    www.rosemount.com ¢00825-0100-4716/¤ Quick Installation Guid e 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiV ariable Sta r t End Step 1: Mount the T ransmitter Step 2: T ransmitter Installation Step 3: Sof tware Installation Step 4: Connect the Wiring and Power Up ( HART or Fieldbus) Step 5: Configure the T ransmitter ( HART or Field ...

  • Emerson 00825-0100-4716 - page 2

    Quick Installation Guide 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiV aria ble 2 © 2009 Rosemo unt Inc. All rights re served. All marks property o f owner. Rosemount and the Rosemount logotype are registered trad emarks of Rosemount Inc. Rosemount Inc. 8200 Market B oulevard Chanhassen, M N USA 55317 T (US) (800) 999 -9 30 7, F (952) ...

  • Emerson 00825-0100-4716 - page 3

    Quick Installation Guid e 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiV ariable 3 T RANS MITTER E XPLODED V IEW Housing O-ring Cover Housing Locking Screw RTD Connector Process Adapter O-ring Electronics Board Nameplate Module O-ring Sensor Module Drain/V ent Valve Flange Adapter O-ring Optional Flange Adapters Bolts Coplanar Flange Ce ...

  • Emerson 00825-0100-4716 - page 4

    Quick Installation Guide 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiV aria ble 4 S TE P 1: M OUNT THE T RANSMITTER Figure 1. Using a Mounting Bracke t Liquid Flow Application s 1. Place taps to the side of the line. 2. Mount beside or below the taps. 3. Mount the transmitter so that the drain/vent valves are oriented upwar d. Gas Flow ...

  • Emerson 00825-0100-4716 - page 5

    Quick Installation Guid e 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiV ariable 5 S TE P 2: T RANSMITT ER I NS TALLATIO N Consider Housin g Rotation T o improve field access or to better view the optional LCD displa y: 1. Loosen the housing rotation set screw . 2. Rotate the housing clockwise to the desired position – up to 180° fro ...

  • Emerson 00825-0100-4716 - page 6

    Quick Installation Guide 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiV aria ble 6 S TE P 2 CONTI NUED ... 3. Set the Failure Mode Alarm (HART devices), which is located on the front of the electronics board inside the electronics housing cover . T he Alar m Jumper position determines if the output is driven high or lo w when a failur e ...

  • Emerson 00825-0100-4716 - page 7

    Quick Installation Guid e 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiV ariable 7 S TE P 2 CONTI NUED ... • Installing a Shielded 3095 RTD Cable (See Figure 4) Note: Shielded cable is intended for use in a conduit. a. Fully engage the black cable connector to the 3 095 R TD Connector. b. T i ghten the cable adapter until metal cont a ...

  • Emerson 00825-0100-4716 - page 8

    Quick Installation Guide 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiV aria ble 8 S TE P 2 CONTI NUED ... Bolting Considerations If the transmitter installation requires assembly of the process flanges , manifolds, or flange adapters, follow these assembly guidelines to ensure a tight seal for optimal performance characteristics of the ...

  • Emerson 00825-0100-4716 - page 9

    Quick Installation Guid e 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiV ariable 9 S TE P 2 CONTI NUED ... Figure 7. T orque values for the flange and flan ge adapter bolts O-rings with Flange Adapters W ARNING Whenever the flanges or adapters are removed, vi su ally inspect the o-rings. Replace them if there are any signs of damage, su ...

  • Emerson 00825-0100-4716 - page 10

    Quick Installation Guide 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiV aria ble 10 S TE P 3: S OFTWARE I NSTALLATION The 3095 Engineering Assistant (EA) for HA RT and 3095 Engineering Assistant (EA) for FOUNDA TION Fieldbus software programs can be installed on the same computer . The applications cannot be open simultaneously . 3095 E ...

  • Emerson 00825-0100-4716 - page 11

    Quick Installation Guid e 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiV ariable 11 S TE P 3 CONTI NUED ... Installing the HART Modem After installing the 3095 Engineering Assist ant, the HAR T mo dem configuration window automatically appears when the 3095 Engineering Assistant is opened. If this window is canceled, the HART modem may ...

  • Emerson 00825-0100-4716 - page 12

    Quick Installation Guide 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiV aria ble 12 S TE P 4: C ON NECT W IRING AND P OWER U P (HART) S TE P 4: C ON NECT W IRING AND P OWER U P (HART) Use the following steps to wire the transmitter: 1. Remove the housing cover on the side marked FIELD TERMINALS. 2. Connect the signal leads to the termin ...

  • Emerson 00825-0100-4716 - page 13

    Quick Installation Guid e 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiV ariable 13 S TE P 4: C ON NECT W IRING AND P OWER U P (F IELDBUS ) Use the following steps to wire the transmitter: 1. Remove the housing cover labeled “Field T erm inals.” T erminals are no t polarity sensitive. 2. Connect the signal leads to the te rminals la ...

