    www.rosemount.com ¢00825-0100-4801J¤ HART ® Quick Installation Guide 00825-0100-4801, Rev HA February 2008 Rosemount 3051S Rosemount 3051S Series Pressure T ransmitter with HART ® Protocol Rosemount 3051SF Series Flowmeter T ransmitter with HART ® Protocol © 2008 Rosemount Inc. All rights reserved. All marks property of owne r . Rosemount and ...

  • Emerson 3051S - page 2

    Quick Installation Guide 00825-0100-4801, Rev HA February 2008 Rosemount 3051S 2 Rosemount Inc. 8200 Market Boulevard Chanhassen, MN USA 55317 T (US) (800) 999-9307 T (Intnl) (952) 906-8888 F (952) 949-7001 Emerson Proces s Management GmbH & Co. OHG Argelsrieder Feld 3 82234 Wessling Germany T 49 (8153) 9390, F49 (8153) 939172 Emerson Proces s ...

  • Emerson 3051S - page 3

    Quick Installation Guide 00825-0100-4801, Rev HA February 2008 Rosemount 3051S 3 W ARNING Explosions could result in death or serious injury: Installation of this transmitter in an explosive environment must be in accordance with the appropriate local, national, and international standards, codes, and practices. Please review the approvals section ...

  • Emerson 3051S - page 4

    Quick Installation Guide 00825-0100-4801, Rev HA February 2008 Rosemount 3051S 4 S TEP 1: M OUNT THE T RANSMITTER Liquid Flow Applications 1. Place taps to the side of the line. 2. Mount beside or below the taps. 3. Mount the transmitter so that the drain/vent valves are oriented upward. Gas Flow Applications 1. Place taps in the top or side of the ...

  • Emerson 3051S - page 5

    Quick Installation Guide 00825-0100-4801, Rev HA February 2008 Rosemount 3051S 5 S TEP 1 CONTINUED ... Panel Mount Pipe Mount Coplanar ™ Flange T raditional Flange In-line Housings PlantWeb ™ Junction Box Remote Mount Display 4801_QIG_RevHA.fm Page 5 Tues day, Februa ry 26, 2008 12:17 PM ...

  • Emerson 3051S - page 6

    Quick Installation Guide 00825-0100-4801, Rev HA February 2008 Rosemount 3051S 6 S TEP 2: C ONSIDER H OUSING R OT ATION S TEP 3: S ET S WITCHES AND J UMPERS If alarm and security adjustment option is not installed, the transmitter will operate normally with the default alarm condition alarm high and the security off . T o improve field access to wi ...

  • Emerson 3051S - page 7

    Quick Installation Guide 00825-0100-4801, Rev HA February 2008 Rosemount 3051S 7 S TEP 4: C ONNECT W IRING AND P OWER U P Use the following steps to wire the transmitter: 1. Remove the housing cover labeled “Field T erminals.” 2. Connect the positive lead to the “+” terminal, and the negative lead to the “–” terminal. NOTE Do not conn ...

  • Emerson 3051S - page 8

    Quick Installation Guide 00825-0100-4801, Rev HA February 2008 Rosemount 3051S 8 S TEP 4 CONTINUED ... Remote Display Wiring and Power Up The Remote Mount Display and Interf ace system consists of a local transmitter and a remote mount LCD display assembly . The local 3051S transmitter assembly includes a Junction Box housing with a three position ...

  • Emerson 3051S - page 9

    Quick Installation Guide 00825-0100-4801, Rev HA February 2008 Rosemount 3051S 9 S TEP 4 CONTINUED ... Intrinsic Safety Consideration: The transmitter assembly with remote display has been approved with Belden 3084A DeviceNet cable. Alternate cable may be used as long as the transmitter with remote display and cable is configured according to the i ...

  • Emerson 3051S - page 10

    Quick Installation Guide 00825-0100-4801, Rev HA February 2008 Rosemount 3051S 10 S TEP 4 CONTINUED ... NOTE Wire colors provided on page 9 are per Belden 3084A DeviceNet cable. Wire color may vary depending on cable selected. Belden 3084A DeviceNet cable includes a ground shield. This shield must be connected to earth ground at either the SuperMod ...

