    HDV100A3 Command & Response Manual-1306cr Cover Page B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 Model: HVD100A3 HDV100A3 Command Response Protocol Documentation Number: HDV100A3-4407CR International Headquarters B&B Electronics Mfg. Co. Inc. 707 Dayton Road -- P.O. Box 10 ...

  • B&B Electronics Command Response Protocol HVD100A3 - page 2

    ...

  • B&B Electronics Command Response Protocol HVD100A3 - page 3

    HDV100A3 Command & Response Manual-1306cr Table of Contents i B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 Table of Contents INTRODUCTION........................................................................................ 1 Intelligent Mode Command Protocol ................ ...

  • B&B Electronics Command Response Protocol HVD100A3 - page 4

    ii HDV100A3 Command & Response Manual-1306cr B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 WARNING! This Model HDV100A3 Converter Module allows you to connect to active J1708 / J1939 networks. It is possible that your transmissions through this converter module could cause malfu ...

  • B&B Electronics Command Response Protocol HVD100A3 - page 5

    HDV100A3 Command & Response Manual-1306cr 1 B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 Introduction The HDV100A3 adapter has two modes of operation: J1708 Intelligent and J1939 Intelligent mode In Intelligen t mode the HDV100A3 works with a comm and protocol to control di ffe ...

  • B&B Electronics Command Response Protocol HVD100A3 - page 6

    2 HDV100A3 Command & Response Manual-1306cr B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 Intelligent Mode Command Protocol The HDV100A3 uses a simple protocol to comm unicate to vehicle bus. The protocol is divided i nto four parts: Start Of Frame (SOF) Control Field (shown i n ...

  • B&B Electronics Command Response Protocol HVD100A3 - page 7

    HDV100A3 Command & Response Manual-1306cr 3 B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 Formatting the Control Bytes The 2 nd byte is “Num ber of Control Byt es” to follow and always precedes the control field. The third byte is the ID byte. This byte tells the hardware wh ...

  • B&B Electronics Command Response Protocol HVD100A3 - page 8

    4 HDV100A3 Command & Response Manual-1306cr B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 Detailed Description of General Function Codes Command Acknowledgement All comma nds sent to the device will be acknowledged. If no error occurs an ACK will be sent with the ID byte that ac ...

  • B&B Electronics Command Response Protocol HVD100A3 - page 9

    HDV100A3 Command & Response Manual-1306cr 5 B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 RS-232 Baud Rate Setup To set the baud rate for the RS-232 port, set a general comm and code of 08. Set the function code to 01. Then set 3 control bytes as follows. Function Start of Frame ...

  • B&B Electronics Command Response Protocol HVD100A3 - page 10

    6 HDV100A3 Command & Response Manual-1306cr B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 Bits 1 and 0 set the word l ength Bit 0 Bit 1 Word Length 0 0 5 0 1 6 1 0 7 1 1 8 (default) Default value. The HDV100A3 should always be set to 8-bit word lengt h. ...

  • B&B Electronics Command Response Protocol HVD100A3 - page 11

    HDV100A3 Command & Response Manual-1306cr 7 B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 Setting Baud 1, Baud 2 Baud Rate Setup Table Baud Rate Decimal Divisor Hex Divisor MSB (Baud 2) Hex Divisor LSB (Baud 1) 9600 48 $00 (default) $30 (default) 14400 32 $00 $20 19200 24 $00 $1 ...

  • B&B Electronics Command Response Protocol HVD100A3 - page 12

    8 HDV100A3 Command & Response Manual-1306cr B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 Baud Rate Example To set the PC baud rate to 57,600 baud, N,8,1, form at the message as follows. Byte Number Byte Value Hex Byte Function 1 01 Start of fram e 2 05 Number of cont rol bytes ...

  • B&B Electronics Command Response Protocol HVD100A3 - page 13

    HDV100A3 Command & Response Manual-1306cr 9 B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 Time Stamp Information The HDV100A3 supports a four-byte rolling time stamp with a resolution of 1.5 mi croseconds per bit. The maxim um ti me stam p value is 6,442.45 seconds before roll o ...

  • B&B Electronics Command Response Protocol HVD100A3 - page 14

    10 HDV100A3 Command & Response Manual-1306cr B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 Byte Number Byte Value Function 1 01 Start of fram e 2 02 Number of control bytes 3 08 ID byte 08 = int ernal comm and 4 20 Function code 20 = stop ti me stam ping 5 00 Number data bytes 6 ...