  • Emerson 00825-0100-4716 - page 14

    Quick Installation Guide 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiV aria ble 14 S TE P 5: C ON FIGURE THE T RANSMITTER (HART) Setting the Lo op to Manu al Set the process application loop to manual when preparing to send or request data that would disrupt the loop or change the output of the tra nsmitter . A prompt will appear remin ...

  • Emerson 00825-0100-4716 - page 15

    Quick Installation Guid e 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiV ariable 15 DP Sens T rim 1, 2, 2, 1, 1 DP Snsr Range 1, 3, 5, 1 DP URV 5 DP units 1, 3, 2, 1 Date 1, 3, 4, 4 Descri ptor 1, 3, 4, 2 Diff p res damp 1, 4, 2, 4 Diff pres 1, 1, 1 Diff pres 2 Fld dev rev 1, 3, 4, 9, 2 Flo rate 1, 1, 4, 5 Flow Rate S pecial Units 1, 4, ...

  • Emerson 00825-0100-4716 - page 16

    Quick Installation Guide 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiV aria ble 16 S TE P 5: C ON FIGURE THE T RANSMITTER (F IELDBUS ) Each F OUNDATION fieldbus host or configuration tool has a different way of displaying and performing configuratio ns. Some use Device Descriptions (DD) or DD methods for configuration and to display da ...

  • Emerson 00825-0100-4716 - page 17

    Quick Installation Guid e 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiV ariable 17 S TE P 6: T RIM THE T RANSMITTE R NOTE T ransmitte rs are shipped from Emerson Process Management fully calibrated and configured for the application when C2 Option is ordered. Without C2 Option, configuration will be by the factory default (span = upper ...

  • Emerson 00825-0100-4716 - page 18

    Quick Installation Guide 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiV aria ble 18 P RODUCT C E RTIFICATIONS Rosemount 3095 with HART Approved Manufacturi ng Locations Rosemount Inc. — Chanhassen, Minnesota USA Emerson Process Management GmbH & Co. — Wessling, Germany Emerson Process Management Asia Pa cific Private Limited — ...

  • Emerson 00825-0100-4716 - page 19

    Quick Installation Guid e 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiV ariable 19 Canadian St andards A ssociation (C SA) C Explosion Proof for Class I, Divi sion 1, Groups B, C, and D. Dust-Ignition Proof for Class II/Class III, Division 1, Groups E, F , and G . CSA enclosure T ype 4X suitable for indoor and outdoor hazardous locatio ...

  • Emerson 00825-0100-4716 - page 20

    Quick Installation Guide 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiV aria ble 20 G A TEX Type n Certificate Number: BAS98A TEX3360X II 3 G Ex nL IIC T5 (T amb = –45 °C to 40 °C) Ex nL IIC T4 (T amb = –45 °C to 70 °C) U i = 55V The apparatus is designed for connect ion to a remote temperature sensor such as a resistance temper ...

  • Emerson 00825-0100-4716 - page 21

    Quick Installation Guid e 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiV ariable 21 The capacitance and either the Induct ance or the Induct ance to Resistance Ratio ( L/R) of the load connected to the 4-pin connecto r must not exceed the following values: NOTE 1. The external circuit contains no comb ined lumped inductance and capacita ...

  • Emerson 00825-0100-4716 - page 22

    Quick Installation Guide 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiV aria ble 22 China (NEPSI) Certifications 2 China Intrinsic Safety Ex ia IIC T4 Special conditions for safe use (x): 1. 3095 Series transmitter with temperature sensor h ave not been certified. 2. The temperature of process medium should be less than 121 °C. 3. The ...

  • Emerson 00825-0100-4716 - page 23

    Quick Installation Guid e 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiV ariable 23 1 1. When inst allation, use and maintenance transmitter , observe the f ollowing st andards GB3836.13-1997 “Electrical apparatus for explosive gas atmospheres Part 13: Repair and overhaul for apparatus us ed in explosive gas atmospheres” GB3836.15-2 ...

  • Emerson 00825-0100-4716 - page 24

    Quick Installation Guide 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiV aria ble 24 Combinations of Certifications S tainless steel certification t ag is provided when optional appr oval is specified. Once a device labeled with multiple approval types is installed, it shou ld not be r einst alled using any other approval types. Permanen ...

  • Emerson 00825-0100-4716 - page 25

    Quick Installation Guid e 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiV ariable 25 Rosemount 3095 Fieldbus Hazardou s Lo ca ti ons Certifications North American Cert ifications FM Approvals A Explosion Proof for Class I, Divi sion 1, Groups B, C, and D. Dust-Ignition Proof for Class II/Class III, Division 1, Groups E, F , and G . Enclo ...

