    www.rosemount.com ¢00825-0100-4716/¤ Quick Installation Guid e 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiV ariable Sta r t End Step 1: Mount the T ransmitter Step 2: T ransmitter Installation Step 3: Sof tware Installation Step 4: Connect the Wiring and Power Up ( HART or Fieldbus) Step 5: Configure the T ransmitter ( HART or Field ...

  • Emerson 00825-0100-4716 - page 2

    Quick Installation Guide 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiV aria ble 2 © 2009 Rosemo unt Inc. All rights re served. All marks property o f owner. Rosemount and the Rosemount logotype are registered trad emarks of Rosemount Inc. Rosemount Inc. 8200 Market B oulevard Chanhassen, M N USA 55317 T (US) (800) 999 -9 30 7, F (952) ...

  • Emerson 00825-0100-4716 - page 3

    Quick Installation Guid e 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiV ariable 3 T RANS MITTER E XPLODED V IEW Housing O-ring Cover Housing Locking Screw RTD Connector Process Adapter O-ring Electronics Board Nameplate Module O-ring Sensor Module Drain/V ent Valve Flange Adapter O-ring Optional Flange Adapters Bolts Coplanar Flange Ce ...

  • Emerson 00825-0100-4716 - page 4

    Quick Installation Guide 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiV aria ble 4 S TE P 1: M OUNT THE T RANSMITTER Figure 1. Using a Mounting Bracke t Liquid Flow Application s 1. Place taps to the side of the line. 2. Mount beside or below the taps. 3. Mount the transmitter so that the drain/vent valves are oriented upwar d. Gas Flow ...

  • Emerson 00825-0100-4716 - page 5

    Quick Installation Guid e 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiV ariable 5 S TE P 2: T RANSMITT ER I NS TALLATIO N Consider Housin g Rotation T o improve field access or to better view the optional LCD displa y: 1. Loosen the housing rotation set screw . 2. Rotate the housing clockwise to the desired position – up to 180° fro ...

  • Emerson 00825-0100-4716 - page 6

    Quick Installation Guide 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiV aria ble 6 S TE P 2 CONTI NUED ... 3. Set the Failure Mode Alarm (HART devices), which is located on the front of the electronics board inside the electronics housing cover . T he Alar m Jumper position determines if the output is driven high or lo w when a failur e ...

  • Emerson 00825-0100-4716 - page 7

    Quick Installation Guid e 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiV ariable 7 S TE P 2 CONTI NUED ... • Installing a Shielded 3095 RTD Cable (See Figure 4) Note: Shielded cable is intended for use in a conduit. a. Fully engage the black cable connector to the 3 095 R TD Connector. b. T i ghten the cable adapter until metal cont a ...

  • Emerson 00825-0100-4716 - page 8

    Quick Installation Guide 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiV aria ble 8 S TE P 2 CONTI NUED ... Bolting Considerations If the transmitter installation requires assembly of the process flanges , manifolds, or flange adapters, follow these assembly guidelines to ensure a tight seal for optimal performance characteristics of the ...

  • Emerson 00825-0100-4716 - page 9

    Quick Installation Guid e 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiV ariable 9 S TE P 2 CONTI NUED ... Figure 7. T orque values for the flange and flan ge adapter bolts O-rings with Flange Adapters W ARNING Whenever the flanges or adapters are removed, vi su ally inspect the o-rings. Replace them if there are any signs of damage, su ...

  • Emerson 00825-0100-4716 - page 10

    Quick Installation Guide 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiV aria ble 10 S TE P 3: S OFTWARE I NSTALLATION The 3095 Engineering Assistant (EA) for HA RT and 3095 Engineering Assistant (EA) for FOUNDA TION Fieldbus software programs can be installed on the same computer . The applications cannot be open simultaneously . 3095 E ...

  • Emerson 00825-0100-4716 - page 11

    Quick Installation Guid e 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiV ariable 11 S TE P 3 CONTI NUED ... Installing the HART Modem After installing the 3095 Engineering Assist ant, the HAR T mo dem configuration window automatically appears when the 3095 Engineering Assistant is opened. If this window is canceled, the HART modem may ...

  • Emerson 00825-0100-4716 - page 12

    Quick Installation Guide 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiV aria ble 12 S TE P 4: C ON NECT W IRING AND P OWER U P (HART) S TE P 4: C ON NECT W IRING AND P OWER U P (HART) Use the following steps to wire the transmitter: 1. Remove the housing cover on the side marked FIELD TERMINALS. 2. Connect the signal leads to the termin ...

  • Emerson 00825-0100-4716 - page 13

    Quick Installation Guid e 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiV ariable 13 S TE P 4: C ON NECT W IRING AND P OWER U P (F IELDBUS ) Use the following steps to wire the transmitter: 1. Remove the housing cover labeled “Field T erm inals.” T erminals are no t polarity sensitive. 2. Connect the signal leads to the te rminals la ...