  • B&B Electronics Command Response Protocol HVD100A3 - page 15

    HDV100A3 Command & Response Manual-1306cr 11 B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 Master Reset Command The master reset com mand all ows the HDV100A3 to be reset from the PC. Sending this comm and resets the HDV100A3 to the defaul t start-up state. You will lose all set ...

  • B&B Electronics Command Response Protocol HVD100A3 - page 16

    12 HDV100A3 Command & Response Manual-1306cr B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 J1708 Commands Receiving Data from the J1708 Bus After the HDV100A3 is set into its Intelligent mode of operation and the RS-232 data rate is confi gured, you are now ready to comm unicate ...

  • B&B Electronics Command Response Protocol HVD100A3 - page 17

    HDV100A3 Command & Response Manual-1306cr 13 B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 Byte number Byte value (hex) Byte Function 1 01 Start of frame 2 02 The number of control by tes 3 01 ID byte 01= J1708 4 10 Function code 10 hex stop receive 5 00 Number of data bytes (00 ...

  • B&B Electronics Command Response Protocol HVD100A3 - page 18

    14 HDV100A3 Command & Response Manual-1306cr B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 Transmitting Data to the J1708 Bus The HDV100A3 supports standard J1708 comm ands of up to 21 bytes. Additional ly the HDV100A3 can send m essages up to 100 bytes to the J1708 bus. It is t ...

  • B&B Electronics Command Response Protocol HVD100A3 - page 19

    HDV100A3 Command & Response Manual-1306cr 15 B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 After sending a transmit me ssage to the HDV100A3 you will get the confirmation message if the checksum is correct. A transmit complete message is sent to the PC after the device successfu ...

  • B&B Electronics Command Response Protocol HVD100A3 - page 20

    16 HDV100A3 Command & Response Manual-1306cr B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 J1708 Message Filter The J1708 message filter will operate on 4 different MID’s. Only m essages with the same MID as set in the filter will be sent to the PC. The filters will be OR’ed ...

  • B&B Electronics Command Response Protocol HVD100A3 - page 21

    HDV100A3 Command & Response Manual-1306cr 17 B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 Broadcast Message The HDV100A3 supports one broadcast message. Once confi gured by the host application, this message will be sent repeatedly by the HDV100A3 at a programme d time interval ...

  • B&B Electronics Command Response Protocol HVD100A3 - page 22

    18 HDV100A3 Command & Response Manual-1306cr B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 To stop broadcast transmi ssion it is not necessary t o send the whole message. The message below will stop broadcast transmission. Byte Number Byte Value Function 1 01 Start of fram e 2 0 ...

  • B&B Electronics Command Response Protocol HVD100A3 - page 23

    HDV100A3 Command & Response Manual-1306cr 19 B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 J1939 Commands The J1939 protocol is sim ilar to the J1708 prot ocol. The message starts wi th Start of Frame byt e 01. The number of control bytes will be 06. The contro l code for J1939 ...

  • B&B Electronics Command Response Protocol HVD100A3 - page 24

    20 HDV100A3 Command & Response Manual-1306cr B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 wise to set the receiver off when not in use. Sending the Start Receive clears the mask. This renders the filter function useless. Start Receive on J1939 Bus Byte Number Byte Value Functio ...

  • B&B Electronics Command Response Protocol HVD100A3 - page 25

    HDV100A3 Command & Response Manual-1306cr 21 B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 Data messages received from the HDV 100A3 operating in the J1939 mode, is formatted as follows: Control Field Data Field Start of Frame # of Control bytes Contr Byte Time S tamp 4 Bytes # ...

  • B&B Electronics Command Response Protocol HVD100A3 - page 26

    22 HDV100A3 Command & Response Manual-1306cr B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 A message received from the HDV will be formatted as follows: <01><05><02><06><C7><CC><ED><0D><67><80><20><00><08 ...

  • B&B Electronics Command Response Protocol HVD100A3 - page 27

    HDV100A3 Command & Response Manual-1306cr 23 B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 Transmit Data to J1939 Bus Byte Number Byte Value Function 1 01 Start of frame 2 06 Control byte s 3 02 ID byt e 1 = J1708 message 4 02 Functi on byte 02 transm it message 5 XX MSB of arbi ...

