Manuel d’utilisation Weil-McLain BCP-3

16 pages 0.47 mb
Télécharger

Aller à la page of 16

Summary
  • Weil-McLain BCP-3 - page 1

    INST ALLA TION AND OPERA TION INSTRUCTIONS BCP-3 Hydronic Multi-Stage Boiler Control Blue (Output 2) White (Output 3) Y ellow (Output 1) Boiler SYS Pump DHW Pump SET SET SYSTEM = 147F TARGET = 150F Output 1 2 Line Alphanumeric Display Displays sensor values and menu settings Output Lights indicate output status Display Section Locking Screws Black ...

  • Weil-McLain BCP-3 - page 2

    2 BCP-3 Installation and Operation Manual thermostat is satisfied. Another, is a Setback input that will switch the heating system to a lower set point determined by the Set Back setting. T ype of Radiation in Building Reset Ratio Offset Radiators (Steel & Cast Iron) 1.00 (O) : 1.00 (S) 0˚F Baseboard (Finned copper tube& Cast Iron) 1.00 ( ...

  • Weil-McLain BCP-3 - page 3

    3 BCP-3 Installation and Operation Manual Mounting the Controller • The BCP-3 is designed to mount on a 1900 (4”x4”) deep electrical box. • If additional room is needed for wiring use the extension skirt provided. • Place the BCP-3 in an indoor convenient location near the unit to be controlled and away from excessive heat or cold. • Pa ...

  • Weil-McLain BCP-3 - page 4

    4 BCP-3 Installation and Operation Manual IMPORT ANT Determining the proper location for the Outdoor Sensor is very important. The BCP-3 will base the heat on the outdoor temperature information it receives from this location. If the sensor is in the sun, or covered with ice, its reading will be different from the actual outdoor temperature. Outdoo ...

  • Weil-McLain BCP-3 - page 5

    5 BCP-3 Installation and Operation Manual Output Mode T able Output Mode Description Output 1 (Y ellow Wires) Output 2 (Blue Wires) Output 3 (White Wires) Notes 1-On/Off+1-Pump One On/Off boiler and a System pump Sys Pump Boiler Not used 1-On/Off+2-Pump One On/Of f boiler , a System pump and a Domestic Hot W ater Pump Sys Pump Boiler DHW Pump 2-On/ ...

  • Weil-McLain BCP-3 - page 6

    6 BCP-3 Installation and Operation Manual T1 T2 COM COM T3+ T3- EXT+ EXT- P+ P- COM 24V AC System Sensor Outdoor Sensor Enable Dry Contact Setback Timer 120 V AC Wiring 1 Lo/Hi Boiler + System Pump System Pump ( Y ellow/Output 1) Boiler Lo (Blue/ Output 2) Boiler Hi ( White/ Output 3) DHW Call Pow er (Black) 120 V AC L N L N T1 T2 COM COM T3+ T3- E ...

  • Weil-McLain BCP-3 - page 7

    7 BCP-3 Installation and Operation Manual Weil McLain V1.00 (c) 2008 BCP-3 Boiler Control Loading Default Values... DISPLAY UNIT: F C SENSOR FAULT: Output On Output Off SETUP COMPLETE! PRESS SET Startup Menu SYSTEM= 68 F TARGET= 150 F ------MAIN------ Set Point 170 F <Out. Reset> <Settings> <Maintenance> <Sys. Startup> <I ...

  • Weil-McLain BCP-3 - page 8

    8 BCP-3 Installation and Operation Manual Button and Navigating Menus The BCP-3 has three buttons. • The SET button function varies. When the Default Screen is displayed, pressing the SET Button views the MENU. When in the Menus and settings, the SET Button accepts the selected entry or setting value. • When in the menus, pressing the Up and Do ...

  • Weil-McLain BCP-3 - page 9

    9 BCP-3 Installation and Operation Manual Outdoor Reset Mode • When Output-On is selected, the BCP-3 will energize all boiler and system relays when the System reads SHORT or OPEN and Outdoor is below Outdoor Cutoff. Thus, all boilers will run on their limits. However , if the Outdoor sensor fails and the Outdoor reads SHORT or OPEN , the BCP-3 w ...

  • Weil-McLain BCP-3 - page 10

    10 BCP-3 Installation and Operation Manual • If required: Adjust the RESET RA TIO in cold weather . If the ambient building temperatures are too cold in cold weather , move the ratio to a higher selection. That is, if 1.00 (O):1.00 (S) was initially selected, change the selection to 1.00 (O):1.25 (S). If the building temperatures are too warm in ...

  • Weil-McLain BCP-3 - page 11

    11 BCP-3 Installation and Operation Manual Minimum T arget (A vailable when Startup Control Mode = Outdoor Reset) Options: From 70 º F/21 ºC to 170 º F/77 ºC Default: 140 º F/60 ºC SET SET /Set Point/<Out. Reset>/Min. Tgt • The Minimum T arget T emperature must be set to the boiler manufacturer ’ s specification. Min Target: 140 F ...

  • Weil-McLain BCP-3 - page 12

    12 BCP-3 Installation and Operation Manual Minimum Runtime Options: 1 to 60 minutes Default: 2 minutes SET SET /<Settings>/<Stage>/Min. Runtime • This is the minimum amount of time any stage will run. • The Minimum Runtime for the lowest firing stage on a boiler starts after the purge cycle. • Initially , set the Min. Runtime to ...

