Manual de instrucciones Weil-McLain BCP-3

16 de páginas 0.47 mb
Descargar

Pasar a la página of 16

Summary
  • Weil-McLain BCP-3 - page 1

    INST ALLA TION AND OPERA TION INSTRUCTIONS BCP-3 Hydronic Multi-Stage Boiler Control Blue (Output 2) White (Output 3) Y ellow (Output 1) Boiler SYS Pump DHW Pump SET SET SYSTEM = 147F TARGET = 150F Output 1 2 Line Alphanumeric Display Displays sensor values and menu settings Output Lights indicate output status Display Section Locking Screws Black ...

  • Weil-McLain BCP-3 - page 2

    2 BCP-3 Installation and Operation Manual thermostat is satisfied. Another, is a Setback input that will switch the heating system to a lower set point determined by the Set Back setting. T ype of Radiation in Building Reset Ratio Offset Radiators (Steel & Cast Iron) 1.00 (O) : 1.00 (S) 0˚F Baseboard (Finned copper tube& Cast Iron) 1.00 ( ...

  • Weil-McLain BCP-3 - page 3

    3 BCP-3 Installation and Operation Manual Mounting the Controller • The BCP-3 is designed to mount on a 1900 (4”x4”) deep electrical box. • If additional room is needed for wiring use the extension skirt provided. • Place the BCP-3 in an indoor convenient location near the unit to be controlled and away from excessive heat or cold. • Pa ...

  • Weil-McLain BCP-3 - page 4

    4 BCP-3 Installation and Operation Manual IMPORT ANT Determining the proper location for the Outdoor Sensor is very important. The BCP-3 will base the heat on the outdoor temperature information it receives from this location. If the sensor is in the sun, or covered with ice, its reading will be different from the actual outdoor temperature. Outdoo ...

  • Weil-McLain BCP-3 - page 5

    5 BCP-3 Installation and Operation Manual Output Mode T able Output Mode Description Output 1 (Y ellow Wires) Output 2 (Blue Wires) Output 3 (White Wires) Notes 1-On/Off+1-Pump One On/Off boiler and a System pump Sys Pump Boiler Not used 1-On/Off+2-Pump One On/Of f boiler , a System pump and a Domestic Hot W ater Pump Sys Pump Boiler DHW Pump 2-On/ ...

  • Weil-McLain BCP-3 - page 6

    6 BCP-3 Installation and Operation Manual T1 T2 COM COM T3+ T3- EXT+ EXT- P+ P- COM 24V AC System Sensor Outdoor Sensor Enable Dry Contact Setback Timer 120 V AC Wiring 1 Lo/Hi Boiler + System Pump System Pump ( Y ellow/Output 1) Boiler Lo (Blue/ Output 2) Boiler Hi ( White/ Output 3) DHW Call Pow er (Black) 120 V AC L N L N T1 T2 COM COM T3+ T3- E ...

  • Weil-McLain BCP-3 - page 7

    7 BCP-3 Installation and Operation Manual Weil McLain V1.00 (c) 2008 BCP-3 Boiler Control Loading Default Values... DISPLAY UNIT: F C SENSOR FAULT: Output On Output Off SETUP COMPLETE! PRESS SET Startup Menu SYSTEM= 68 F TARGET= 150 F ------MAIN------ Set Point 170 F <Out. Reset> <Settings> <Maintenance> <Sys. Startup> <I ...

  • Weil-McLain BCP-3 - page 8

    8 BCP-3 Installation and Operation Manual Button and Navigating Menus The BCP-3 has three buttons. • The SET button function varies. When the Default Screen is displayed, pressing the SET Button views the MENU. When in the Menus and settings, the SET Button accepts the selected entry or setting value. • When in the menus, pressing the Up and Do ...

  • Weil-McLain BCP-3 - page 9

    9 BCP-3 Installation and Operation Manual Outdoor Reset Mode • When Output-On is selected, the BCP-3 will energize all boiler and system relays when the System reads SHORT or OPEN and Outdoor is below Outdoor Cutoff. Thus, all boilers will run on their limits. However , if the Outdoor sensor fails and the Outdoor reads SHORT or OPEN , the BCP-3 w ...

  • Weil-McLain BCP-3 - page 10

    10 BCP-3 Installation and Operation Manual • If required: Adjust the RESET RA TIO in cold weather . If the ambient building temperatures are too cold in cold weather , move the ratio to a higher selection. That is, if 1.00 (O):1.00 (S) was initially selected, change the selection to 1.00 (O):1.25 (S). If the building temperatures are too warm in ...

  • Weil-McLain BCP-3 - page 11

    11 BCP-3 Installation and Operation Manual Minimum T arget (A vailable when Startup Control Mode = Outdoor Reset) Options: From 70 º F/21 ºC to 170 º F/77 ºC Default: 140 º F/60 ºC SET SET /Set Point/<Out. Reset>/Min. Tgt • The Minimum T arget T emperature must be set to the boiler manufacturer ’ s specification. Min Target: 140 F ...

  • Weil-McLain BCP-3 - page 12

    12 BCP-3 Installation and Operation Manual Minimum Runtime Options: 1 to 60 minutes Default: 2 minutes SET SET /<Settings>/<Stage>/Min. Runtime • This is the minimum amount of time any stage will run. • The Minimum Runtime for the lowest firing stage on a boiler starts after the purge cycle. • Initially , set the Min. Runtime to ...

