Manual de instrucciones B&B Electronics Command Response Protocol HVD100A3

31 de páginas 0.55 mb
Descargar

Pasar a la página of 31

Summary
  • B&B Electronics Command Response Protocol HVD100A3 - page 1

    HDV100A3 Command & Response Manual-1306cr Cover Page B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 Model: HVD100A3 HDV100A3 Command Response Protocol Documentation Number: HDV100A3-4407CR International Headquarters B&B Electronics Mfg. Co. Inc. 707 Dayton Road -- P.O. Box 10 ...

  • B&B Electronics Command Response Protocol HVD100A3 - page 2

    ...

  • B&B Electronics Command Response Protocol HVD100A3 - page 3

    HDV100A3 Command & Response Manual-1306cr Table of Contents i B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 Table of Contents INTRODUCTION........................................................................................ 1 Intelligent Mode Command Protocol ................ ...

  • B&B Electronics Command Response Protocol HVD100A3 - page 4

    ii HDV100A3 Command & Response Manual-1306cr B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 WARNING! This Model HDV100A3 Converter Module allows you to connect to active J1708 / J1939 networks. It is possible that your transmissions through this converter module could cause malfu ...

  • B&B Electronics Command Response Protocol HVD100A3 - page 5

    HDV100A3 Command & Response Manual-1306cr 1 B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 Introduction The HDV100A3 adapter has two modes of operation: J1708 Intelligent and J1939 Intelligent mode In Intelligen t mode the HDV100A3 works with a comm and protocol to control di ffe ...

  • B&B Electronics Command Response Protocol HVD100A3 - page 6

    2 HDV100A3 Command & Response Manual-1306cr B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 Intelligent Mode Command Protocol The HDV100A3 uses a simple protocol to comm unicate to vehicle bus. The protocol is divided i nto four parts: Start Of Frame (SOF) Control Field (shown i n ...

  • B&B Electronics Command Response Protocol HVD100A3 - page 7

    HDV100A3 Command & Response Manual-1306cr 3 B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 Formatting the Control Bytes The 2 nd byte is “Num ber of Control Byt es” to follow and always precedes the control field. The third byte is the ID byte. This byte tells the hardware wh ...

  • B&B Electronics Command Response Protocol HVD100A3 - page 8

    4 HDV100A3 Command & Response Manual-1306cr B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 Detailed Description of General Function Codes Command Acknowledgement All comma nds sent to the device will be acknowledged. If no error occurs an ACK will be sent with the ID byte that ac ...

  • B&B Electronics Command Response Protocol HVD100A3 - page 9

    HDV100A3 Command & Response Manual-1306cr 5 B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 RS-232 Baud Rate Setup To set the baud rate for the RS-232 port, set a general comm and code of 08. Set the function code to 01. Then set 3 control bytes as follows. Function Start of Frame ...

  • B&B Electronics Command Response Protocol HVD100A3 - page 10

    6 HDV100A3 Command & Response Manual-1306cr B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 Bits 1 and 0 set the word l ength Bit 0 Bit 1 Word Length 0 0 5 0 1 6 1 0 7 1 1 8 (default) Default value. The HDV100A3 should always be set to 8-bit word lengt h. ...

  • B&B Electronics Command Response Protocol HVD100A3 - page 11

    HDV100A3 Command & Response Manual-1306cr 7 B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 Setting Baud 1, Baud 2 Baud Rate Setup Table Baud Rate Decimal Divisor Hex Divisor MSB (Baud 2) Hex Divisor LSB (Baud 1) 9600 48 $00 (default) $30 (default) 14400 32 $00 $20 19200 24 $00 $1 ...

  • B&B Electronics Command Response Protocol HVD100A3 - page 12

    8 HDV100A3 Command & Response Manual-1306cr B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 Baud Rate Example To set the PC baud rate to 57,600 baud, N,8,1, form at the message as follows. Byte Number Byte Value Hex Byte Function 1 01 Start of fram e 2 05 Number of cont rol bytes ...

  • B&B Electronics Command Response Protocol HVD100A3 - page 13

    HDV100A3 Command & Response Manual-1306cr 9 B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 Time Stamp Information The HDV100A3 supports a four-byte rolling time stamp with a resolution of 1.5 mi croseconds per bit. The maxim um ti me stam p value is 6,442.45 seconds before roll o ...

  • B&B Electronics Command Response Protocol HVD100A3 - page 14

    10 HDV100A3 Command & Response Manual-1306cr B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 Byte Number Byte Value Function 1 01 Start of fram e 2 02 Number of control bytes 3 08 ID byte 08 = int ernal comm and 4 20 Function code 20 = stop ti me stam ping 5 00 Number data bytes 6 ...