  • Emerson 3051S - page 11

    Quick Installation Guide 00825-0100-4801, Rev HA February 2008 Rosemount 3051S 11 S TEP 4 CONTINUED ... 2. Place coupling nut over quick connect and wrench tighten to a maximum of 300 in-lb. (34 N-m). 3. T ighten the set screw using a 3 / 32 -in hex wrench. 4. Install Cordset/ Field Wireable Co nnectors onto the Quick Connect. Do not over tighten. ...

  • Emerson 3051S - page 12

    Quick Installation Guide 00825-0100-4801, Rev HA February 2008 Rosemount 3051S 12 S TEP 4 CONTINUED ... Power Supply The dc power supply should provide power with less than two percent ripple. The total resistance load is the sum of the resistance of the signal leads and the load resistance of the controller , indicator , and related pieces. Note t ...

  • Emerson 3051S - page 13

    Quick Installation Guide 00825-0100-4801, Rev HA February 2008 Rosemount 3051S 13 S TEP 5: V ERIFY C ONFIGURATION Use any HART -compliant master to communicate with and verify configuration of the 3051S. For the HART Diagnostics transmitter (option code DA1), DD revision 3051S HDT Dev . 1 Rev . 1 is required. A check ( ⻫ ) indicates the basic con ...

  • Emerson 3051S - page 14

    Quick Installation Guide 00825-0100-4801, Rev HA February 2008 Rosemount 3051S 14 S TEP 5 CONTINUED ... Function Fast Key Sequence Saturation Level Configura tion 1, 4, 2, 7, 8 Scaled D/A T rim (4–20 mA Output) 1, 2, 3, 2, 2 Scaled V ariable Configu ration 1, 4, 3, 4, 7 Self T est (T ransmitter) 1, 2, 1, 1 Sensor Information 1, 4, 4, 2 Sensor T e ...

  • Emerson 3051S - page 15

    Quick Installation Guide 00825-0100-4801, Rev HA February 2008 Rosemount 3051S 15 S TEP 6: T RIM THE T RANSMITTER T ransmitters are shipped fully calibrat ed per request or by the factory default of full scale (lower range value = zero, upper range value = upper range limit). Zero T rim A zero trim is a single-point adjustment used for compensating ...

  • Emerson 3051S - page 16

    Quick Installation Guide 00825-0100-4801, Rev HA February 2008 Rosemount 3051S 16 Using the T ransmitter Zero Adjustment Button Push and hold the zero adjustment button for at least two seconds but no longer than ten seconds. Figure 8. T ransmi tter Adjustme nt Buttons PlantWeb Junction Box Span Zero Span Zero 4801_QIG_RevHA.fm Page 16 Tuesday, Feb ...

  • Emerson 3051S - page 17

    Quick Installation Guide 00825-0100-4801, Rev HA February 2008 Rosemount 3051S 17 S AFETY I NSTRUMENTED S YSTEMS Additional Safety Instrumented System s information is available in the Rosemount 3051S reference manual (document number 00809-0100-4801). The manual is available electronically on www .rosemount.com or by cont acting an Emerson Process ...

  • Emerson 3051S - page 18

    Quick Installation Guide 00825-0100-4801, Rev HA February 2008 Rosemount 3051S 18 Inst allation No special installation is required in addition to the st andard installation practices outlined in this document. Always ensure a proper seal by installing the electr onics housing covers so that metal co ntacts metal . The loop should be designed so th ...

  • Emerson 3051S - page 19

    Quick Installation Guide 00825-0100-4801, Rev HA February 2008 Rosemount 3051S 19 NOTES 1. T ransmitter output is not safety-rated during the following: configuration changes, multidrop, loop test. Alternative means should be used to ensure process safety during transmitter configuration and maintenance activities. 2. DCS or safety logic solver sho ...

  • Emerson 3051S - page 20

    Quick Installation Guide 00825-0100-4801, Rev HA February 2008 Rosemount 3051S 20 Setting the alarm values and directi on is dependent on whether or not the hardware switch option is insta lled. Y ou can use a HAR T master or communicator to set the Alarm and Saturation values. Switches installed 1. If using a communicator , use the following fast ...

  • Emerson 3051S - page 21

    Quick Installation Guide 00825-0100-4801, Rev HA February 2008 Rosemount 3051S 21 Operation and Maintenance Proof T est and Inspection The following proof tests are recommended. Proof test result s and corrective actions taken must be documented at www .emersonprocess.com/rosemount/safety/certtechdocumentation. htm in the event that an error is fou ...