  • Weil-McLain BCP-3 - page 13

    13 BCP-3 Installation and Operation Manual Domestic Hot W ater (DHW) Priority Options: NO and From 1 min to 120 min Default: NO SET SET /Settings>/DHW Prior . DHW Priority: 60m • The DHW Priority , with a value set to other than NO, provides the user with an adjustable DHW priority timer for the domestic hot water call. That is, initiating a D ...

  • Weil-McLain BCP-3 - page 14

    14 BCP-3 Installation and Operation Manual T roubleshooting No Display or LED Lights Check the power to the BCP-3. The BCP-3 requires 120V AC power to the Black wires or 24V AC to the right-most terminals. T urn the power off and back on to restore the display . If unsuccessful, make sure that the control's Display Cover is securely mounted to ...

  • Weil-McLain BCP-3 - page 15

    15 BCP-3 Installation and Operation Manual Boiler1 DHW Indirect Building Heat System Sensor Outdoor Sensor T1 T2 COM COM T3+ T3- EXT+ EXT- P+ P- COM 24VAC } System Sensor } Outdoor Sensor } DHW Call Dry Contact } Enable Dry Contact } Setback Dry Contact Boiler SYS Pump DHW Pump SET SET SYSTEM = 147F TARGET = 150F Y ellow Wires (Output 1) Blue Wires ...

  • Weil-McLain BCP-3 - page 16

    16 BCP-3 Installation and Operation Manual 500 Blaine Street Michigan City , Indiana 46360 219-879-6561 http://www .weil-mclain.com HT #059075-00 A Specifications V oltage Input: . . . . . . . 120 V AC 60 Hz(2 Black wires) /24V AC 60 Hz (24V Ac terminals) (Only One Power Source) Power Consumption: . . . . . . . . . . . . . . . . . . . . . . . . . ...

Fabricante Weil-McLain Categoría Boiler

Los documentos del dispositivo Weil-McLain BCP-3 que obtenemos del fabricante se pueden dividir en varios grupos. Entre ellos están::
- dibujos técnicos Weil-McLain
- manuales de instrucciones BCP-3
- hojas de producto Weil-McLain
- folletos informativos
- o etiquetas energéticas Weil-McLain BCP-3
Todos son importantes, pero lo más importante desde el punto de vista del usuario de un dispositivo lo encontraremos en el manual de instrucciones Weil-McLain BCP-3.

Un conjunto de documentos determinado como manual de instrucciones se divide también en tipos más detallados, tales como: instrucciones de montaje Weil-McLain BCP-3, instrucciones de servicio, instrucciones cortas o instrucciones de usuario Weil-McLain BCP-3. Dependiendo de la situación debes buscar el documento que necesitas. En nuestra página puedes consultar el manual de instrucciones más popular del producto Weil-McLain BCP-3.

Manuales de instrucciones parecidos

El manual de instrucciones del dispositivo Weil-McLain BCP-3, ¿cómo debería ser?
El manual de instrucciones, también determinado como el manual de usuario o simplemente instrucciones, es un documento técnico que tiene como objetivo ayudar a los usuarios a utilizar Weil-McLain BCP-3. Las instrucciones normalmente las realiza un escritor técnico pero en un lenguaje comprensible para todos los usuarios de Weil-McLain BCP-3.

El manual de instrucciones completo de Weil-McLain debe contener unos elementos básicos. Una parte de ellos es menos importante, como por ejemplo: la portada / la página principal o las páginas de autor. Sin embargo, lo demás debe facilitarnos la información más importante desde el punto de vista del usuario.

1. Introducción y pistas sobre cómo orientarse con el manual Weil-McLain BCP-3 - Al principio de cada manual se deben encontrar las indicaciones acerca de la manera de usar un manual de instrucciones. Debe contener información sobre dónde encontrar el índice Weil-McLain BCP-3, preguntas frecuentes o problemas más comunes – son los apartados más buscados por los usuarios de cada manual de instrucciones.
2. Índice - listados de todos los consejos acerca de Weil-McLain BCP-3 que encontraremos en el documento
3. Consejos de uso de las funciones básicas del dispositivo Weil-McLain BCP-3 - que deben facilitarnos los primeros pasos durante el uso de Weil-McLain BCP-3
4. Troubleshooting - una secuencia sistematizada de acciones que nos ayudará a diagnosticar los problemas más importantes con Weil-McLain BCP-3
5. FAQ - las preguntas frecuentes
6. Datos de contacto Información acerca de cómo encontrar los datos de contacto del fabricante / servicio de Weil-McLain BCP-3 en cada país si no somos capaces de solucionar el problema por nuestra cuenta.

¿Tienes una pregunta acerca de Weil-McLain BCP-3?

Utiliza el formulario que se encuentra abajo

Si con la ayuda del manual de instrucciones encontrado no has podido solucionar tu problema con Weil-McLain BCP-3, haz una pregunta utilizando el formulario que se encuentra abajo. Si alguno de los usuarios ha tenido un problema parecido con Weil-McLain BCP-3 probablemente compartirá una forma de solucionarlo.

Copia el texto de la imagen

Comentarios (0)