  • B&B Electronics Command Response Protocol HVD100A3 - page 28

    24 HDV100A3 Command & Response Manual-1306cr B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 The mask can be used to look at a group of m essages: To set the mask to filter on the J1939 priority field, the m ask would be loaded with: (01, 06, 02, 04, E0, 00, 00, 00, 00, ED) To set ...

  • B&B Electronics Command Response Protocol HVD100A3 - page 29

    HDV100A3 Command & Response Manual-1306cr 25 B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 2. Set the “Mask” to the desired patt ern (01, 06, 02, 04, XX, XX, XX, XX, 00, CS). 3. Set a filter (1 to 4) to the match value (01, 06, 0 2 , YY, XX, XX, XX, XX, 00, CS). Be sure that ...

  • B&B Electronics Command Response Protocol HVD100A3 - page 30

    26 HDV100A3 Command & Response Manual-1306cr B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 J1939 Header Worksheet This worksheet will aid in filling ou t/decoding the J1939 arbitration field. Bit Number J1939 Function CAN Fram e Entry Hex Value 29 28 27 Priority Bits 26 Reserved ...

  • B&B Electronics Command Response Protocol HVD100A3 - page 31

    HDV100A3 Command & Response Manual-1306cr 27 B&B Electronics -- 707 Dayton Rd. -- PO Box 1040 -- Ottawa, IL 61350 PH (815) 433-5100 -- FAX (815) 433-5104 Error Codes Error Code Format: Byte Number Byte Value Functio n 1 01 Start of frame 2 03 Number of control by tes 3 05 Function code error = 05 4 XY ID of message that caused error 5 0Z Er ...

Manufacturer B&B Electronics Category Network Card

Documents that we receive from a manufacturer of a B&B Electronics Command Response Protocol HVD100A3 can be divided into several groups. They are, among others:
- B&B Electronics technical drawings
- Command Response Protocol HVD100A3 manuals
- B&B Electronics product data sheets
- information booklets
- or energy labels B&B Electronics Command Response Protocol HVD100A3
All of them are important, but the most important information from the point of view of use of the device are in the user manual B&B Electronics Command Response Protocol HVD100A3.

A group of documents referred to as user manuals is also divided into more specific types, such as: Installation manuals B&B Electronics Command Response Protocol HVD100A3, service manual, brief instructions and user manuals B&B Electronics Command Response Protocol HVD100A3. Depending on your needs, you should look for the document you need. In our website you can view the most popular manual of the product B&B Electronics Command Response Protocol HVD100A3.

A complete manual for the device B&B Electronics Command Response Protocol HVD100A3, how should it look like?
A manual, also referred to as a user manual, or simply "instructions" is a technical document designed to assist in the use B&B Electronics Command Response Protocol HVD100A3 by users. Manuals are usually written by a technical writer, but in a language understandable to all users of B&B Electronics Command Response Protocol HVD100A3.

A complete B&B Electronics manual, should contain several basic components. Some of them are less important, such as: cover / title page or copyright page. However, the remaining part should provide us with information that is important from the point of view of the user.

1. Preface and tips on how to use the manual B&B Electronics Command Response Protocol HVD100A3 - At the beginning of each manual we should find clues about how to use the guidelines. It should include information about the location of the Contents of the B&B Electronics Command Response Protocol HVD100A3, FAQ or common problems, i.e. places that are most often searched by users in each manual
2. Contents - index of all tips concerning the B&B Electronics Command Response Protocol HVD100A3, that we can find in the current document
3. Tips how to use the basic functions of the device B&B Electronics Command Response Protocol HVD100A3 - which should help us in our first steps of using B&B Electronics Command Response Protocol HVD100A3
4. Troubleshooting - systematic sequence of activities that will help us diagnose and subsequently solve the most important problems with B&B Electronics Command Response Protocol HVD100A3
5. FAQ - Frequently Asked Questions
6. Contact detailsInformation about where to look for contact to the manufacturer/service of B&B Electronics Command Response Protocol HVD100A3 in a specific country, if it was not possible to solve the problem on our own.

Do you have a question concerning B&B Electronics Command Response Protocol HVD100A3?

Use the form below

If you did not solve your problem by using a manual B&B Electronics Command Response Protocol HVD100A3, ask a question using the form below. If a user had a similar problem with B&B Electronics Command Response Protocol HVD100A3 it is likely that he will want to share the way to solve it.

Copy the text from the picture

Comments (0)