    INST ALLA TION AND OPERA TION INSTRUCTIONS BCP-3 Hydronic Multi-Stage Boiler Control Blue (Output 2) White (Output 3) Y ellow (Output 1) Boiler SYS Pump DHW Pump SET SET SYSTEM = 147F TARGET = 150F Output 1 2 Line Alphanumeric Display Displays sensor values and menu settings Output Lights indicate output status Display Section Locking Screws Black ...

  • Weil-McLain BCP-3 - page 2

    2 BCP-3 Installation and Operation Manual thermostat is satisfied. Another, is a Setback input that will switch the heating system to a lower set point determined by the Set Back setting. T ype of Radiation in Building Reset Ratio Offset Radiators (Steel & Cast Iron) 1.00 (O) : 1.00 (S) 0˚F Baseboard (Finned copper tube& Cast Iron) 1.00 ( ...

  • Weil-McLain BCP-3 - page 3

    3 BCP-3 Installation and Operation Manual Mounting the Controller • The BCP-3 is designed to mount on a 1900 (4”x4”) deep electrical box. • If additional room is needed for wiring use the extension skirt provided. • Place the BCP-3 in an indoor convenient location near the unit to be controlled and away from excessive heat or cold. • Pa ...

  • Weil-McLain BCP-3 - page 4

    4 BCP-3 Installation and Operation Manual IMPORT ANT Determining the proper location for the Outdoor Sensor is very important. The BCP-3 will base the heat on the outdoor temperature information it receives from this location. If the sensor is in the sun, or covered with ice, its reading will be different from the actual outdoor temperature. Outdoo ...

  • Weil-McLain BCP-3 - page 5

    5 BCP-3 Installation and Operation Manual Output Mode T able Output Mode Description Output 1 (Y ellow Wires) Output 2 (Blue Wires) Output 3 (White Wires) Notes 1-On/Off+1-Pump One On/Off boiler and a System pump Sys Pump Boiler Not used 1-On/Off+2-Pump One On/Of f boiler , a System pump and a Domestic Hot W ater Pump Sys Pump Boiler DHW Pump 2-On/ ...

  • Weil-McLain BCP-3 - page 6

    6 BCP-3 Installation and Operation Manual T1 T2 COM COM T3+ T3- EXT+ EXT- P+ P- COM 24V AC System Sensor Outdoor Sensor Enable Dry Contact Setback Timer 120 V AC Wiring 1 Lo/Hi Boiler + System Pump System Pump ( Y ellow/Output 1) Boiler Lo (Blue/ Output 2) Boiler Hi ( White/ Output 3) DHW Call Pow er (Black) 120 V AC L N L N T1 T2 COM COM T3+ T3- E ...

  • Weil-McLain BCP-3 - page 7

    7 BCP-3 Installation and Operation Manual Weil McLain V1.00 (c) 2008 BCP-3 Boiler Control Loading Default Values... DISPLAY UNIT: F C SENSOR FAULT: Output On Output Off SETUP COMPLETE! PRESS SET Startup Menu SYSTEM= 68 F TARGET= 150 F ------MAIN------ Set Point 170 F <Out. Reset> <Settings> <Maintenance> <Sys. Startup> <I ...

  • Weil-McLain BCP-3 - page 8

    8 BCP-3 Installation and Operation Manual Button and Navigating Menus The BCP-3 has three buttons. • The SET button function varies. When the Default Screen is displayed, pressing the SET Button views the MENU. When in the Menus and settings, the SET Button accepts the selected entry or setting value. • When in the menus, pressing the Up and Do ...

  • Weil-McLain BCP-3 - page 9

    9 BCP-3 Installation and Operation Manual Outdoor Reset Mode • When Output-On is selected, the BCP-3 will energize all boiler and system relays when the System reads SHORT or OPEN and Outdoor is below Outdoor Cutoff. Thus, all boilers will run on their limits. However , if the Outdoor sensor fails and the Outdoor reads SHORT or OPEN , the BCP-3 w ...

  • Weil-McLain BCP-3 - page 10

    10 BCP-3 Installation and Operation Manual • If required: Adjust the RESET RA TIO in cold weather . If the ambient building temperatures are too cold in cold weather , move the ratio to a higher selection. That is, if 1.00 (O):1.00 (S) was initially selected, change the selection to 1.00 (O):1.25 (S). If the building temperatures are too warm in ...