  • Emerson 3051S - page 22

    Quick Installation Guide 00825-0100-4801, Rev HA February 2008 Rosemount 3051S 22 Proof T est 2 This proof test, when combined with the Proof T est 1, will detect over 92% of DU failures not detected by the 3051S_C or 3051S_L automatic diagnostics, and over 95% of DU failures not detected by the 3051S_T automatic diagnostics. Required tools: HART h ...

  • Emerson 3051S - page 23

    Quick Installation Guide 00825-0100-4801, Rev HA February 2008 Rosemount 3051S 23 Reference Certification The 3051S Safety-Certified Pressure T ransmitter was designed, developed, and audited to be complia nt to IEC 61508 safety-certified SIL 2 Claim Limit. Specifications The 3051S Safety-Certified Pressure T ransmitter must be operated in accordan ...

  • Emerson 3051S - page 24

    Quick Installation Guide 00825-0100-4801, Rev HA February 2008 Rosemount 3051S 24 P RODUCT C ERTIFICATIONS Approved Manufacturing Locations Rosemount Inc. — Chanhassen, Minnesota USA Fisher-Rosemount GmbH & Co. — Wessling, Germany Emerson Process Management Asia Paci fic Private Limited — Singapore Beijing Rosemount Far East Instru ment C ...

  • Emerson 3051S - page 25

    Quick Installation Guide 00825-0100-4801, Rev HA February 2008 Rosemount 3051S 25 Hazardous Locations Certifications North American Certifications FM Approvals E5 Explosion proof for Class I, Division 1, Groups B, C, and D; dust-ignition proof for Class II a nd Class III, Division 1, Groups E, F , and G; hazardous locations; en closure T ype 4X, co ...

  • Emerson 3051S - page 26

    Quick Installation Guide 00825-0100-4801, Rev HA February 2008 Rosemount 3051S 26 European Certifications I1 A TEX Intrinsic Safety Certificate No.: BAS01A TEX1303X II 1 G EEx ia IIC T4 (T a = -60 °C to 70 °C) -HART/Remote Display/Quick Connect/HAR T Diagnostics 1 180 Special Conditions for Safe Use (X) 1. The apparatus, excluding the T ypes 3051 ...

  • Emerson 3051S - page 27

    Quick Installation Guide 00825-0100-4801, Rev HA February 2008 Rosemount 3051S 27 Special Conditions for Safe Use (x) The apparatus is not capable of withst anding the 500V insulation test required by Clause 9.1 of EN 50021: 1999. This must be taken into account when installing the app aratus. ND A TEX Dust Certificate No.: BAS01A TEX1374X II 1 D T ...

  • Emerson 3051S - page 28

    Quick Installation Guide 00825-0100-4801, Rev HA February 2008 Rosemount 3051S 28 E1 A TEX Flame-Proof Certificate No.: KEMA00A TEX2143X II 1/2 G EEx d IIC T6 (-50 °C ≤ T amb ≤ 65 °C) EEx d IIC T5 (-50 °C ≤ T amb ≤ 80 °C) V max = 42.4V 1 180 Special conditions for safe use (x) This device contains a thin wall diaphragm. Installation, ma ...

  • Emerson 3051S - page 29

    Quick Installation Guide 00825-0100-4801, Rev HA February 2008 Rosemount 3051S 29 Australian Certifications E7 SAA Explosion-Proof and Dust Ignition-Proof Certification No.: AUS Ex 3798X Ex d IIC T6 (T a = 60°C) IP66 DIP A21 T A T6 (T a = 60°C) IP66 Conditions for safe use (X) 1. It is a condition of safe use that each housing shall be connected ...

  • Emerson 3051S - page 30

    Quick Installation Guide 00825-0100-4801, Rev HA February 2008 Rosemount 3051S 30 I7 IECEx Intrinsic Safety Certificate No.: IECExBAS04.0017X Ex ia IIC T4 (T a = -60 °C to 70 °C) -HART/Remote Display/Quick Connect/HAR T Diagnostics IP66 Conditions for safe use (X) 1. The 3051S HART 4-20mA, 3051S F OUNDATION fieldbus, 3051S Profibus and 3051S FISC ...

  • Emerson 3051S - page 31

    Quick Installation Guide 00825-0100-4801, Rev HA February 2008 Rosemount 3051S 31 Combinations of Certifications S tainless steel certification t ag is pr ovided when optional approval is specified. Once a device labeled with multiple approval types is installed, it should not be reinst al led using any other approval types. Permanently mark the ap ...

