Manuel d’utilisation B&B Electronics Command Response Protocol HVD100A3

31 pages 0.55 mb
Télécharger

Aller à la page of 31

Summary
  • B&B Electronics Command Response Protocol HVD100A3 - page 1

    HDV100A3 Command & Response Manual-1306cr Cover Page B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 Model: HVD100A3 HDV100A3 Command Response Protocol Documentation Number: HDV100A3-4407CR International Headquarters B&B Electronics Mfg. Co. Inc. 707 Dayton Road -- P.O. Box 10 ...

  • B&B Electronics Command Response Protocol HVD100A3 - page 2

    ...

  • B&B Electronics Command Response Protocol HVD100A3 - page 3

    HDV100A3 Command & Response Manual-1306cr Table of Contents i B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 Table of Contents INTRODUCTION........................................................................................ 1 Intelligent Mode Command Protocol ................ ...

  • B&B Electronics Command Response Protocol HVD100A3 - page 4

    ii HDV100A3 Command & Response Manual-1306cr B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 WARNING! This Model HDV100A3 Converter Module allows you to connect to active J1708 / J1939 networks. It is possible that your transmissions through this converter module could cause malfu ...

  • B&B Electronics Command Response Protocol HVD100A3 - page 5

    HDV100A3 Command & Response Manual-1306cr 1 B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 Introduction The HDV100A3 adapter has two modes of operation: J1708 Intelligent and J1939 Intelligent mode In Intelligen t mode the HDV100A3 works with a comm and protocol to control di ffe ...

  • B&B Electronics Command Response Protocol HVD100A3 - page 6

    2 HDV100A3 Command & Response Manual-1306cr B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 Intelligent Mode Command Protocol The HDV100A3 uses a simple protocol to comm unicate to vehicle bus. The protocol is divided i nto four parts: Start Of Frame (SOF) Control Field (shown i n ...

  • B&B Electronics Command Response Protocol HVD100A3 - page 7

    HDV100A3 Command & Response Manual-1306cr 3 B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 Formatting the Control Bytes The 2 nd byte is “Num ber of Control Byt es” to follow and always precedes the control field. The third byte is the ID byte. This byte tells the hardware wh ...

  • B&B Electronics Command Response Protocol HVD100A3 - page 8

    4 HDV100A3 Command & Response Manual-1306cr B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 Detailed Description of General Function Codes Command Acknowledgement All comma nds sent to the device will be acknowledged. If no error occurs an ACK will be sent with the ID byte that ac ...

  • B&B Electronics Command Response Protocol HVD100A3 - page 9

    HDV100A3 Command & Response Manual-1306cr 5 B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 RS-232 Baud Rate Setup To set the baud rate for the RS-232 port, set a general comm and code of 08. Set the function code to 01. Then set 3 control bytes as follows. Function Start of Frame ...

  • B&B Electronics Command Response Protocol HVD100A3 - page 10

    6 HDV100A3 Command & Response Manual-1306cr B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 Bits 1 and 0 set the word l ength Bit 0 Bit 1 Word Length 0 0 5 0 1 6 1 0 7 1 1 8 (default) Default value. The HDV100A3 should always be set to 8-bit word lengt h. ...

  • B&B Electronics Command Response Protocol HVD100A3 - page 11

    HDV100A3 Command & Response Manual-1306cr 7 B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 Setting Baud 1, Baud 2 Baud Rate Setup Table Baud Rate Decimal Divisor Hex Divisor MSB (Baud 2) Hex Divisor LSB (Baud 1) 9600 48 $00 (default) $30 (default) 14400 32 $00 $20 19200 24 $00 $1 ...

  • B&B Electronics Command Response Protocol HVD100A3 - page 12

    8 HDV100A3 Command & Response Manual-1306cr B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 Baud Rate Example To set the PC baud rate to 57,600 baud, N,8,1, form at the message as follows. Byte Number Byte Value Hex Byte Function 1 01 Start of fram e 2 05 Number of cont rol bytes ...

  • B&B Electronics Command Response Protocol HVD100A3 - page 13

    HDV100A3 Command & Response Manual-1306cr 9 B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 Time Stamp Information The HDV100A3 supports a four-byte rolling time stamp with a resolution of 1.5 mi croseconds per bit. The maxim um ti me stam p value is 6,442.45 seconds before roll o ...

  • B&B Electronics Command Response Protocol HVD100A3 - page 14

    10 HDV100A3 Command & Response Manual-1306cr B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 Byte Number Byte Value Function 1 01 Start of fram e 2 02 Number of control bytes 3 08 ID byte 08 = int ernal comm and 4 20 Function code 20 = stop ti me stam ping 5 00 Number data bytes 6 ...

