    www.rosemount.com ¢00825-0100-4801J¤ HART ® Quick Installation Guide 00825-0100-4801, Rev HA February 2008 Rosemount 3051S Rosemount 3051S Series Pressure T ransmitter with HART ® Protocol Rosemount 3051SF Series Flowmeter T ransmitter with HART ® Protocol © 2008 Rosemount Inc. All rights reserved. All marks property of owne r . Rosemount and ...

  • Emerson 3051S - page 2

    Quick Installation Guide 00825-0100-4801, Rev HA February 2008 Rosemount 3051S 2 Rosemount Inc. 8200 Market Boulevard Chanhassen, MN USA 55317 T (US) (800) 999-9307 T (Intnl) (952) 906-8888 F (952) 949-7001 Emerson Proces s Management GmbH & Co. OHG Argelsrieder Feld 3 82234 Wessling Germany T 49 (8153) 9390, F49 (8153) 939172 Emerson Proces s ...

  • Emerson 3051S - page 3

    Quick Installation Guide 00825-0100-4801, Rev HA February 2008 Rosemount 3051S 3 W ARNING Explosions could result in death or serious injury: Installation of this transmitter in an explosive environment must be in accordance with the appropriate local, national, and international standards, codes, and practices. Please review the approvals section ...

  • Emerson 3051S - page 4

    Quick Installation Guide 00825-0100-4801, Rev HA February 2008 Rosemount 3051S 4 S TEP 1: M OUNT THE T RANSMITTER Liquid Flow Applications 1. Place taps to the side of the line. 2. Mount beside or below the taps. 3. Mount the transmitter so that the drain/vent valves are oriented upward. Gas Flow Applications 1. Place taps in the top or side of the ...

  • Emerson 3051S - page 5

    Quick Installation Guide 00825-0100-4801, Rev HA February 2008 Rosemount 3051S 5 S TEP 1 CONTINUED ... Panel Mount Pipe Mount Coplanar ™ Flange T raditional Flange In-line Housings PlantWeb ™ Junction Box Remote Mount Display 4801_QIG_RevHA.fm Page 5 Tues day, Februa ry 26, 2008 12:17 PM ...

  • Emerson 3051S - page 6

    Quick Installation Guide 00825-0100-4801, Rev HA February 2008 Rosemount 3051S 6 S TEP 2: C ONSIDER H OUSING R OT ATION S TEP 3: S ET S WITCHES AND J UMPERS If alarm and security adjustment option is not installed, the transmitter will operate normally with the default alarm condition alarm high and the security off . T o improve field access to wi ...

  • Emerson 3051S - page 7

    Quick Installation Guide 00825-0100-4801, Rev HA February 2008 Rosemount 3051S 7 S TEP 4: C ONNECT W IRING AND P OWER U P Use the following steps to wire the transmitter: 1. Remove the housing cover labeled “Field T erminals.” 2. Connect the positive lead to the “+” terminal, and the negative lead to the “–” terminal. NOTE Do not conn ...

  • Emerson 3051S - page 8

    Quick Installation Guide 00825-0100-4801, Rev HA February 2008 Rosemount 3051S 8 S TEP 4 CONTINUED ... Remote Display Wiring and Power Up The Remote Mount Display and Interf ace system consists of a local transmitter and a remote mount LCD display assembly . The local 3051S transmitter assembly includes a Junction Box housing with a three position ...

  • Emerson 3051S - page 9

    Quick Installation Guide 00825-0100-4801, Rev HA February 2008 Rosemount 3051S 9 S TEP 4 CONTINUED ... Intrinsic Safety Consideration: The transmitter assembly with remote display has been approved with Belden 3084A DeviceNet cable. Alternate cable may be used as long as the transmitter with remote display and cable is configured according to the i ...

  • Emerson 3051S - page 10

    Quick Installation Guide 00825-0100-4801, Rev HA February 2008 Rosemount 3051S 10 S TEP 4 CONTINUED ... NOTE Wire colors provided on page 9 are per Belden 3084A DeviceNet cable. Wire color may vary depending on cable selected. Belden 3084A DeviceNet cable includes a ground shield. This shield must be connected to earth ground at either the SuperMod ...