  • Weil-McLain BCP-3 - page 13

    13 BCP-3 Installation and Operation Manual Domestic Hot W ater (DHW) Priority Options: NO and From 1 min to 120 min Default: NO SET SET /Settings>/DHW Prior . DHW Priority: 60m • The DHW Priority , with a value set to other than NO, provides the user with an adjustable DHW priority timer for the domestic hot water call. That is, initiating a D ...

  • Weil-McLain BCP-3 - page 14

    14 BCP-3 Installation and Operation Manual T roubleshooting No Display or LED Lights Check the power to the BCP-3. The BCP-3 requires 120V AC power to the Black wires or 24V AC to the right-most terminals. T urn the power off and back on to restore the display . If unsuccessful, make sure that the control's Display Cover is securely mounted to ...

  • Weil-McLain BCP-3 - page 15

    15 BCP-3 Installation and Operation Manual Boiler1 DHW Indirect Building Heat System Sensor Outdoor Sensor T1 T2 COM COM T3+ T3- EXT+ EXT- P+ P- COM 24VAC } System Sensor } Outdoor Sensor } DHW Call Dry Contact } Enable Dry Contact } Setback Dry Contact Boiler SYS Pump DHW Pump SET SET SYSTEM = 147F TARGET = 150F Y ellow Wires (Output 1) Blue Wires ...

  • Weil-McLain BCP-3 - page 16

    16 BCP-3 Installation and Operation Manual 500 Blaine Street Michigan City , Indiana 46360 219-879-6561 http://www .weil-mclain.com HT #059075-00 A Specifications V oltage Input: . . . . . . . 120 V AC 60 Hz(2 Black wires) /24V AC 60 Hz (24V Ac terminals) (Only One Power Source) Power Consumption: . . . . . . . . . . . . . . . . . . . . . . . . . ...

Fabricant Weil-McLain Catégorie Boiler

Les documents que nous recevons du fabricant de l'appareilWeil-McLain BCP-3 peuvent être divisés en plusieurs groupes. Ceux-ci sont, entre autres:
- dessins techniques Weil-McLain
- manuels d’utilisations BCP-3
- fiches produit Weil-McLain
- dépliants
- ou étiquettes-énergie Weil-McLain BCP-3
Tous sont importants, mais les informations les plus importantes du point de vue de l'utilisation de l'appareil se trouvent dans le manuel d’utilisation Weil-McLain BCP-3.

Un groupe de documents appelé manuels d’utilisation est également divisé en types plus spécifiques, tels que: Manuels d’installation Weil-McLain BCP-3, manuels d’entretien, brefs manuels ou manuels de l’utilisateur Weil-McLain BCP-3. Selon vos besoins, vous devriez chercher le document dont vous avez besoin. Sur notre site, vous pouvez voir le manuel le plus populaire d’utilisation du produit Weil-McLain BCP-3.

Manuels d’utilsiation similaires

Manuel d’utilisation complet de l’appareil Weil-McLain BCP-3, quelle devrait-elle être?
Le manuel d’utilisation, également appelé le mode d’emploi, ou tout simplement le manuel, est un document technique destiné à aider à utiliser Weil-McLain BCP-3 par les utilisateurs. Des manuels sont généralement écrits par un rédacteur technique, mais dans un langage accessible à tous les utilisateurs Weil-McLain BCP-3.

Le manuel d’utilisation complet Weil-McLain, devrait inclure plusieurs éléments de base. Certains d'entre eux sont moins importants, tels que: la couverture / page de titre ou pages d'auteur. Cependant, la partie restante, devrait nous fournir des informations importantes du point de vue de l'utilisateur.

1. Introduction et des conseils sur la façon d'utiliser le manuel Weil-McLain BCP-3 - Au début de chaque manuel, nous devrions trouver des indices sur la façon d'utiliser le document. Il doit contenir des informations sur l'emplacement de la table des matières Weil-McLain BCP-3, FAQ ou des problèmes les plus fréquents - les points qui sont les plus souvent recherchés par les utilisateurs de chaque manuel
2. Table des matières - index de tous les conseils pour lWeil-McLain BCP-3 qui peuvent être trouvés dans le document courant
3. Conseils sur la façon d'utiliser les fonctions de base de l’appareil Weil-McLain BCP-3 - qui devraient nous aider dans les premières étapes lors de l'utilisation Weil-McLain BCP-3
4. Troubleshooting - séquence systématique des activités qui nous aideront à diagnostiquer et ensuite résoudre les principaux problèmes de Weil-McLain BCP-3
5. FAQ - questions fréquemment posées
6. Détails du contact Informations sur l'endroit où chercher le contact avec le fabricant / service Weil-McLain BCP-3 dans un pays donné, si le problème ne peut être résolu par nous-mêmes.

Avez-vous une question à propos de Weil-McLain BCP-3?

Utiliser le formulaire ci-dessous

Si vous n’avez pas résolu votre problème avec Weil-McLain BCP-3, avec l'aide du manuel que vous avez trouvé, posez une question en utilisant le formulaire ci-dessous. Si un utilisateur a eu un problème similaire avec Weil-McLain BCP-3 il est probable qu’il a envie de partager la façon de le résoudre.