  • B&B Electronics Command Response Protocol HVD100A3 - page 15

    HDV100A3 Command & Response Manual-1306cr 11 B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 Master Reset Command The master reset com mand all ows the HDV100A3 to be reset from the PC. Sending this comm and resets the HDV100A3 to the defaul t start-up state. You will lose all set ...

  • B&B Electronics Command Response Protocol HVD100A3 - page 16

    12 HDV100A3 Command & Response Manual-1306cr B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 J1708 Commands Receiving Data from the J1708 Bus After the HDV100A3 is set into its Intelligent mode of operation and the RS-232 data rate is confi gured, you are now ready to comm unicate ...

  • B&B Electronics Command Response Protocol HVD100A3 - page 17

    HDV100A3 Command & Response Manual-1306cr 13 B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 Byte number Byte value (hex) Byte Function 1 01 Start of frame 2 02 The number of control by tes 3 01 ID byte 01= J1708 4 10 Function code 10 hex stop receive 5 00 Number of data bytes (00 ...

  • B&B Electronics Command Response Protocol HVD100A3 - page 18

    14 HDV100A3 Command & Response Manual-1306cr B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 Transmitting Data to the J1708 Bus The HDV100A3 supports standard J1708 comm ands of up to 21 bytes. Additional ly the HDV100A3 can send m essages up to 100 bytes to the J1708 bus. It is t ...

  • B&B Electronics Command Response Protocol HVD100A3 - page 19

    HDV100A3 Command & Response Manual-1306cr 15 B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 After sending a transmit me ssage to the HDV100A3 you will get the confirmation message if the checksum is correct. A transmit complete message is sent to the PC after the device successfu ...

  • B&B Electronics Command Response Protocol HVD100A3 - page 20

    16 HDV100A3 Command & Response Manual-1306cr B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 J1708 Message Filter The J1708 message filter will operate on 4 different MID’s. Only m essages with the same MID as set in the filter will be sent to the PC. The filters will be OR’ed ...

  • B&B Electronics Command Response Protocol HVD100A3 - page 21

    HDV100A3 Command & Response Manual-1306cr 17 B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 Broadcast Message The HDV100A3 supports one broadcast message. Once confi gured by the host application, this message will be sent repeatedly by the HDV100A3 at a programme d time interval ...

  • B&B Electronics Command Response Protocol HVD100A3 - page 22

    18 HDV100A3 Command & Response Manual-1306cr B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 To stop broadcast transmi ssion it is not necessary t o send the whole message. The message below will stop broadcast transmission. Byte Number Byte Value Function 1 01 Start of fram e 2 0 ...

  • B&B Electronics Command Response Protocol HVD100A3 - page 23

    HDV100A3 Command & Response Manual-1306cr 19 B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 J1939 Commands The J1939 protocol is sim ilar to the J1708 prot ocol. The message starts wi th Start of Frame byt e 01. The number of control bytes will be 06. The contro l code for J1939 ...

  • B&B Electronics Command Response Protocol HVD100A3 - page 24

    20 HDV100A3 Command & Response Manual-1306cr B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 wise to set the receiver off when not in use. Sending the Start Receive clears the mask. This renders the filter function useless. Start Receive on J1939 Bus Byte Number Byte Value Functio ...

  • B&B Electronics Command Response Protocol HVD100A3 - page 25

    HDV100A3 Command & Response Manual-1306cr 21 B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 Data messages received from the HDV 100A3 operating in the J1939 mode, is formatted as follows: Control Field Data Field Start of Frame # of Control bytes Contr Byte Time S tamp 4 Bytes # ...

  • B&B Electronics Command Response Protocol HVD100A3 - page 26

    22 HDV100A3 Command & Response Manual-1306cr B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 A message received from the HDV will be formatted as follows: <01><05><02><06><C7><CC><ED><0D><67><80><20><00><08 ...

  • B&B Electronics Command Response Protocol HVD100A3 - page 27

    HDV100A3 Command & Response Manual-1306cr 23 B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 Transmit Data to J1939 Bus Byte Number Byte Value Function 1 01 Start of frame 2 06 Control byte s 3 02 ID byt e 1 = J1708 message 4 02 Functi on byte 02 transm it message 5 XX MSB of arbi ...

  • B&B Electronics Command Response Protocol HVD100A3 - page 28

    24 HDV100A3 Command & Response Manual-1306cr B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 The mask can be used to look at a group of m essages: To set the mask to filter on the J1939 priority field, the m ask would be loaded with: (01, 06, 02, 04, E0, 00, 00, 00, 00, ED) To set ...