  • Emerson 3051S - page 11

    Quick Installation Guide 00825-0100-4801, Rev HA February 2008 Rosemount 3051S 11 S TEP 4 CONTINUED ... 2. Place coupling nut over quick connect and wrench tighten to a maximum of 300 in-lb. (34 N-m). 3. T ighten the set screw using a 3 / 32 -in hex wrench. 4. Install Cordset/ Field Wireable Co nnectors onto the Quick Connect. Do not over tighten. ...

  • Emerson 3051S - page 12

    Quick Installation Guide 00825-0100-4801, Rev HA February 2008 Rosemount 3051S 12 S TEP 4 CONTINUED ... Power Supply The dc power supply should provide power with less than two percent ripple. The total resistance load is the sum of the resistance of the signal leads and the load resistance of the controller , indicator , and related pieces. Note t ...

  • Emerson 3051S - page 13

    Quick Installation Guide 00825-0100-4801, Rev HA February 2008 Rosemount 3051S 13 S TEP 5: V ERIFY C ONFIGURATION Use any HART -compliant master to communicate with and verify configuration of the 3051S. For the HART Diagnostics transmitter (option code DA1), DD revision 3051S HDT Dev . 1 Rev . 1 is required. A check ( ⻫ ) indicates the basic con ...

  • Emerson 3051S - page 14

    Quick Installation Guide 00825-0100-4801, Rev HA February 2008 Rosemount 3051S 14 S TEP 5 CONTINUED ... Function Fast Key Sequence Saturation Level Configura tion 1, 4, 2, 7, 8 Scaled D/A T rim (4–20 mA Output) 1, 2, 3, 2, 2 Scaled V ariable Configu ration 1, 4, 3, 4, 7 Self T est (T ransmitter) 1, 2, 1, 1 Sensor Information 1, 4, 4, 2 Sensor T e ...

  • Emerson 3051S - page 15

    Quick Installation Guide 00825-0100-4801, Rev HA February 2008 Rosemount 3051S 15 S TEP 6: T RIM THE T RANSMITTER T ransmitters are shipped fully calibrat ed per request or by the factory default of full scale (lower range value = zero, upper range value = upper range limit). Zero T rim A zero trim is a single-point adjustment used for compensating ...

  • Emerson 3051S - page 16

    Quick Installation Guide 00825-0100-4801, Rev HA February 2008 Rosemount 3051S 16 Using the T ransmitter Zero Adjustment Button Push and hold the zero adjustment button for at least two seconds but no longer than ten seconds. Figure 8. T ransmi tter Adjustme nt Buttons PlantWeb Junction Box Span Zero Span Zero 4801_QIG_RevHA.fm Page 16 Tuesday, Feb ...

  • Emerson 3051S - page 17

    Quick Installation Guide 00825-0100-4801, Rev HA February 2008 Rosemount 3051S 17 S AFETY I NSTRUMENTED S YSTEMS Additional Safety Instrumented System s information is available in the Rosemount 3051S reference manual (document number 00809-0100-4801). The manual is available electronically on www .rosemount.com or by cont acting an Emerson Process ...

  • Emerson 3051S - page 18

    Quick Installation Guide 00825-0100-4801, Rev HA February 2008 Rosemount 3051S 18 Inst allation No special installation is required in addition to the st andard installation practices outlined in this document. Always ensure a proper seal by installing the electr onics housing covers so that metal co ntacts metal . The loop should be designed so th ...

  • Emerson 3051S - page 19

    Quick Installation Guide 00825-0100-4801, Rev HA February 2008 Rosemount 3051S 19 NOTES 1. T ransmitter output is not safety-rated during the following: configuration changes, multidrop, loop test. Alternative means should be used to ensure process safety during transmitter configuration and maintenance activities. 2. DCS or safety logic solver sho ...

  • Emerson 3051S - page 20

    Quick Installation Guide 00825-0100-4801, Rev HA February 2008 Rosemount 3051S 20 Setting the alarm values and directi on is dependent on whether or not the hardware switch option is insta lled. Y ou can use a HAR T master or communicator to set the Alarm and Saturation values. Switches installed 1. If using a communicator , use the following fast ...

  • Emerson 3051S - page 21

    Quick Installation Guide 00825-0100-4801, Rev HA February 2008 Rosemount 3051S 21 Operation and Maintenance Proof T est and Inspection The following proof tests are recommended. Proof test result s and corrective actions taken must be documented at www .emersonprocess.com/rosemount/safety/certtechdocumentation. htm in the event that an error is fou ...