  • B&B Electronics Command Response Protocol HVD100A3 - page 15

    HDV100A3 Command & Response Manual-1306cr 11 B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 Master Reset Command The master reset com mand all ows the HDV100A3 to be reset from the PC. Sending this comm and resets the HDV100A3 to the defaul t start-up state. You will lose all set ...

  • B&B Electronics Command Response Protocol HVD100A3 - page 16

    12 HDV100A3 Command & Response Manual-1306cr B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 J1708 Commands Receiving Data from the J1708 Bus After the HDV100A3 is set into its Intelligent mode of operation and the RS-232 data rate is confi gured, you are now ready to comm unicate ...

  • B&B Electronics Command Response Protocol HVD100A3 - page 17

    HDV100A3 Command & Response Manual-1306cr 13 B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 Byte number Byte value (hex) Byte Function 1 01 Start of frame 2 02 The number of control by tes 3 01 ID byte 01= J1708 4 10 Function code 10 hex stop receive 5 00 Number of data bytes (00 ...

  • B&B Electronics Command Response Protocol HVD100A3 - page 18

    14 HDV100A3 Command & Response Manual-1306cr B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 Transmitting Data to the J1708 Bus The HDV100A3 supports standard J1708 comm ands of up to 21 bytes. Additional ly the HDV100A3 can send m essages up to 100 bytes to the J1708 bus. It is t ...

  • B&B Electronics Command Response Protocol HVD100A3 - page 19

    HDV100A3 Command & Response Manual-1306cr 15 B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 After sending a transmit me ssage to the HDV100A3 you will get the confirmation message if the checksum is correct. A transmit complete message is sent to the PC after the device successfu ...

  • B&B Electronics Command Response Protocol HVD100A3 - page 20

    16 HDV100A3 Command & Response Manual-1306cr B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 J1708 Message Filter The J1708 message filter will operate on 4 different MID’s. Only m essages with the same MID as set in the filter will be sent to the PC. The filters will be OR’ed ...

  • B&B Electronics Command Response Protocol HVD100A3 - page 21

    HDV100A3 Command & Response Manual-1306cr 17 B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 Broadcast Message The HDV100A3 supports one broadcast message. Once confi gured by the host application, this message will be sent repeatedly by the HDV100A3 at a programme d time interval ...

  • B&B Electronics Command Response Protocol HVD100A3 - page 22

    18 HDV100A3 Command & Response Manual-1306cr B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 To stop broadcast transmi ssion it is not necessary t o send the whole message. The message below will stop broadcast transmission. Byte Number Byte Value Function 1 01 Start of fram e 2 0 ...

  • B&B Electronics Command Response Protocol HVD100A3 - page 23

    HDV100A3 Command & Response Manual-1306cr 19 B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 J1939 Commands The J1939 protocol is sim ilar to the J1708 prot ocol. The message starts wi th Start of Frame byt e 01. The number of control bytes will be 06. The contro l code for J1939 ...

  • B&B Electronics Command Response Protocol HVD100A3 - page 24

    20 HDV100A3 Command & Response Manual-1306cr B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 wise to set the receiver off when not in use. Sending the Start Receive clears the mask. This renders the filter function useless. Start Receive on J1939 Bus Byte Number Byte Value Functio ...

  • B&B Electronics Command Response Protocol HVD100A3 - page 25

    HDV100A3 Command & Response Manual-1306cr 21 B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 Data messages received from the HDV 100A3 operating in the J1939 mode, is formatted as follows: Control Field Data Field Start of Frame # of Control bytes Contr Byte Time S tamp 4 Bytes # ...

  • B&B Electronics Command Response Protocol HVD100A3 - page 26

    22 HDV100A3 Command & Response Manual-1306cr B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 A message received from the HDV will be formatted as follows: <01><05><02><06><C7><CC><ED><0D><67><80><20><00><08 ...

  • B&B Electronics Command Response Protocol HVD100A3 - page 27

    HDV100A3 Command & Response Manual-1306cr 23 B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 Transmit Data to J1939 Bus Byte Number Byte Value Function 1 01 Start of frame 2 06 Control byte s 3 02 ID byt e 1 = J1708 message 4 02 Functi on byte 02 transm it message 5 XX MSB of arbi ...

  • B&B Electronics Command Response Protocol HVD100A3 - page 28

    24 HDV100A3 Command & Response Manual-1306cr B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 The mask can be used to look at a group of m essages: To set the mask to filter on the J1939 priority field, the m ask would be loaded with: (01, 06, 02, 04, E0, 00, 00, 00, 00, ED) To set ...

  • B&B Electronics Command Response Protocol HVD100A3 - page 29

    HDV100A3 Command & Response Manual-1306cr 25 B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 2. Set the “Mask” to the desired patt ern (01, 06, 02, 04, XX, XX, XX, XX, 00, CS). 3. Set a filter (1 to 4) to the match value (01, 06, 0 2 , YY, XX, XX, XX, XX, 00, CS). Be sure that ...