  • B&B Electronics Command Response Protocol HVD100A3 - page 29

    HDV100A3 Command & Response Manual-1306cr 25 B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 2. Set the “Mask” to the desired patt ern (01, 06, 02, 04, XX, XX, XX, XX, 00, CS). 3. Set a filter (1 to 4) to the match value (01, 06, 0 2 , YY, XX, XX, XX, XX, 00, CS). Be sure that ...

  • B&B Electronics Command Response Protocol HVD100A3 - page 30

    26 HDV100A3 Command & Response Manual-1306cr B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 J1939 Header Worksheet This worksheet will aid in filling ou t/decoding the J1939 arbitration field. Bit Number J1939 Function CAN Fram e Entry Hex Value 29 28 27 Priority Bits 26 Reserved ...

  • B&B Electronics Command Response Protocol HVD100A3 - page 31

    HDV100A3 Command & Response Manual-1306cr 27 B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 Error Codes Error Code Format: Byte Number Byte Value Functio n 1 01 Start of frame 2 03 Number of control by tes 3 05 Function code error = 05 4 XY ID of message that caused error 5 0Z Er ...

Fabricante B&B Electronics Categoría Network Card

Los documentos del dispositivo B&B Electronics Command Response Protocol HVD100A3 que obtenemos del fabricante se pueden dividir en varios grupos. Entre ellos están::
- dibujos técnicos B&B Electronics
- manuales de instrucciones Command Response Protocol HVD100A3
- hojas de producto B&B Electronics
- folletos informativos
- o etiquetas energéticas B&B Electronics Command Response Protocol HVD100A3
Todos son importantes, pero lo más importante desde el punto de vista del usuario de un dispositivo lo encontraremos en el manual de instrucciones B&B Electronics Command Response Protocol HVD100A3.

Un conjunto de documentos determinado como manual de instrucciones se divide también en tipos más detallados, tales como: instrucciones de montaje B&B Electronics Command Response Protocol HVD100A3, instrucciones de servicio, instrucciones cortas o instrucciones de usuario B&B Electronics Command Response Protocol HVD100A3. Dependiendo de la situación debes buscar el documento que necesitas. En nuestra página puedes consultar el manual de instrucciones más popular del producto B&B Electronics Command Response Protocol HVD100A3.

Manuales de instrucciones parecidos

El manual de instrucciones del dispositivo B&B Electronics Command Response Protocol HVD100A3, ¿cómo debería ser?
El manual de instrucciones, también determinado como el manual de usuario o simplemente instrucciones, es un documento técnico que tiene como objetivo ayudar a los usuarios a utilizar B&B Electronics Command Response Protocol HVD100A3. Las instrucciones normalmente las realiza un escritor técnico pero en un lenguaje comprensible para todos los usuarios de B&B Electronics Command Response Protocol HVD100A3.

El manual de instrucciones completo de B&B Electronics debe contener unos elementos básicos. Una parte de ellos es menos importante, como por ejemplo: la portada / la página principal o las páginas de autor. Sin embargo, lo demás debe facilitarnos la información más importante desde el punto de vista del usuario.

1. Introducción y pistas sobre cómo orientarse con el manual B&B Electronics Command Response Protocol HVD100A3 - Al principio de cada manual se deben encontrar las indicaciones acerca de la manera de usar un manual de instrucciones. Debe contener información sobre dónde encontrar el índice B&B Electronics Command Response Protocol HVD100A3, preguntas frecuentes o problemas más comunes – son los apartados más buscados por los usuarios de cada manual de instrucciones.
2. Índice - listados de todos los consejos acerca de B&B Electronics Command Response Protocol HVD100A3 que encontraremos en el documento
3. Consejos de uso de las funciones básicas del dispositivo B&B Electronics Command Response Protocol HVD100A3 - que deben facilitarnos los primeros pasos durante el uso de B&B Electronics Command Response Protocol HVD100A3
4. Troubleshooting - una secuencia sistematizada de acciones que nos ayudará a diagnosticar los problemas más importantes con B&B Electronics Command Response Protocol HVD100A3
5. FAQ - las preguntas frecuentes
6. Datos de contacto Información acerca de cómo encontrar los datos de contacto del fabricante / servicio de B&B Electronics Command Response Protocol HVD100A3 en cada país si no somos capaces de solucionar el problema por nuestra cuenta.

¿Tienes una pregunta acerca de B&B Electronics Command Response Protocol HVD100A3?

Utiliza el formulario que se encuentra abajo

Si con la ayuda del manual de instrucciones encontrado no has podido solucionar tu problema con B&B Electronics Command Response Protocol HVD100A3, haz una pregunta utilizando el formulario que se encuentra abajo. Si alguno de los usuarios ha tenido un problema parecido con B&B Electronics Command Response Protocol HVD100A3 probablemente compartirá una forma de solucionarlo.

Copia el texto de la imagen

Comentarios (0)