  • Emerson 3051S - page 32

    Quick Installation Guide 00825-0100-4801, Rev HA February 2008 Rosemount 3051S 32 4801_QIG_RevHA.fm Page 32 Wednes day, Februa ry 20, 2008 9:16 AM ...

  • Emerson 3051S - page 33

    Quick Installation Guide 00825-0100-4801, Rev HA February 2008 Rosemount 3051S 33 4801_QIG_RevHA.fm Page 33 Wednes day, Februa ry 20, 2008 9:16 AM ...

  • Emerson 3051S - page 34

    Quick Installation Guide 00825-0100-4801, Rev HA February 2008 Rosemount 3051S 34 4801_QIG_RevHA.fm Page 34 Wednes day, Februa ry 20, 2008 9:16 AM ...

  • Emerson 3051S - page 35

    Quick Installation Guide 00825-0100-4801, Rev HA February 2008 Rosemount 3051S 35 4801_QIG_RevHA.fm Page 35 Wednes day, Februa ry 20, 2008 9:16 AM ...

  • Emerson 3051S - page 36

    Quick Installation Guide 00825-0100-4801, Rev HA February 2008 Rosemount 3051S 36 NOTES 4801_QIG_RevHA.fm Page 36 Tuesday, Februar y 26, 2008 12:17 PM ...

メーカー Emerson カテゴリー Pacemaker

Emerson 3051Sのメーカーから受け取ることができるドキュメントは、いくつかのグループに分けられます。その一部は次の通りです:
- #BRANDの図面#
- 3051Sの取扱説明書
- Emersonの製品カード
- パンフレット
- またはEmerson 3051Sの消費電力シール
それらは全部重要ですが、デバイス使用の観点から最も重要な情報は、Emerson 3051Sの取扱説明書に含まれています。

取扱説明書と呼ばれる文書のグループは、Emerson 3051Sの取り付け説明書、サービスマニュアル、簡易説明書、またはEmerson 3051Sのユーザーマニュアル等、より具体的なカテゴリーに分類されます。ご必要に応じてドキュメントを検索しましょう。私たちのウェブサイトでは、Emerson 3051Sの製品を使用するにあたって最も人気のある説明書を閲覧できます。

関連する取扱説明書

Emerson 3051Sデバイスの取扱説明書はどのようなものですか?
取扱説明書は、ユーザーマニュアル又は単に「マニュアル」とも呼ばれ、ユーザーがEmerson 3051Sを使用するのを助ける技術的文書のことです。説明書は通常、全てのEmerson 3051Sユーザーが容易に理解できる文章にて書かれており、その作成者はその分野の専門家です。

Emersonの取扱説明書には、基本的な要素が記載されているはずです。その一部は、カバー/タイトルページ、著作権ページ等、比較的重要度の低いものです。ですが、その他の部分には、ユーザーにとって重要な情報が記載されているはずです。

1. Emerson 3051Sの説明書の概要と使用方法。説明書にはまず、その閲覧方法に関する手引きが書かれているはずです。そこにははEmerson 3051Sの目次に関する情報やよくある質問、最も一般的な問題に関する情報を見つけられるはずです。つまり、それらはユーザーが取扱説明書に最も期待する情報なのです。
2. 目次。Emerson 3051Sに関してこのドキュメントで見つけることができる全てのヒントの目次
3. Emerson 3051Sデバイスの基本機能を使うにあたってのヒント。 Emerson 3051Sのユーザーが使い始めるのを助けてくれるはずです。
4. トラブルシューティング。Emerson 3051Sに関する最も重要な問題を診断し、解決するために役立つ体系化された手続き
5. FAQ。よくある質問
6. 連絡先。一人では問題を解決できない場合に、その国におけるEmerson 3051Sのメーカー/サービスへの連絡先に関する情報。

Emerson 3051Sについてご質問がありますか?

次のフォームを使用してください

見つけた説明書を読んでもEmerson 3051Sの問題を解決できない場合、下記のフォームを使用して質問をしましょう。ユーザーのどなたかがEmerson 3051Sで同様の問題を抱えていた場合、その解決方法を共有したいと考えるかもしれません。

画像のテキストを入力してください

コメント (0)