  • Emerson 00825-0100-4716 - page 26

    Quick Installation Guide 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiV aria ble 26 Special conditions for safe use (x): V ersions of the apparatus fitted with the transient protected terminals are not capable of withstanding the 500 volts insulation test required by Clause 6.4.12 of EN 50020:2002. This must be taken into account when i ...

  • Emerson 00825-0100-4716 - page 27

    Quick Installation Guid e 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiV ariable 27 P A TEX Dust Certificate Number: KEMA02A TEX2321 II 1 D T90°C (-50°C  T amb  80°C) Vmax = 55 Vdc Imax = 23 mA IP66 11 8 0 IECEx Certifications (Fieldbus) 4/Y IECEx Intrinsic Safety Certificate Number: IECEx BAS05.0023X Ex ia IIC T4 (-45°C  T ...

  • Emerson 00825-0100-4716 - page 28

    Quick Installation Guide 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiV aria ble 28 7 IECEx Flameproof Certificate Number: IECEx KEM 06.0018 Zone 0/1 Ex d IIC T6 (-20°C  T a  65°C) Zone 0/1 Ex d IIC T5 (-20°C  T a  80°C) V max = 55 Vdc I max = 23 mAdc 8 IECEx Dust Certificate Number: IECEx KEM 06.0018 Ex tD A22 T90°C IP ...

  • Emerson 00825-0100-4716 - page 29

    Quick Installation Guid e 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiV ariable 29 ...

  • Emerson 00825-0100-4716 - page 30

    Quick Installation Guide 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiV aria ble 30 ...

  • Emerson 00825-0100-4716 - page 31

    Quick Installation Guid e 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiV ariable 31 ...

  • Emerson 00825-0100-4716 - page 32

    Quick Installation Guide 00825-0100-4716, Rev DA October 2009 Rosemount 3095 MultiV aria ble 32 ...

Производитель Emerson Категория Marine Instruments

Документы, которые мы получаем от производителя устройства Emerson 00825-0100-4716 мы можем разделить на несколько групп. Это в частности:
- технические чертежи Emerson
- инструкции обслуживания 00825-0100-4716
- паспорта изделия Emerson
- информационные брошюры
- энергетические этикетки Emerson 00825-0100-4716
Все из них важны, однако самую важную информацию с точки зрения пользователя мы найдем в инструкции обслуживания Emerson 00825-0100-4716.

Группа документов, определяемая как инструкции обслуживания, делится также на более подробные типы, такие как: Инструкции монтажа Emerson 00825-0100-4716, инструкции обслуживания, короткие инструкции или инструкции пользователя Emerson 00825-0100-4716. В зависимости от потребностей, Вам необходимо поискать требуемый документ. На нашем сайте Вы можете просмотреть самую популярную инструкцию использования изделия Emerson 00825-0100-4716.

Похожие инструкции обслуживания

Полная инструкция обслуживания устройства Emerson 00825-0100-4716, как должна выглядеть?
Инструкция обслуживания, определяемая также как пособие пользователя, или просто "руководство" - это технический документ, цель которого заключается в использовании Emerson 00825-0100-4716 пользователями. Инструкции пишет, как правило технический писатель, языком, доступным для всех пользователей Emerson 00825-0100-4716.

Полная инструкция обслуживания Emerson, должна заключать несколько основных элементов. Часть из них менее важная, как например: обложка / титульный лист или авторские страницы. Однако остальная часть, должна дать нам важную с точки зрения пользователя информацию.

1. Вступление и рекомендации, как пользоваться инструкцией Emerson 00825-0100-4716 - В начале каждой инструкции, необходимо найти указания, как пользоваться данным пособием. Здесь должна находится информация, касающаяся местонахождения содержания Emerson 00825-0100-4716, FAQ и самых распространенных проблем - то есть мест, которые чаще всего ищут пользователи в каждой инструкции обслуживания
2. Содержание - индекс всех советов, касающихся Emerson 00825-0100-4716, которое найдем в данном документе
3. Советы по использованию основных функций устройства Emerson 00825-0100-4716 - которые должны облегчить нам первые шаги во время использования Emerson 00825-0100-4716
4. Troubleshooting - систематизированный ряд действия, который поможет нам диагностировать а в дальнейшем очередность решения важнейших проблем Emerson 00825-0100-4716
5. FAQ - чаще всего задаваемые вопросы
6. Контактные данные Информация о том, где искать контактные данные производителя / сервисного центра Emerson 00825-0100-4716 в данной стране, если самостоятельно не получится решить проблему.

У вас вопрос, касающийся Emerson 00825-0100-4716?

Воспользуйтесь формуляром, находящимся ниже

Если с помощью найденной инструкции Вы не решили свою проблему с Emerson 00825-0100-4716, задайте вопрос, заполнив следующий формуляр. Если у какого то из пользователей была похожая проблема с Emerson 00825-0100-4716 со всей вероятностью он захочет поделиться методом ее решения.

Перепишите текст с картинки

Комментарии (0)