  • Weil-McLain BCP-3 - page 11

    11 BCP-3 Installation and Operation Manual Minimum T arget (A vailable when Startup Control Mode = Outdoor Reset) Options: From 70 º F/21 ºC to 170 º F/77 ºC Default: 140 º F/60 ºC SET SET /Set Point/<Out. Reset>/Min. Tgt • The Minimum T arget T emperature must be set to the boiler manufacturer ’ s specification. Min Target: 140 F ...

  • Weil-McLain BCP-3 - page 12

    12 BCP-3 Installation and Operation Manual Minimum Runtime Options: 1 to 60 minutes Default: 2 minutes SET SET /<Settings>/<Stage>/Min. Runtime • This is the minimum amount of time any stage will run. • The Minimum Runtime for the lowest firing stage on a boiler starts after the purge cycle. • Initially , set the Min. Runtime to ...

  • Weil-McLain BCP-3 - page 13

    13 BCP-3 Installation and Operation Manual Domestic Hot W ater (DHW) Priority Options: NO and From 1 min to 120 min Default: NO SET SET /Settings>/DHW Prior . DHW Priority: 60m • The DHW Priority , with a value set to other than NO, provides the user with an adjustable DHW priority timer for the domestic hot water call. That is, initiating a D ...

  • Weil-McLain BCP-3 - page 14

    14 BCP-3 Installation and Operation Manual T roubleshooting No Display or LED Lights Check the power to the BCP-3. The BCP-3 requires 120V AC power to the Black wires or 24V AC to the right-most terminals. T urn the power off and back on to restore the display . If unsuccessful, make sure that the control's Display Cover is securely mounted to ...

  • Weil-McLain BCP-3 - page 15

    15 BCP-3 Installation and Operation Manual Boiler1 DHW Indirect Building Heat System Sensor Outdoor Sensor T1 T2 COM COM T3+ T3- EXT+ EXT- P+ P- COM 24VAC } System Sensor } Outdoor Sensor } DHW Call Dry Contact } Enable Dry Contact } Setback Dry Contact Boiler SYS Pump DHW Pump SET SET SYSTEM = 147F TARGET = 150F Y ellow Wires (Output 1) Blue Wires ...

  • Weil-McLain BCP-3 - page 16

    16 BCP-3 Installation and Operation Manual 500 Blaine Street Michigan City , Indiana 46360 219-879-6561 http://www .weil-mclain.com HT #059075-00 A Specifications V oltage Input: . . . . . . . 120 V AC 60 Hz(2 Black wires) /24V AC 60 Hz (24V Ac terminals) (Only One Power Source) Power Consumption: . . . . . . . . . . . . . . . . . . . . . . . . . ...

Manufacturer Weil-McLain Category Boiler

Documents that we receive from a manufacturer of a Weil-McLain BCP-3 can be divided into several groups. They are, among others:
- Weil-McLain technical drawings
- BCP-3 manuals
- Weil-McLain product data sheets
- information booklets
- or energy labels Weil-McLain BCP-3
All of them are important, but the most important information from the point of view of use of the device are in the user manual Weil-McLain BCP-3.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals Weil-McLain BCP-3, service manual, brief instructions and user manuals Weil-McLain BCP-3. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product Weil-McLain BCP-3.

A complete manual for the device Weil-McLain BCP-3, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use Weil-McLain BCP-3 by users. Manuals are usually written by a technical writer, but in a language understandable to all users of Weil-McLain BCP-3.

A complete Weil-McLain manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual Weil-McLain BCP-3 - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the Weil-McLain BCP-3, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the Weil-McLain BCP-3, that we can find in the current document
3. Tips how to use the basic functions of the device Weil-McLain BCP-3 - which should help us in our first steps of using Weil-McLain BCP-3
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with Weil-McLain BCP-3
5. FAQ - Frequently Asked Questions
6. Contact detailsInformation about where to look for contact to the manufacturer/service of Weil-McLain BCP-3 in a specific country, if it was not possible to solve the problem on our own.

Do you have a question concerning Weil-McLain BCP-3?

Use the form below

If you did not solve your problem by using a manual Weil-McLain BCP-3, ask a question using the form below. If a user had a similar problem with Weil-McLain BCP-3 it is likely that he will want to share the way to solve it.

Copy the text from the picture

Comments (0)