  • Emerson 00825-0100-4716 - page 14

    Quick Installation Guide 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiV aria ble 14 S TE P 5: C ON FIGURE THE T RANSMITTER (HART) Setting the Lo op to Manu al Set the process application loop to manual when preparing to send or request data that would disrupt the loop or change the output of the tra nsmitter . A prompt will appear remin ...

  • Emerson 00825-0100-4716 - page 15

    Quick Installation Guid e 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiV ariable 15 DP Sens T rim 1, 2, 2, 1, 1 DP Snsr Range 1, 3, 5, 1 DP URV 5 DP units 1, 3, 2, 1 Date 1, 3, 4, 4 Descri ptor 1, 3, 4, 2 Diff p res damp 1, 4, 2, 4 Diff pres 1, 1, 1 Diff pres 2 Fld dev rev 1, 3, 4, 9, 2 Flo rate 1, 1, 4, 5 Flow Rate S pecial Units 1, 4, ...

  • Emerson 00825-0100-4716 - page 16

    Quick Installation Guide 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiV aria ble 16 S TE P 5: C ON FIGURE THE T RANSMITTER (F IELDBUS ) Each F OUNDATION fieldbus host or configuration tool has a different way of displaying and performing configuratio ns. Some use Device Descriptions (DD) or DD methods for configuration and to display da ...

  • Emerson 00825-0100-4716 - page 17

    Quick Installation Guid e 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiV ariable 17 S TE P 6: T RIM THE T RANSMITTE R NOTE T ransmitte rs are shipped from Emerson Process Management fully calibrated and configured for the application when C2 Option is ordered. Without C2 Option, configuration will be by the factory default (span = upper ...

  • Emerson 00825-0100-4716 - page 18

    Quick Installation Guide 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiV aria ble 18 P RODUCT C E RTIFICATIONS Rosemount 3095 with HART Approved Manufacturi ng Locations Rosemount Inc. — Chanhassen, Minnesota USA Emerson Process Management GmbH & Co. — Wessling, Germany Emerson Process Management Asia Pa cific Private Limited — ...

  • Emerson 00825-0100-4716 - page 19

    Quick Installation Guid e 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiV ariable 19 Canadian St andards A ssociation (C SA) C Explosion Proof for Class I, Divi sion 1, Groups B, C, and D. Dust-Ignition Proof for Class II/Class III, Division 1, Groups E, F , and G . CSA enclosure T ype 4X suitable for indoor and outdoor hazardous locatio ...

  • Emerson 00825-0100-4716 - page 20

    Quick Installation Guide 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiV aria ble 20 G A TEX Type n Certificate Number: BAS98A TEX3360X II 3 G Ex nL IIC T5 (T amb = –45 °C to 40 °C) Ex nL IIC T4 (T amb = –45 °C to 70 °C) U i = 55V The apparatus is designed for connect ion to a remote temperature sensor such as a resistance temper ...

  • Emerson 00825-0100-4716 - page 21

    Quick Installation Guid e 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiV ariable 21 The capacitance and either the Induct ance or the Induct ance to Resistance Ratio ( L/R) of the load connected to the 4-pin connecto r must not exceed the following values: NOTE 1. The external circuit contains no comb ined lumped inductance and capacita ...

  • Emerson 00825-0100-4716 - page 22

    Quick Installation Guide 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiV aria ble 22 China (NEPSI) Certifications 2 China Intrinsic Safety Ex ia IIC T4 Special conditions for safe use (x): 1. 3095 Series transmitter with temperature sensor h ave not been certified. 2. The temperature of process medium should be less than 121 °C. 3. The ...

  • Emerson 00825-0100-4716 - page 23

    Quick Installation Guid e 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiV ariable 23 1 1. When inst allation, use and maintenance transmitter , observe the f ollowing st andards GB3836.13-1997 “Electrical apparatus for explosive gas atmospheres Part 13: Repair and overhaul for apparatus us ed in explosive gas atmospheres” GB3836.15-2 ...

  • Emerson 00825-0100-4716 - page 24

    Quick Installation Guide 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiV aria ble 24 Combinations of Certifications S tainless steel certification t ag is provided when optional appr oval is specified. Once a device labeled with multiple approval types is installed, it shou ld not be r einst alled using any other approval types. Permanen ...

  • Emerson 00825-0100-4716 - page 25

    Quick Installation Guid e 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiV ariable 25 Rosemount 3095 Fieldbus Hazardou s Lo ca ti ons Certifications North American Cert ifications FM Approvals A Explosion Proof for Class I, Divi sion 1, Groups B, C, and D. Dust-Ignition Proof for Class II/Class III, Division 1, Groups E, F , and G . Enclo ...

  • Emerson 00825-0100-4716 - page 26

    Quick Installation Guide 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiV aria ble 26 Special conditions for safe use (x): V ersions of the apparatus fitted with the transient protected terminals are not capable of withstanding the 500 volts insulation test required by Clause 6.4.12 of EN 50020:2002. This must be taken into account when i ...