  • Emerson 3051S - page 22

    Quick Installation Guide 00825-0100-4801, Rev HA February 2008 Rosemount 3051S 22 Proof T est 2 This proof test, when combined with the Proof T est 1, will detect over 92% of DU failures not detected by the 3051S_C or 3051S_L automatic diagnostics, and over 95% of DU failures not detected by the 3051S_T automatic diagnostics. Required tools: HART h ...

  • Emerson 3051S - page 23

    Quick Installation Guide 00825-0100-4801, Rev HA February 2008 Rosemount 3051S 23 Reference Certification The 3051S Safety-Certified Pressure T ransmitter was designed, developed, and audited to be complia nt to IEC 61508 safety-certified SIL 2 Claim Limit. Specifications The 3051S Safety-Certified Pressure T ransmitter must be operated in accordan ...

  • Emerson 3051S - page 24

    Quick Installation Guide 00825-0100-4801, Rev HA February 2008 Rosemount 3051S 24 P RODUCT C ERTIFICATIONS Approved Manufacturing Locations Rosemount Inc. — Chanhassen, Minnesota USA Fisher-Rosemount GmbH & Co. — Wessling, Germany Emerson Process Management Asia Paci fic Private Limited — Singapore Beijing Rosemount Far East Instru ment C ...

  • Emerson 3051S - page 25

    Quick Installation Guide 00825-0100-4801, Rev HA February 2008 Rosemount 3051S 25 Hazardous Locations Certifications North American Certifications FM Approvals E5 Explosion proof for Class I, Division 1, Groups B, C, and D; dust-ignition proof for Class II a nd Class III, Division 1, Groups E, F , and G; hazardous locations; en closure T ype 4X, co ...

  • Emerson 3051S - page 26

    Quick Installation Guide 00825-0100-4801, Rev HA February 2008 Rosemount 3051S 26 European Certifications I1 A TEX Intrinsic Safety Certificate No.: BAS01A TEX1303X II 1 G EEx ia IIC T4 (T a = -60 °C to 70 °C) -HART/Remote Display/Quick Connect/HAR T Diagnostics 1 180 Special Conditions for Safe Use (X) 1. The apparatus, excluding the T ypes 3051 ...

  • Emerson 3051S - page 27

    Quick Installation Guide 00825-0100-4801, Rev HA February 2008 Rosemount 3051S 27 Special Conditions for Safe Use (x) The apparatus is not capable of withst anding the 500V insulation test required by Clause 9.1 of EN 50021: 1999. This must be taken into account when installing the app aratus. ND A TEX Dust Certificate No.: BAS01A TEX1374X II 1 D T ...

  • Emerson 3051S - page 28

    Quick Installation Guide 00825-0100-4801, Rev HA February 2008 Rosemount 3051S 28 E1 A TEX Flame-Proof Certificate No.: KEMA00A TEX2143X II 1/2 G EEx d IIC T6 (-50 °C ≤ T amb ≤ 65 °C) EEx d IIC T5 (-50 °C ≤ T amb ≤ 80 °C) V max = 42.4V 1 180 Special conditions for safe use (x) This device contains a thin wall diaphragm. Installation, ma ...

  • Emerson 3051S - page 29

    Quick Installation Guide 00825-0100-4801, Rev HA February 2008 Rosemount 3051S 29 Australian Certifications E7 SAA Explosion-Proof and Dust Ignition-Proof Certification No.: AUS Ex 3798X Ex d IIC T6 (T a = 60°C) IP66 DIP A21 T A T6 (T a = 60°C) IP66 Conditions for safe use (X) 1. It is a condition of safe use that each housing shall be connected ...

  • Emerson 3051S - page 30

    Quick Installation Guide 00825-0100-4801, Rev HA February 2008 Rosemount 3051S 30 I7 IECEx Intrinsic Safety Certificate No.: IECExBAS04.0017X Ex ia IIC T4 (T a = -60 °C to 70 °C) -HART/Remote Display/Quick Connect/HAR T Diagnostics IP66 Conditions for safe use (X) 1. The 3051S HART 4-20mA, 3051S F OUNDATION fieldbus, 3051S Profibus and 3051S FISC ...

  • Emerson 3051S - page 31

    Quick Installation Guide 00825-0100-4801, Rev HA February 2008 Rosemount 3051S 31 Combinations of Certifications S tainless steel certification t ag is pr ovided when optional approval is specified. Once a device labeled with multiple approval types is installed, it should not be reinst al led using any other approval types. Permanently mark the ap ...

