON COILS - FOR FURNACE APPLICA TIONS G1NA UNCASED UPFLOW G1F A FULL CASED UPFLOW G2FD090 is upflow only . ...

  • York THRU H*RA018 THRU 060 - page 20

    Subject to change without notice. Printed in U .S.A. 036-21121-002 Rev. A (0602) Copyright © by York International Corp. 2002. All right s reserved. Supersedes: 036-21 121-001 Rev . A (301) Unitary 5005 Norman Product s Y ork O K Group Drive 73069 NOTES ...

Производитель York Категория Air Conditioner

Документы, которые мы получаем от производителя устройства York THRU H*RA018 THRU 060 мы можем разделить на несколько групп. Это в частности:
- технические чертежи York
- инструкции обслуживания THRU H*RA018 THRU 060
- паспорта изделия York
- информационные брошюры
- энергетические этикетки York THRU H*RA018 THRU 060
Все из них важны, однако самую важную информацию с точки зрения пользователя мы найдем в инструкции обслуживания York THRU H*RA018 THRU 060.

Группа документов, определяемая как инструкции обслуживания, делится также на более подробные типы, такие как: Инструкции монтажа York THRU H*RA018 THRU 060, инструкции обслуживания, короткие инструкции или инструкции пользователя York THRU H*RA018 THRU 060. В зависимости от потребностей, Вам необходимо поискать требуемый документ. На нашем сайте Вы можете просмотреть самую популярную инструкцию использования изделия York THRU H*RA018 THRU 060.

Похожие инструкции обслуживания

Полная инструкция обслуживания устройства York THRU H*RA018 THRU 060, как должна выглядеть?
Инструкция обслуживания, определяемая также как пособие пользователя, или просто "руководство" - это технический документ, цель которого заключается в использовании York THRU H*RA018 THRU 060 пользователями. Инструкции пишет, как правило технический писатель, языком, доступным для всех пользователей York THRU H*RA018 THRU 060.

Полная инструкция обслуживания York, должна заключать несколько основных элементов. Часть из них менее важная, как например: обложка / титульный лист или авторские страницы. Однако остальная часть, должна дать нам важную с точки зрения пользователя информацию.

1. Вступление и рекомендации, как пользоваться инструкцией York THRU H*RA018 THRU 060 - В начале каждой инструкции, необходимо найти указания, как пользоваться данным пособием. Здесь должна находится информация, касающаяся местонахождения содержания York THRU H*RA018 THRU 060, FAQ и самых распространенных проблем - то есть мест, которые чаще всего ищут пользователи в каждой инструкции обслуживания
2. Содержание - индекс всех советов, касающихся York THRU H*RA018 THRU 060, которое найдем в данном документе
3. Советы по использованию основных функций устройства York THRU H*RA018 THRU 060 - которые должны облегчить нам первые шаги во время использования York THRU H*RA018 THRU 060
4. Troubleshooting - систематизированный ряд действия, который поможет нам диагностировать а в дальнейшем очередность решения важнейших проблем York THRU H*RA018 THRU 060
5. FAQ - чаще всего задаваемые вопросы
6. Контактные данные Информация о том, где искать контактные данные производителя / сервисного центра York THRU H*RA018 THRU 060 в данной стране, если самостоятельно не получится решить проблему.

У вас вопрос, касающийся York THRU H*RA018 THRU 060?

Воспользуйтесь формуляром, находящимся ниже

Если с помощью найденной инструкции Вы не решили свою проблему с York THRU H*RA018 THRU 060, задайте вопрос, заполнив следующий формуляр. Если у какого то из пользователей была похожая проблема с York THRU H*RA018 THRU 060 со всей вероятностью он захочет поделиться методом ее решения.

Перепишите текст с картинки

Комментарии (0)