  • Emerson 00825-0100-4716 - page 27

    Quick Installation Guid e 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiV ariable 27 P A TEX Dust Certificate Number: KEMA02A TEX2321 II 1 D T90°C (-50°C  T amb  80°C) Vmax = 55 Vdc Imax = 23 mA IP66 11 8 0 IECEx Certifications (Fieldbus) 4/Y IECEx Intrinsic Safety Certificate Number: IECEx BAS05.0023X Ex ia IIC T4 (-45°C  T ...

  • Emerson 00825-0100-4716 - page 28

    Quick Installation Guide 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiV aria ble 28 7 IECEx Flameproof Certificate Number: IECEx KEM 06.0018 Zone 0/1 Ex d IIC T6 (-20°C  T a  65°C) Zone 0/1 Ex d IIC T5 (-20°C  T a  80°C) V max = 55 Vdc I max = 23 mAdc 8 IECEx Dust Certificate Number: IECEx KEM 06.0018 Ex tD A22 T90°C IP ...

  • Emerson 00825-0100-4716 - page 29

    Quick Installation Guid e 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiV ariable 29 ...

  • Emerson 00825-0100-4716 - page 30

    Quick Installation Guide 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiV aria ble 30 ...

  • Emerson 00825-0100-4716 - page 31

    Quick Installation Guid e 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiV ariable 31 ...

  • Emerson 00825-0100-4716 - page 32

    Quick Installation Guide 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiV aria ble 32 ...

Fabbricante Emerson Categoria Marine Instruments

I documenti che otteniamo dal fabbricante del dispositivoEmerson 00825-0100-4716 possono essere suddivisi in diversi gruppi. Questi sono tra gli altri:
- disegni tecnici Emerson
- manuali per l’uso 00825-0100-4716
- schede prodotto Emerson
- opuscoli
- o etichette energetiche Emerson 00825-0100-4716
Tutti sono importanti, ma le informazioni più importanti dal punto di vista di utilizzo del dispositivo possono essere trovate nel manuale per l’uso Emerson 00825-0100-4716.

Un gruppo di documenti denominato manuali per l’uso, è anche suddiviso in tipi più specifici, come: Manuali di installazione Emerson 00825-0100-4716, manuali di manutenzione, brevi manuali o manuali utente Emerson 00825-0100-4716. A seconda delle esigenze, si dovrebbe cercare il documento necessario. Nel nostro sito web, puoi visualizzare il manuale più popolare per l'uso del prodotto Emerson 00825-0100-4716.

Manuali per l’uso simili

Manuale completo del dispositivo Emerson 00825-0100-4716, come deve essere?
Il manuale per l’uso, denominato anche istruzioni per l’uso, o semplicemente il manuale è un documento tecnico progettato per aiutare ad utilizzare Emerson 00825-0100-4716 dagli utenti. I manuali sono di solito scritti da uno scrittore tecnico, ma in un linguaggio accessibile a tutti gli utenti Emerson 00825-0100-4716.

Il manuale per l’uso completo Emerson, dovrebbe includere vari elementi di base. Alcuni di loro sono meno importanti, come ad esempio: copertina / pagina del titolo o pagina di autore. Tuttavia, la parte rimanente, dovrebbe fornire informazioni importanti dal punto di vista dell'utente.

1. Introduzione e la guida su come utilizzare il manuale Emerson 00825-0100-4716 - All'inizio di ogni manuale, dovremmo trovare indizi su come utilizzare il documento. Dovrebbe contenere informazioni sulla posizione dell’indice Emerson 00825-0100-4716, FAQ o i problemi più comuni : i punti che sono più spesso cercati dagli utenti di ogni manuale
2. Indice - elenco di tutti i suggerimenti per Emerson 00825-0100-4716 che possono essere trovati nel documento corrente
3. Suggerimenti su come utilizzare le funzioni di base del dispositivo Emerson 00825-0100-4716 - che ci dovrebbe aiutare nei primi passi durante l'uso Emerson 00825-0100-4716
4. Troubleshooting - sequenza sistematica delle attività che vi aiuterà a diagnosticare e, successivamente, risolvere i problemi più importanti del Emerson 00825-0100-4716
5. FAQ - domande più frequenti
6. Dettagli di contatto Informazioni su dove cercare il contatto con il fabbricante / servizio Emerson 00825-0100-4716 in un dato paese, se il problema non può essere risolto da noi stessi.

Hai una domanda su Emerson 00825-0100-4716?

Utilizza il modulo sottostante

Se non hai risolto il problema con Emerson 00825-0100-4716 con l'aiuto del manuale che hai trovato, fai una domanda utilizzando il modulo sottostante. Se un utente ha avuto un problema simile con Emerson 00825-0100-4716 è probabile che voglia condividere il modo di risolverlo.

Riscrivi il testo dall’immagine

Commenti (0)