  • B&B Electronics Command Response Protocol HVD100A3 - page 30

    26 HDV100A3 Command & Response Manual-1306cr B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 J1939 Header Worksheet This worksheet will aid in filling ou t/decoding the J1939 arbitration field. Bit Number J1939 Function CAN Fram e Entry Hex Value 29 28 27 Priority Bits 26 Reserved ...

  • B&B Electronics Command Response Protocol HVD100A3 - page 31

    HDV100A3 Command & Response Manual-1306cr 27 B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 Error Codes Error Code Format: Byte Number Byte Value Functio n 1 01 Start of frame 2 03 Number of control by tes 3 05 Function code error = 05 4 XY ID of message that caused error 5 0Z Er ...

Fabricant B&B Electronics Catégorie Network Card

Les documents que nous recevons du fabricant de l'appareilB&B Electronics Command Response Protocol HVD100A3 peuvent être divisés en plusieurs groupes. Ceux-ci sont, entre autres:
- dessins techniques B&B Electronics
- manuels d’utilisations Command Response Protocol HVD100A3
- fiches produit B&B Electronics
- dépliants
- ou étiquettes-énergie B&B Electronics Command Response Protocol HVD100A3
Tous sont importants, mais les informations les plus importantes du point de vue de l'utilisation de l'appareil se trouvent dans le manuel d’utilisation B&B Electronics Command Response Protocol HVD100A3.

Un groupe de documents appelé manuels d’utilisation est également divisé en types plus spécifiques, tels que: Manuels d’installation B&B Electronics Command Response Protocol HVD100A3, manuels d’entretien, brefs manuels ou manuels de l’utilisateur B&B Electronics Command Response Protocol HVD100A3. Selon vos besoins, vous devriez chercher le document dont vous avez besoin. Sur notre site, vous pouvez voir le manuel le plus populaire d’utilisation du produit B&B Electronics Command Response Protocol HVD100A3.

Manuels d’utilsiation similaires

Manuel d’utilisation complet de l’appareil B&B Electronics Command Response Protocol HVD100A3, quelle devrait-elle être?
Le manuel d’utilisation, également appelé le mode d’emploi, ou tout simplement le manuel, est un document technique destiné à aider à utiliser B&B Electronics Command Response Protocol HVD100A3 par les utilisateurs. Des manuels sont généralement écrits par un rédacteur technique, mais dans un langage accessible à tous les utilisateurs B&B Electronics Command Response Protocol HVD100A3.

Le manuel d’utilisation complet B&B Electronics, devrait inclure plusieurs éléments de base. Certains d'entre eux sont moins importants, tels que: la couverture / page de titre ou pages d'auteur. Cependant, la partie restante, devrait nous fournir des informations importantes du point de vue de l'utilisateur.

1. Introduction et des conseils sur la façon d'utiliser le manuel B&B Electronics Command Response Protocol HVD100A3 - Au début de chaque manuel, nous devrions trouver des indices sur la façon d'utiliser le document. Il doit contenir des informations sur l'emplacement de la table des matières B&B Electronics Command Response Protocol HVD100A3, FAQ ou des problèmes les plus fréquents - les points qui sont les plus souvent recherchés par les utilisateurs de chaque manuel
2. Table des matières - index de tous les conseils pour lB&B Electronics Command Response Protocol HVD100A3 qui peuvent être trouvés dans le document courant
3. Conseils sur la façon d'utiliser les fonctions de base de l’appareil B&B Electronics Command Response Protocol HVD100A3 - qui devraient nous aider dans les premières étapes lors de l'utilisation B&B Electronics Command Response Protocol HVD100A3
4. Troubleshooting - séquence systématique des activités qui nous aideront à diagnostiquer et ensuite résoudre les principaux problèmes de B&B Electronics Command Response Protocol HVD100A3
5. FAQ - questions fréquemment posées
6. Détails du contact Informations sur l'endroit où chercher le contact avec le fabricant / service B&B Electronics Command Response Protocol HVD100A3 dans un pays donné, si le problème ne peut être résolu par nous-mêmes.

Avez-vous une question à propos de B&B Electronics Command Response Protocol HVD100A3?

Utiliser le formulaire ci-dessous

Si vous n’avez pas résolu votre problème avec B&B Electronics Command Response Protocol HVD100A3, avec l'aide du manuel que vous avez trouvé, posez une question en utilisant le formulaire ci-dessous. Si un utilisateur a eu un problème similaire avec B&B Electronics Command Response Protocol HVD100A3 il est probable qu’il a envie de partager la façon de le résoudre.

Réécrire le texte de l'image

Commentaires (0)