  • Emerson 3051S - page 32

    Quick Installation Guide 00825-0100-4801, Rev HA February 2008 Rosemount 3051S 32 4801_QIG_RevHA.fm Page 32 Wednes day, Februa ry 20, 2008 9:16 AM ...

  • Emerson 3051S - page 33

    Quick Installation Guide 00825-0100-4801, Rev HA February 2008 Rosemount 3051S 33 4801_QIG_RevHA.fm Page 33 Wednes day, Februa ry 20, 2008 9:16 AM ...

  • Emerson 3051S - page 34

    Quick Installation Guide 00825-0100-4801, Rev HA February 2008 Rosemount 3051S 34 4801_QIG_RevHA.fm Page 34 Wednes day, Februa ry 20, 2008 9:16 AM ...

  • Emerson 3051S - page 35

    Quick Installation Guide 00825-0100-4801, Rev HA February 2008 Rosemount 3051S 35 4801_QIG_RevHA.fm Page 35 Wednes day, Februa ry 20, 2008 9:16 AM ...

  • Emerson 3051S - page 36

    Quick Installation Guide 00825-0100-4801, Rev HA February 2008 Rosemount 3051S 36 NOTES 4801_QIG_RevHA.fm Page 36 Tuesday, Februar y 26, 2008 12:17 PM ...

Производитель Emerson Категория Pacemaker

Документы, которые мы получаем от производителя устройства Emerson 3051S мы можем разделить на несколько групп. Это в частности:
- технические чертежи Emerson
- инструкции обслуживания 3051S
- паспорта изделия Emerson
- информационные брошюры
- энергетические этикетки Emerson 3051S
Все из них важны, однако самую важную информацию с точки зрения пользователя мы найдем в инструкции обслуживания Emerson 3051S.

Группа документов, определяемая как инструкции обслуживания, делится также на более подробные типы, такие как: Инструкции монтажа Emerson 3051S, инструкции обслуживания, короткие инструкции или инструкции пользователя Emerson 3051S. В зависимости от потребностей, Вам необходимо поискать требуемый документ. На нашем сайте Вы можете просмотреть самую популярную инструкцию использования изделия Emerson 3051S.

Похожие инструкции обслуживания

Полная инструкция обслуживания устройства Emerson 3051S, как должна выглядеть?
Инструкция обслуживания, определяемая также как пособие пользователя, или просто "руководство" - это технический документ, цель которого заключается в использовании Emerson 3051S пользователями. Инструкции пишет, как правило технический писатель, языком, доступным для всех пользователей Emerson 3051S.

Полная инструкция обслуживания Emerson, должна заключать несколько основных элементов. Часть из них менее важная, как например: обложка / титульный лист или авторские страницы. Однако остальная часть, должна дать нам важную с точки зрения пользователя информацию.

1. Вступление и рекомендации, как пользоваться инструкцией Emerson 3051S - В начале каждой инструкции, необходимо найти указания, как пользоваться данным пособием. Здесь должна находится информация, касающаяся местонахождения содержания Emerson 3051S, FAQ и самых распространенных проблем - то есть мест, которые чаще всего ищут пользователи в каждой инструкции обслуживания
2. Содержание - индекс всех советов, касающихся Emerson 3051S, которое найдем в данном документе
3. Советы по использованию основных функций устройства Emerson 3051S - которые должны облегчить нам первые шаги во время использования Emerson 3051S
4. Troubleshooting - систематизированный ряд действия, который поможет нам диагностировать а в дальнейшем очередность решения важнейших проблем Emerson 3051S
5. FAQ - чаще всего задаваемые вопросы
6. Контактные данные Информация о том, где искать контактные данные производителя / сервисного центра Emerson 3051S в данной стране, если самостоятельно не получится решить проблему.

У вас вопрос, касающийся Emerson 3051S?

Воспользуйтесь формуляром, находящимся ниже

Если с помощью найденной инструкции Вы не решили свою проблему с Emerson 3051S, задайте вопрос, заполнив следующий формуляр. Если у какого то из пользователей была похожая проблема с Emerson 3051S со всей вероятностью он захочет поделиться методом ее решения.

Перепишите текст с картинки

Комментарии (0)